Installation Manual
AC41 — 4-Door Controller

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
AC41 Overview
INTRODUCTION
In the Box What You’ll Need
•1 AC41 Door Access Controller (ACU)
• 1 Wall Mount Plate
• 1 T10 Security Torx Screwdriver
• 4 Mounting Screws and Wall Anchors
• A working wired Internet connection over
Ethernet
•A smartphone or laptop
• A #2 Phillips screwdriver or power drill
with a #2 Phillips driver bit
• 5/16 inch (7.9mm) drill bit for wall
anchors
• 5/32 inch (4mm) drill bit for pilot holes
• A Cat5 or Cat6 Ethernet cable
Door security screw
Power cable exit
Access control cable exit
Wall mount
Cable management box
Door context switch
Access control cable exitPower cable exit
Wall mount security screws
AC41
1

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
AC41 Details
INTRODUCTION
AC41 Testing Interface Status LED
To make installation easier, the AC41 has four buttons
to help test or emulate different events.
• Door: Pressing the “Door” button will cycle which
door is selected for testing.
• Trigger Lock: Trigger the lock relay on the selected
door. When triggered, the LED will be off.
• Emulate DPI: Emulate the door position indicator.
When a door is closed, the LED is on.
• Emulate REX: Emulate the request-to-exit. When
the REX is triggered, the LED is on.
Flashing orange
Controller is updating rmware
Solid blue
Controller is managing doors and
connected to the server
Solid orange
Controller is on and booting up
Flashing blue
Controller is managing doors, but
cannot reach the server
Toggle between doors Active door
Status LED
Door status LED
Dry / 12V / 24V
Selection switch
Power Dual USB 2.0
Dual EthernetPower supply monitor
Test Lock
Test DPI
Tes t RE X
Removable
cassette
2

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
AC41 Cassettes
INTRODUCTION
Getting Started
These removable cassettes are designed to make the installation and cabling process quick
and easy.
• Remove all 5 cassettes from their packaging and insert into the AC41.
• Ensure the USB-C and other mating features are aligned for correct tment.
• Once the AC41 has been mounted, simply remove the cassette, install the necessary wires
into the cassette, and plug the cassette back into the AC41.
3

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
Verkada AC41 is capable of supporting Verkada Readers over RS-485 and standard wiegand
readers. The following diagram shows the wire types that are recommended for use with the
Verkada AC41.
We recommend using one twisted pair for GND and VIN (power) and one twisted pair for the data (D0/D1 or A/B).
Shield Wiring
With the AC41, you must use shield wiring:
• Connect one end of the drain wire into the GND input of the AC41 cassette.
• The drain wire and the GND wire should simultaneously share the COM [Common] port on the cassette.
• The other end of the drain wire shouldn’t be connected to anything.
Recommended Wiring
INTRODUCTION
Signal AWG Twisted Pair Conductor Shielded Max Length
RS485 Comm - two wire 24 Yes Yes 4000 ft
Power (22 Gauge) 22 Yes Yes 600 ft
Power (18 Gauge) 18 Yes Yes 1500 ft
Request-to-Exit 22/18 Yes Yes 1500 ft
Door Contact 22 Yes Yes 1500 ft
Reader Option 1 (22 AWG) 22 Yes Yes 250 ft
Reader Option 2 (20 AWG) 20 Yes Yes 300 ft
Reader Option 3 (18 AWG) 18 Yes Yes 500 ft
Required Network Settings
An Ethernet connection with DHCP must be used to connect the AC41 to the Local Area Network (LAN). You also
need to congure rewall settings to communicate with the AC41.
• TCP port 443
• UDP port 123 (NTP time synchronization)
4

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
Disconnect the Mount
To remove the wall mount, unscrew
the two security torx screws from the
inside.
Remove the Closet
Once the security screws are fully
removed, slide the wall mount down
and away from the main enclosure.
This section takes you through how to mount the AC41.
Install the Mount
Drill four 5/16” Ø holes into the wall.
Insert the drywall anchors into the
holes. Fasten the mount plate onto
the wall by installing the mounting
screws into the wall anchors.
Drill four 5/32” Ø holes into the wall.
Fasten the mount plate onto the wall
by installing the mounting screws into
the pilot holes.
Mounting
INSTALLATION
1
3
2
5

