Vericom Micro Data Center Instruction manual

Micro Data Center –Technical Data Manual
1
Micro Data Center
Technical Data Manual

Micro Data Center –Technical Data Manual
2
Contents
1. INTRODUCTION....................................................................................................................................3
1.1 Product Introduction..............................................................................................................................3
2.1 Major Components Introduction.............................................................................................................5
3.1 Environmental Requirements .................................................................................................................6
2. TECHNLCAL DATA.................................................................................................................................7
3. INSTALLATION DATA............................................................................................................................9

Micro Data Center –Technical Data Manual
3
1.
INTRODUCTION
1.1 Product Introduction
A Micro data center is a standalone rack-level system containing all the components of a 'traditional' data
center including precision cooling, UPS power supply, power backup, cabinets, security, and monitoring systems.
Their size, versatility and plug & play features make them an ideal solution for use in remote locations, branch
offices, or even for temporary use in high risk zones.
Figure 1-1 Exterior Layout
1
Glass door
2
Monitoring host
3
Cable entry holes

Micro Data Center –Technical Data Manual
4
Figure 1-2 Internal Layout
1
Leveling feet
2
castors
3
Air Conditioner
4
Battery Pack
5
UPS
6
Power distribution module
7
Mechanical lock
8
Backlight
9
Temperature and Humidity
Sensor
10
Switch
11
Lighting
12
Smoke Sensor
13
PDU
14
Water Leakage Rope

Micro Data Center –Technical Data Manual
5
2.1 Major Components Introduction
⚫UPS——The UPS has two main functions, one is to optimize the input power supply to provide clean power
to the critical load equipment, the second is the use of battery backup for the critical load equipment after
the main power supply fails or drops to an unacceptable level.
⚫Battery——When the main power supply is normal, power is stored in battery bank. In the event of the
electricity failure, the batteries are discharged through the UPS to critical load equipment.
⚫Air conditioner——Provides stable temperature, humidity and clean air for critical load equipment.
⚫Power distribution module——Power distribution and monitoring for critical load and infrastructure
equipment.
⚫Monitoring system——The monitoring host is the information center of entire device and the hub of
human-computer interaction. It monitors, controls, and provides alarms for the entire system, including the
UPS, air conditioner, power distribution module, temperature and humidity sensors, and other intelligent
equipment. It also monitors and provides alarms for the door switch status, leak detection status, and other
dry contacts. All information can be monitored remotely by network (for details refer to the monitoring
system chapter).
⚫Blank panel——Installed in unused rack spaces to maintain hot and cold air isolation and improve the
operating efficiency of the air conditioning system.
⚫Temperature and humidity sensor——Detects the cold aisle temperature and humidity of the cabinet.
⚫Light——When the cabinet door is opened, the lights are automatically lit to facilitate operation of the
internal equipment.
⚫Door switch——Detects the door status (open or closed) and provides the corresponding signal to the
monitoring host; also controls the lights.
⚫Smoke sensor——Detects smoke inside the cabinet; if smoke is detected, an alarm is sounded and an alarm
signal is sent to the monitoring host.
⚫Wiring channel——Arrange the rear wiring of the monitoring host, improve the maintenance convenience
and appearance experience.
⚫Electromagnet——The core device of automatic doors, the electromagnet automatically opens the doors if
a high temperature is detected.
⚫Castors——During initial installation, allows the device to roll over smooth, hard surfaces into the final
position.
⚫Leveling feet——After the device is placed into the final position, leveling feet are used to level the device
on uneven surfaces. If necessary, adjust the four leveling feet to raise the device to an appropriate level so
that the copper pipe, cable and drain pipe can be routed underneath.

Micro Data Center –Technical Data Manual
6
3.1 Environmental Requirements
Operating Environment
Table 1-1 Product Operating Environment
Item
Indoor
Outdoor
Temperature
18℃~40℃
Air cooled: -20℃~+55℃
Humidity
20% ~80%
—
Altitude
<1000m (if >1000m, derating capacity of air conditioner and UPS will be 6% per
kilometer)
Power
Voltage 230V/380V±10% Frequency 50Hz±2Hz
Storage Environment
Table 1-2 Product Storage Environment
Item
Requirements
Environment
Clean (no dust), good ventilation
Temperature
-40℃~+60℃
Humidity
5%RH~95%RH without condensation
Duration
less than 6 months, (If more than 6 months, please contact Vericom technical support)

Micro Data Center –Technical Data Manual
7
2.
TECHNLCAL DATA
Table 2-1 Vericom Micro Data Center Technical Specifications
Model
VRMDC3000-R3G-U10KVA1-C4KW2-M-PD6
Available Space
97U
Width
per Cabinet
600
Depth
per Cabinet
1200
Height
per Cabinet
2000
Cabinet System
Load-
bearing
1500kg
Aisle
Containment
Hot and cold aisle containment
Front Door
Single glass door
Rear Door
Double iron door
Power Supply and Distribution System
Power Input
220V/50Hz/1Ph
Power Output
220V/50Hz/1Ph
UPS (kVA)
10
UPS Qty
1
UPS Configuration
N
UPS Output PF
0.9
UPS Efficiency
93%
UPS Installation
Type
Rack-mount
Battery Pack
(Standard)
3*12V/9AH/16pcs

Micro Data Center –Technical Data Manual
8
Long Time Delay
Battery
Optional
Lightning/Surge
Protection
C-Class
Manual
Maintenance
Bypass
Support
PDU Type
Basic(16A)
PDU Qty
6
PDU interface
(C13*12+C19*4)
Cooling System
Cooling Capacity
(KW)
2*4.2
Configuration
N, Support teamwork control
Sensible Heat
Ratio
95%
Maximum
Airflow- -m3/h
800
Cooling Type
DX cooling
Installation Type
Rack-mount
Monitoring System
Monitoring
Function
Touch screen display
Remote access
Temperature and Humidity
Detection
UPS monitoring
Power distribution module
monitoring
Air conditioning monitoring
Smoke detection
Leakage detection
Door status detection

Micro Data Center –Technical Data Manual
9
3.
INSTALLATION DATA
Table 3-1 Micro Data Center Product Dimension
Model
Width-mm
Depth-mm
Height-mm
VRMDC3000-R3G-
U10KVA1-C4KW2-
M-PD6
1800
1200
2050
Table 3-2 Dimension of Outdoor Unit
Model
Width-mm
Depth-mm
Height-mm
D06WP13VSG-04-S2
830
325
540
Table 3-3 Dimension and Gross Weight of Outdoor Unit After Packing
Model
Dimension after packing(mm)W×D×H
Gross Weight(kg)
D06WP13VSG-04-S2
900×400×600
32
[Remark: L-Length, W-Width, H-Height]
Table 3-4 Dimension and Gross Weight of Indoor Unit After Packing
Model
Dimension after
packing(mm)W×D×H
Synthesize cabinet/subsidiary
cabinet Gross Weight(kg)
VRMDC3000
N*W680XD1280XH2080(With
pallet W700XD1280XH2210)
380/140
[Remark: N-Quantity of cabinets, W-Width, D-Depth, H-Height, weight is for reference only, and the weight will
vary according to the configuration]