Carbon Monoxide Transmitter
and Fan Controller
Installer’s Specifications
Sensor Digitally proled Metal Oxide Semiconductor (MOS)
Sensor Life 5-year expected sensor element life, replaceable
Supply Power 15-30VDC, 24VAC, 250mA
Detection Range 0 to 200 ppm
Analog Output User selectable 100 ppm F.S. or 200ppm F.S.
Relay Setpoint 25ppm
Relay Output N.O. Form A (SPST) 8A@30VAC/VDC; (Use with N.C. contactor)
High Limit Setpoint 100ppm for 30 minutes
High Limit Alarm Audible, 85dB, resets below 100ppm (solid-state contact for A ver)
LED Indicators Normal=Green LED; Call for ventilation = Red LED;
High-limit alarm = Flashing Red LED;
Sensor life has expired = Flashing Green LED
Operating Environment -20° to 50°C (-4°to 122°F); 0 to 90% RH non-condensing
Coverage 5000 sq ft typical
G SerieS G SerieS
Dimensions
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
ProDuct iDentification
quick install
Lock out all power supplies prior to installation
Select a location for the sensor in a secure area where it will be accessible only to
qualied service personnel The G Series sensor should be installed centrally in the
parking structure near the main trac paths but away from outside air vents and
excessive drafts Mount the unit securely to a wall or column at a height of about
ft m from the oor
Connect wiring as shown in the Wiring Diagram
Apply power to the unit A green LED on the circuit board indicates proper
operation of the power supply
Note: Coverage is NOT dependant on the sensor Coverage is a function of the building structure
and air ow patterns A minimum of one sensor for sq ft is recommended Wide open areas
where the air is well mixed may require a few sensors
2.4"
(55 mm)
2.5"
(63 mm)
0.9" dia.
(22 mm)
4.5”
(114 mm) 4"
(102 mm)
5.0"
(127 mm)
G
D = Duct mount
W = Wall mount
Enclosure Auxiliary Alarm OutputOutput
A = Auxiliary Contact
X = None
= StandardV = Field-selectable,
0-5/0-10VDC
M =4-20mA
R = Relay only
S
US or EU