Veris Industries TWS Series User manual

Installation Guide
Temperature
Z204455-0E Page 1 of 4 ©2014 Veris Industries 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed byVeris Industries for any consequences arising out of the
use of this material.
Product Identification
Product Overview
The TWS analog series measures the temperature of the air inside a room. Devices are designed for use in hospital
rooms, laboratories, and other spaces that require precise environmental control. The keypad allows control of
setpoint values. The slide switch position determines the output type (amp or volt). To maintain accuracy, keep
vents clear of dust, debris, etc. The TWS is warranted for period of ve years.
TWS Series
Wall Mount with Analog Setpoints, LCD and
Thermostat Control
Setpoint
= Analog
TWS
Temp Cal
Certificate
0 = None
1 = 1 point Cal
Validation
2 = 2 point Cal
Validation
Option
S
= CE
A
Specifications
Input Power 15-30VDC/24VAC, 100mA max.
Outputs Switch-selectable amp or volt
If volt is selected, the configuration menu allows selection between
0-5V or 0-10V
Physical UL 94-V-O fire retardant ABS
Temperature Accuracy ±0.5°C (±1°F)
Operating Humidity Range 0-100% RH (non-condensing)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Analog Output Scaling 10° to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F), menu
selectable*
Calibration Offset Adjustable ±9.9° (C or F) in 0.1° increments
Setpoint Range
Minimum to Full Scale in 1° (C or F) increments
* If the 0° to 50°C (32° to 122°F) scaling range is selected, the device’s operating temperature range still applies.
One side of the transformer secondary is connected to the signal common, so an isolation transformer or
dedicated power supply may be required.
RTD/Thermistors in wall packages are not compensated for internal heating of the product.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper
surge protection (EN 61000-6-1:2007 specification requirements).
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
I = 1k Balco (nickel-iron) RTD
J = 10k Dale,Thermistor
K = 10k w/11k shunt,Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
Q = 1uA/C, Linitemp
R = 10k US, Thermistor
S = 10k 3A 221, Thermistor
T = 100k, Thermistor
U = 20k“D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor
CC= 15k, Thermistor

Z204455-0E Page 2 of 4 ©2014 Veris Industries 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Temperature
TWSSeries TM
Dimensions
1.2"
(29 mm)
3.5"
(89 mm)
4.75"
(121 mm)
- +
Installation Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Locate the tab at the top of the sensor housing. Using only the minimum required force, press this tab down and pull the cover
outward from the top. Set the cover aside.
Housing, Top View
Tab
2. Remove the backplate by unfastening the sensor from the bottom of the backplate and pivoting the sensor outward.
3. Punch out wire opening in the backplate.
4. Position the backplate vertically on the wall, 4 ½ feet (1.4 m) above the oor. Locate away from windows, vents, and other
sources of draft. If possible, do not mount on an external wall, as this might cause inaccurate temperature readings.

Z204455-0E Page 3 of 4 ©2014 Veris Industries 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Temperature
TWSSeries TM
5. Mount the backplate onto the wall using the screws provided.
Five screwholes available; use a minimum
of two for secure mounting.
6. Wire the backplate.
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
Temp Input
Temp Setpoint Input
Thermistor/RTD Input
Thermistor/RTD Input
-
-
-
+
Temp Output
GND
Temp Setpoint Output
RTD/Thermistor Output
RTD/Thermistor Output
7. Install and congure the sensor.
NOTICE
RISK OF EQUIPMENT DAMAGE
Ensure that the output selection is correct before applying power.
Failure to follow these instructions may result in permanent
equipment damage.
TEMP
SENSOR
AMP VOLT
YES
RUN
CAL
NO
TEMP
–
Minus Select Plus
+
RUN/CAL Jumper:
CAL Mode - allows full access to all features.
RUN Mode - allows access to relay setpoints ONLY.
TEMP YES/NO Jumper:
YES - allows user to change temp setpoint
NO - user can NOT change temp setpoint
8. When the installation is complete, replace the cover and snap it into position.
Installation (cont.)

Z204455-0E Page 4 of 4 ©2014 Veris Industries 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Temperature
TWSSeries TM
Temperature calibration allows for a calibration oset of ±9.9° (C or F) at the user’s discretion. To calibrate temperature, move the
RUN/CAL jumper to CAL position.
Calibration
Instructions
Menu Options
O U T P U T
0 - 1 0 V
T E M P S E T
+ 5 0 + 9 5
C A L T
+ 0 . 0 F
6 8 . 5 º F
U N I T S
* º F º C
S E T P O I N T
7 0 F
S E T P O I N T
7 0 F
SETPOINT MODE
(Enter by any keypress when
RH Yes/No jumper is in Yes position)
NORMAL MODE
Output Scaling
(does not aect LCD display)
Only for switch in
Volts position
CONFIG/CAL MODE
(Enter by any keypress when
Run/Cal jumper is in CAL position)
Press +/- to change, press Select button to select
Press +/- to change, press Select button to select
Options are 50-95˚F (10-35˚C) or 32-122˚F (0-50˚C)
Press +/- to change, press Select button to select
Press +/- to change, press Select button to select
Setpoint in ˚C if Celsius units are selected
Press +/- to change, press Select button to select
Setpoint in ˚C if Celsius units are selected
Press +/- to change, press Select button to select
Setpoint in ˚C if Celsius units are selected
- +
Display screen
Scroll down
Select
Scroll up