Installation Guide
Humidity
HTSeries TM
Input Power 15 to 30VDC/24VAC, 100mA max.
Outputs Switch-selectable amp or volt (switch affects both temp and
humidity outputs)
If volt is selected, the configuration menu allows selection
between 0-5V or 0-10V
Setpoint Relays 2 Form C (SPDT), 1A 30VDC, resistive, 30W max
RH Sensor* Digitally profiled thin-film capacitive (32-bit mathematics)
U.S. Patent 5,844,138
RH Accuracy at 25°C from 10-80% RH**
(Multi-point Calibration NIST traceable)
±1% at 12-40% RH in mA output mode;
±1% at 30% RH in voltage output mode
Reset Rate†24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Hysteresis RH: 1.5% (typical)
Deadband RH: 1 to 10% in 1% increments
Temp: 1 to 10°F or 1 to 5°C in 1° increments
Linearity Included in Accuracy spec.
Operating Humidity Range 0-100% RH (non-condensing)
Temperature Coefficient ± 0.1%RH/ °C above or below 25°C (typical)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Accuracy ± 1.0°C ( ± 1.8°F)
Analog Output Scaling RH: 0-100% RH; Temp: 10° to 35°C (50° to 95°F) or 0° to 50°C
(32° to 122°F) menu selectable‡
Calibration Offset RH: Adjustable ±9.9% in 0.1% increments;
Temp: Adjustable ±9.9° (C or F) in 0.1° increments
Setpoint Range RH: 10-80% RH in 1% increments;
Temp: Minimum to Full Scale in 1° increments
* The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.
** Accuracy is specified with 24 VDC supplied power with rising humidity.
†Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
‡If the 0° to 50°C (32° to 122°F) scaling range is selected, the device’s operating temperature range still applies.
One side of the transformer secondary is connected to the signal common, so an isolation transformer or
dedicated power supply may be required.
RTD/Thermistors in wall packages are not compensated for internal heating of the product.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper
surge protection (EN 61000-6-1:2007 specification requirements).