AX11 IO Controller
Install Guide

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
Introduction
Document revision
Firmware
Levels of Access Control
V1.0
Firmware version can be veried and upgraded in the
Command dashboard at command.verkada.com.
• Attack Level/Grade: Level I
• Endurance Level/Grade: Level I
• Line Security Level/Grade: Level I
• Standby Power Level/Grade: Level I
Note
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
This equipment is for use in a restricted access area.
Ensure power is disconnected from the AX11 before servicing the product or connecting/disconnecting
peripherals.
Warning
Document Details

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
AX11 Recommended Testing AX11 Status LED Behavior
AX11 AC Power LED Behavior
AX11 Overview
Introduction
To ensure ongoing functionality of AX11, it is
recommended to check the following interfaces
every 6 months:
• Short each input to its adjacent COM port and
verify LED illuminates
• Use multimeter to conrm expected
impedance across relay outputs
- Short across NC and COM
- Open across NO and COM
• Use multimeter to verify aux voltage is supplied
at 12V outputs
Solid Orange
Controller is on and booting up
Flashing Orange
Controller is updating rmware
Flashing Blue
Controller is managing inputs and outputs
but cannot reach the server
Solid Blue
Controller is managing inputs and outputs
and is connected to the server
Solid Green
AC power supplied to controller
Dual USB 2.0
Inputs
Wiegand
readers
Relay
outputs
12V
power
Chassis
Ground
Chassis
Ground
Chassis Ground
Verkada
readers
AC power
Dual Ethernet
Status
LED
Battery
LED
AC Power LED

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
AX11 Technical Specications
Introduction
Power
Consumption 60W Max
AC Power
Input
110-240VAC
50-60Hz
Inputs 16 Dry Inputs
Nominal 5VDC
Relay
Outputs
16 Dry Relays
1A/24VDC Contacts
AUX Power
2 External Outputs
1A/12V Power Each
2A Combined Max
Dimensions With Mount
415.6mm (L) x 319.6mm (W) x 111.74 (H)
Without Mount
415.6mm (L) x 319.6mm (W) x 105.74 (H)
Weight 8.3kg
Operating
Temperature 0C - 50C 5-90% Humidity
Compliance FCC, CE
Connectivity
Ethernet: 100/1000Mbps RJ-45 cable
connector for network connection
USB 2.0
Included
Accessories Quick start guide, Install kit
Mounting
Options Drywall anchors (M8) and screws (M5)

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
To remove the mounting plate, unscrew the two
security torx screws from the inside.
Once the security screws are fully removed,
slide the mounting plate down and away from
the main enclosure.
Mounting
Installation

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
Drill four 5/16” Ø holes into the wall.
Insert the drywall anchors into the
holes. Fasten the mounting plate onto
the wall by installing the mounting
screws into the wall anchors.
Drill four 5/32” Ø holes into the wall.
Fasten the mounting plate onto the
wall by installing the mounting screws
into the pilot holes.
Place the sheet metal enclosure over and onto
the mounting plate tabs.
Fasten the two security torx screws to secure
the enclosure to the mounting plate.
Mounting
Installation

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
Recommended Wiring
Wiring
Signal AWG Twisted Pair Conductor Shielded Max Length
Reader Option 1
(Wiegand or AD31) 22 Yes Yes 250ft
Reader Option 2
(Wiegand or AD31) 20 Yes Yes 300ft
Reader Option 3
(Wiegand or AD31) 18 Yes Yes 500ft
12V Power (22 Gauge) 22 Yes Yes 600ft
12V Power (18 Gauge) 18 Yes Yes 1500ft
Inputs 22 Yes Yes 1000ft
Dry Relay Output 18 Yes Yes 1500ft
The AX11 card reader interface is capable of supporting Verkada Readers over RS-485 and standard
Wiegand readers. The following table shows the wire types that are recommended for use with AX11.
We recommend using one twisted pair for GND and Vin (power) and one twisted pair for the data (D0/D1 or
A/B).
Wiring methods shall be in accordance with National Electrical Code, ANSI/NFPA 70.
Required Network Settings
With the AX11, you must use shield wiring.
Drain wire of the cable should be secure to the nearest grounding point, indicated with on the controller,
with a conductive M4 screw.
An Ethernet connection with DHCP must be used to connect the AX11 to the Local Area Network (LAN).
You also need to congure rewall settings to communicate with the AX11.
• TCP port 443
• UDP port 123 (NTP time synchronization)
Shield Wiring and Grounding

