Veris HT Series User manual

Installation Guide
Humidity
Z202979-0U Page 1 of 7 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed byVeris Industries for any consequences arising out of the
use of this material.
Product Identification
Product Overview
The HT relay series has dual outputs to measure temperature and humidity of the air inside a room. They are
designed for use in hospital rooms, laboratories, and other spaces that require precise environmental control.
Two separate relays control the setpoints for heating and cooling when in thermostat mode or humidifying and
de-humidifying when in humidistat mode. The slide switch position determines the output type (amp or volt). To
maintain accuracy, keep vents clear of dust, debris, etc. The HT is warranted for period of ve years.
HT Series
Wall Mount with Relay Setpoints, LCD, and
Humidistat and Thermostat Control
SetpointAccuracy NIST
= Relay1 = 1%
2 = 2%
3 = 3%
5 = 5%
HT
Temp Cal
Certificate
0 = None
1 = 1 point Cal
Validation
2 = 2 point Cal
Validation
Option
N = NIST (1 & 2% only)
X = No (2, 3, 5% only)
S
= CE
R
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
I = 1k Balco (nickel-iron) RTD
J = 10k Dale,Thermistor
K = 10k w/11k shunt,Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
Q = 1uA/C, Linitemp
R = 10k US, Thermistor
S = 10k 3A 221, Thermistor
T = 100k, Thermistor
U = 20k“D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor
CC= 15k, Thermistor

Z202979-0U Page 2 of 7 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HTSeries TM
Input Power 15 to 30VDC/24VAC, 100mA max.
Outputs Switch-selectable amp or volt (switch affects both temp and
humidity outputs)
If volt is selected, the configuration menu allows selection
between 0-5V or 0-10V
Setpoint Relays 2 Form C (SPDT), 1A 30VDC, resistive, 30W max
RH Sensor* Digitally profiled thin-film capacitive (32-bit mathematics)
U.S. Patent 5,844,138
RH Accuracy at 25°C from 10-80% RH**
(Multi-point Calibration NIST traceable)
±1% at 12-40% RH in mA output mode;
±1% at 30% RH in voltage output mode
Reset Rate†24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Hysteresis RH: 1.5% (typical)
Deadband RH: 1 to 10% in 1% increments
Temp: 1 to 10°F or 1 to 5°C in 1° increments
Linearity Included in Accuracy spec.
Operating Humidity Range 0-100% RH (non-condensing)
Temperature Coefficient ± 0.1%RH/ °C above or below 25°C (typical)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Accuracy ± 1.0°C ( ± 1.8°F)
Analog Output Scaling RH: 0-100% RH; Temp: 10° to 35°C (50° to 95°F) or 0° to 50°C
(32° to 122°F) menu selectable‡
Calibration Offset RH: Adjustable ±9.9% in 0.1% increments;
Temp: Adjustable ±9.9° (C or F) in 0.1° increments
Setpoint Range RH: 10-80% RH in 1% increments;
Temp: Minimum to Full Scale in 1° increments
* The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.
** Accuracy is specified with 24 VDC supplied power with rising humidity.
†Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
‡If the 0° to 50°C (32° to 122°F) scaling range is selected, the device’s operating temperature range still applies.
One side of the transformer secondary is connected to the signal common, so an isolation transformer or
dedicated power supply may be required.
RTD/Thermistors in wall packages are not compensated for internal heating of the product.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper
surge protection (EN 61000-6-1:2007 specification requirements).
Specifications
Dimensions
1.2"
(29 mm)
3.5"
(89 mm)
4.75"
(121 mm)
- +

Z202979-0U Page 3 of 7 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HTSeries TM
Installation
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Locate the tab at the top of the sensor housing. Using only the minimum required force, press this tab down and pull the cover
outward from the top. Set the cover aside.
Housing, Top View
Tab
2. Remove the backplate by unfastening the sensor from the bottom of the backplate and pivoting the sensor outward.
3. Punch out wire opening in the backplate.
4. Position the backplate vertically on the wall, 4 ½ feet (1.4 m) above the oor. Locate away from windows, vents, and other
sources of draft. If possible, do not mount on an external wall, as this might cause inaccurate temperature readings.
5. Mount the backplate onto the wall using the screws provided.
Five screwholes available; use a minimum
of two for secure mounting.