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
Install the Closet
Place the sheet metal enclosure over
and onto the mounting plate tabs.
Mounting
INSTALLATION
Secure the Closet
Fasten the two security torx screws
to secure the enclosure to the
mounting plate.
4
5
6

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
Fail secure and fail safe are ways of conguring
locking hardware:
•Fail secure hardware locks when power is
interrupted. Usually uses NO (Normally Open
Conguration)
•Fail safe hardware unlocks when power
is interrupted. Usually uses NC (Normally
Closed conguration)
This section takes you through how to connect a door to your AC41.
The AC41 comes equipped with a Form C relay that can be driven dry or wet. AC41 is rated to power 12V locks up to
700mA and 24V locks up to 350mA.
Connecting a Door
Before Getting Started
Wiring Fail Secure and Fail Safe Locking Hardware
INSTALLATION
WARNING!
Ensure power is disconnected from the AC41 and locking hardware before wiring readers and other devices.
Failure to do so can damage the AC41.
Remove the Cassettes
Begin by removing a door cassette from the
AC41 by lifting it from the side tabs.
1
2
Keep in mind that some door strikes can be wired as
fail safe and some electromagnetic locks can be fail
secure; always check your third-party locking hard-
ware wiring instructions and ensure you’re using the
right conguration for your requirements.
7

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
Connecting a Door
INSTALLATION
Connect the Lock (Dry)
For a dry setup, please ensure that “NONE” is selected on the door power selection switch.
Fail Safe
• LOCK (+) positive goes into NC
• LOCK (-) negative and ground wire goes into COM
Fail Safe
Fail Secure
• LOCK (+) positive goes into NO
• LOCK (-) negative and ground wire goes into COM
Fail Secure
Connect the Lock (Wet)
In a Wet conguration, ensure that power selection
for each door is set to the correct voltage as outlined
by the locking hardware specications.
• Set it to “12VDC” for 12 Volt locking hardware
• Set it to “24VDC” for 24 Volt locking hardware
The AC41 is rated to power 12V locks up to 700mA
and 24V locks up to 350mA.
WARNING!
When connecting the lock in the Wet
conguration, ensure the negative of the
lock goes into the COM port as shown in
the diagrams below.
3a
3b
8

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
Verkada AD31 Reader Standard Wiegand Reader
Door Position Indicator
Verkada AC41 expects the DPI to be NORMALLY
CLOSED (NC).
Request-to-Exit (REX)
Verkada AC41 expects the REX to be NORMALLY
OPEN (NO).
Connecting a Reader
INSTALLATION
The REX can be congured to release the lock in Verkada command; most commonly seen in electromagnetic
locks. The REX unlock time can also be congured.
Connecting the Inputs
Both the DPI (Door Position Indicator) and the Request-to-Exit (REX) inputs are dry contacts. Installing these
inputs is optional. They can be congured in Verkada Command. Both of these inputs are optional.
Connecting the Reader
The AC41 is rated to power readers at 12V up to 250mA via the + (VIN) and – (GND) connection. Verkada
readers use the far left 4-port inputs while Standard Wiegand readers use the middle 6-port inputs.
4
5
9

VERKADA INC AC41 — INSTALLATION MANUAL
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
CONFIDENTIAL
Wiring the REX
INSTALLATION
Wiring the REX With the Door Strike
For safety-related applications, wire the REX in parallel with the Door Strike. You can wire additional REX
switches and sensors to the door cassette if needed.
Wiring the REX With an Electromagnetic Lock
For safety-related applications, wire the REX directly to the mag lock. You can wire additional REX switches
and sensors to the door cassette if needed.
DRY Conguration
DRY Conguration
WET Conguration
WET Conguration
6a
6b
10