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
Connecting Peripherals
Installation
Current Limiting Resistor
If a powered peripheral has inrush current over 10A, an in-line current limiting power resistor of 10 should be
used to ensure peripheral does not exceed max power draw, which may disrupt normal operation.
Max Line Resistance
The maximum line resistance for input wire runs should be less than 100, exclusive of end-of-line
supervision resistors.
12V Power
12V Output terminals support up to 2A combined max.
Battery Backup
Battery should be sized to provide at least 4 hours of operation. The AX11 consumes 8.6W with no load (i.e.,
no inputs, outputs, or readers connected).
AC Field Wiring
If AC power is brought in via conduit, cut and splice wire going from AC inlet to PSU.
Inputs
AX11 has 16 Dry Contact Inputs. Nominal 5VDC. Line resistance should be less than 100 exclusive of EOL
resistor.
Relay Outputs
AX11 comes equipped with 16 Form C relays that can be driven dry. Max DC load: 24V @ 1A, Max DC current =
1A, Max DC voltage = 60VDC.
12V 2A MAX
Output 1 (12V 1A)
Output 2 (12V 1A)
IN1
GND
IN2
Input 1
COM
Input 2
COM
NO or NC
NO or NC
Inputs 3 - 16 omitted from diagram, as wiring is identical for all inputs.

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
Connecting an Output
Installation
Wiring a Powered Lock
It is recommended to interface with an Access Power Controller (APC) to provide power to the accessory. If
the APC detects the AX11 relay is triggered, it will trigger its own relay.
Fail Secure
Fail Safe
Depending on your APC and lock, your conguration may vary from the above.
Ensure power is disconnected from the AX11 before plugging in or unplugging any of the terminal blocks.
Failure to do so may damage the AX11
Warning
Access Power ControllerAX11 Relay Output
IN
Input Output
GND
NC
COM
NO
Lock
+
–
Access Power ControllerAX11 Relay Output
IN
Input Output
GND
NC
COM
NO
Lock
+
–
NC
COM
NO
NC
COM
NO
Access Power ControllerAX11 Relay Output
IN
Input Output
GND
NC
COM
NO
Lock
+
–
Access Power ControllerAX11 Relay Output
IN
Input Output
GND
NC
COM
NO
Lock
+
–
NC
COM
NO
NC
COM
NO

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
Connecting a Reader
Installation
Wiring a Verkada or Wiegand Reader
The AX11 is rated to power readers at 12V up to 250mA via the + Vin and - GND connection. The drain wire of
the shielded cable should be secured to nearest AX11 chassis ground.
Verkada Reader
Wiegand Reader
Wire Color Signal
Red 12V Power +
Black 12V Power -
Purple A
Blue B
Wire Color Signal
Red 12V Power +
Black 12V Power -
Green Data 0
White/Gray Data 1
Brown Red LED
Orange Green LED
Shielded CableAX11 RS-485 Verkada Reader
+
–
A
B
Shielded CableWiegand Reader AX11 Wiegand
+
–
D0
D1
RLED
GLED
Shielded CableAX11 RS-485 Verkada Reader
+
–
A
B
Shielded CableWiegand Reader AX11 Wiegand
+
–
D0
D1
RLED
GLED
Verkada Reader Wiegand Reader

Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
All specications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
Battery Backup
Installation
Battery Backup
A 12V Battery can be connected to the F2
connectors located at the bottom of the AX11.
You can t one or two batteries at the bottom
of the AX11.
We recommend and sell a 12 Volt 4.5 Ah Sealed
Lead Acid Rechargeable battery.
If you are using two batteries, ensure they are
wired in parallel.
Connect
Connect the AX11 to your network using either of the Ethernet ports located at the bottom of the controller.
If you are installing multiple controllers, you can connect up to 4 additional controllers via the spare Ethernet
port on each controller.
Connect the AX11 power supply to your standard power outlet (120 VAC)
Battery 1
12V 4.5 Ah
+
-
Battery 1
12V 4.5 Ah
+
-
AX11
Battery Leads
+
-
Other manuals for AX11
1
Table of contents
Other Verkada Controllers manuals
Popular Controllers manuals by other brands

Volt Polska
Volt Polska AVR PRO 1000 product manual

Lucenti
Lucenti BLACKWAVE PIXLDRIVE8 PRO quick start guide

evertz
evertz 7700 Series manual

Ropex
Ropex RESISTRON RES-409 operating instructions

rotork
rotork EH Pro Series Installation and maintenance instructions

Status Instruments
Status Instruments SEM1700 user guide

progressive automations
progressive automations PA-37 User's manual and setup instructions

Robe
Robe DMX Control 1024 user manual

Deif
Deif iE 250 Operator's manual

Siemens
Siemens SIPART DR19 quick reference

Gewiss
Gewiss Chorus GW 10 766 Technical manual

Montavlo
Montavlo X-3000ce-UW Installation and operating instructions