Z202979-0U Page 4 of 7 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HTSeries TM
6. Wire the backplate.
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
RH Input
Temp Input
Thermistor/RTD Input
Thermistor/RTD Input
Heat/Humidify Alarm
Cool/De-Humidify Alarm
Comm alarm
-
-
-
+
RH Output
GND
Heat/Hum. Alarm
Comm Alarm
Temp output
Thermistor/RTD
Thermistor/RTD
Cool/De-Hum. Alarm
7. Install and congure the sensor.
NOTICE
RISK OF EQUIPMENT DAMAGE
Ensure that the output selection is correct before applying power.
Failure to follow these instructions may result in permanent
equipment damage.
RH
SENSOR TEMP
SENSOR
RH
YES
AMP VOLT
NO YES
RUN
CAL
NO
TEMP
–
Minus Select Plus
+
RUN/CAL Jumper:
CAL Mode - allows full access to all features.
RUN Mode - allows access to relay setpoints ONLY.
RH YES/NO Jumper:
YES - allows user to change RH setpoint
NO - user can NOT change RH setpoint
TEMP YES/NO Jumper:
YES - allows user to change temp setpoint
NO - user can NOT change temp setpoint
8. When the installation is complete, replace the cover and snap it into position.
Installation (cont.)

Z202979-0U Page 5 of 7 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HTSeries TM
1. Temperature calibration allows for a calibration oset of ±9.9° (C or F), at the user’s discretion.
2. Relative humidity allows for a calibration oset of ±9.9% RH, at the user’s discretion.
RH and temperature can be eld calibrated by moving the RUN/CAL jumper to the CAL position.
Calibration
Instructions
- +
Display screen
Scroll down
Select
Scroll up
Normal Operation
4 5 . 5 % R H
6 8 . 5 º F
NORMAL MODE
Temperature Selection
Use the (+) and (-) buttons to scroll to the Thermostat mode:
S E T P O I N T
7 0 F
Press +/- to change the setpoint value.
When the desired setpoint appears,
press the Select button to select.
The setpoint is in ˚C if Celsius units are selected.
Humidity Selection
Use the (+) and (-) buttons to scroll to the Humidistat mode:
Press +/- to change the setpoint value.
When the desired setpoint appears,
press the Select button to select.
S E T P O I N T
4 5 % R H
Operation
Instructions

Z202979-0U Page 6 of 7 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HTSeries TM
Menu Options
O U T P U T
0 - 1 0 V
U N I T S
* º F º C
CONFIG/CAL MODE
(Enter by any keypress when
Run/Cal jumper is in CAL position)
4 5 . 5 % R H
6 8 . 5 º F
NORMAL MODE
R E L A Y S
* R H T
C A L T
+ 0 . 0 F
C A L R H
+ 0 . 0 %
T E M P S E T
+ 5 0 + 9 5
S E T P O I N T
4 5 % R H
S E T P O I N T
7 0 F
- OR -
D E A D B A N D
5 % R H
D E A D B A N D
4 F
Output Scaling
(does not aect LCD display)
Only for switch in
Volts position
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Setpoint in ˚C if Celsius units are selected.
Press +/- to change, press Select button to select.
Deadband in ˚C if Celsius units are selected.
Press +/- to change, press Select button to select.
Setpoint in ˚C if Celsius units are selected.
Press +/- to change, press Select button to select.
Options are 10˚ to 35˚C (50˚ to 95˚F) or 0˚ to 50˚C (32˚ to 122˚F).

Z202979-0U Page 7 of 7 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HTSeries TM
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Disconnect power to the unit.
2. Remove the faceplate.
3. Remove the HS element by gently pulling from the pin connector.
4. Place a new HS element onto the pin connector. Orient as shown, or the unit will not function. Ensure that the four HS pin holes
are inserted fully onto the unit pin connectors.
Top
Side
Bottom
Side
5. Replace the faceplate.
Replacing the
HSElement
Table of contents
Other Veris Control Panel manuals
Popular Control Panel manuals by other brands

Truma
Truma CP plus operating instructions

Ziton
Ziton zp1-f Series Quick installation guide

Honeywell
Honeywell MS-10UD Series manual

Crowcon
Crowcon Gasmaster 1 Installation, commissioning and maintenance instructions

Miranda
Miranda RCP-200 Guide to installation and operation

Crow
Crow RUNNER 8/64 Installation & programming guide

Schaudt
Schaudt DT 220 B instruction manual

Bosch
Bosch Solution 6+6 Wireless On/Off Quick reference guide

Bosch
Bosch D9112B Program entry guide

MuxLab
MuxLab 500816-IP-V2 Installation and operation manual

Harris
Harris NUCLEUS Installation and operation manual

Generac Power Systems
Generac Power Systems H-100 Operation manual