Vertiv Liebert EXL S1 User manual

Liebert®
EXL S1™ Touchscreen Control Panel
User Manual

Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent
section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
The products covered by this instruction manual are manufactured
and/or sold by Vertiv This document is the property of Vertiv and
contains confidential and proprietary information owned by Vertiv.
Any copying, use or disclosure of it without the written permission of
Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions regarding
usage of trademark names should be directed to the original
manufacturer.

Vertiv™|Liebert
®EXL™S1 Touchscreen Control User Manual | i
TABLE OF CONTENTS
1.0 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 NAVIGATING THROUGH THE TOUCHSCREEN CONTROL PANEL . . . . . . 2
2.1 Restrict Physical Access with Barriers or Set Log-In Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Touchscreen Control Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2.1 Context Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 SYSTEM PANE—Mimic Display Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3.1 UNIT STATUS Pane Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Customizing the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4.1 Remove a Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.4.2 Using the Edit Icon to Customize Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.4.3 Edit the UNIT STATUS Panel with the Edit Icon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.4.4 Setting DISPLAY PROPERTIES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.4.5 Setting Date, Time and Time Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.5 Changing Date, Time and Measurement Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2.5.1 Change the Date Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
2.5.2 Change the Time Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
2.5.3 Change the Measurement System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
2.6 Create or Modify Custom Labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
3.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.1 Log In to the Touchscreen Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.2 Operator Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.2.1 LIFE™ Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.3 OPERATE Menu Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.3.1 OPERATE Menu—Silence an Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.3.2 OPERATE Menu—Inverter On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3.3.3 OPERATE Menu—Inverter Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.3.4 OPERATE Menu—Reset Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.3.5 OPERATE Menu—Suspended Time Remaining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.3.6 OPERATE Menu—Energy Saving Mode Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.4 Audible Alarm Enabled or Disabled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
3.5 LIFE™ Services—Context Menu and LIFE Services Function Menu . . . . . . . . . . . . . . . . . . . .35
4.0 VIEWING UPS STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
4.1 Viewing UPS Data with the Status Gauge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
4.2 Viewing UPS Data with the Status Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
4.3 Logs—Events and Log-In Times. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.1 Logs—Filtering and Sorting Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
4.4 Logs—Exporting Event and Audit Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.0 VIEWING UPS COMPONENT STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
6.0 STATUS BAR COMPOSITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.1 Status Bar Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.0 LIEBERT® EXL™ S1 EVENTS, ALARMS AND FAULTS . . . . . . . . . . . . . . . . . . .53

Vertiv™|Liebert
®EXL™S1 Touchscreen Control User Manual | ii
FIGURES
Figure 1 Touchscreen Control Panel components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Opening screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 3 Interface overview—STATUS screen; graphic display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 4 Control display by access level—if PIN’s are required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 5 Context Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6 Mimic display, normal operation, default view/unit view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 7 Mimic display, normal operation, system view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Figure 8 UNIT STATUS pane components—Graphic display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 9 UNIT STATUS pane—Load details; graphic display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 10 UNIT STATUS pane—Input details; graphic display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 11 UNIT STATUS pane—Bypass details; graphic display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 12 UNIT STATUS pane—Battery and cabinet details; graphic display . . . . . . . . . . . . . . . . . 13
Figure 13 UNIT STATUS pane—Environmental details; graphic display. . . . . . . . . . . . . . . . . . . . . . . 13
Figure 14 Customize the display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 15 Set number of panes and choose data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 16 Edit UNIT STATUS panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 17 Change panel content. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 18 Resize, remove or rearrange a panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 19 Edit UNIT STATUS panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Figure 20 Date and time settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 21 Time Zone drop-down menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 22 Change the date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 23 Change the time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Figure 24 Date/Time format and Measurement System choices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Figure 25 CUSTOM LABELS page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Figure 26 Custom Labels for Network Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 27 Set a PIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 28 Log in screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Figure 29 OPERATE Function Menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Figure 30 Inverter On command, single UPS configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Figure 31 Inverter On command, parallel UPS configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Figure 32 Inverter Off command, single UPS configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 33 Inverter Off command inhibited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 34 Disable Inhibit Manual Bypass Overload Transfer command. . . . . . . . . . . . . . . . . . . . . . . .32
Figure 35 Inhibit Manual Bypass Overload Transfer command disabled . . . . . . . . . . . . . . . . . . . . . .32
Figure 36 Bypass overloaded, connected equipment unprotected . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Figure 37 Reset fault command. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Figure 38 Activating Energy Savings Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Figure 39 LIFE Services contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Figure 40 LIFE Services—Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Figure 41 Default Status Gauge view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Figure 42 Access Status Gauge settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 43 Status Gauge settings options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Figure 44 UNIT STATUS—Load details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

Vertiv™|Liebert
®EXL™S1 Touchscreen Control User Manual | iii
Figure 45 UNIT STATUS—Input details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 46 UNIT STATUS—Bypass details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 47 UNIT STATUS—Battery details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Figure 48 UNIT STATUS—Environmental details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Figure 49 View alarms, events, log-out times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 50 Sorting and filtering events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Figure 51 Exporting logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 52 Component status—STATUS Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Figure 53 UNIT STATUS—Main Input details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Figure 54 UNIT STATUS details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
TABLES
Table 1 Available display properties by access level if PIN’s are required . . . . . . . . . . . . . . . . . . .20
Table 2 Additional custom label choices for Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table 3 Load menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Table 4 Input menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 5 Bypass menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 6 Normal messages—Green status bar *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 7 Warning messages—Yellow status bar * . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 8 Critical messages—Red status bar * . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 9 Liebert® EXL™ S1 Status Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Table 10 All Liebert® EXL™ S1 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Table 11 All EXL S1 Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62

Vertiv™|Liebert
®EXL™S1 Touchscreen Control User Manual | iv

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 1
1.0 INTRODUCTION
The Touchscreen Control Panel’s integrated interface simplifies monitoring and managing single
or multiple Liebert®UPS modules. The control collects a profusion of information about the health
of the modules and presents it in a standardized format. This simple, dynamic display speeds
operator response to changing power input and demand.
Many of the settings will depend on the UPS type and features. Many settings will be made by
Vertiv personnel when setting up the UPS.
The Touchscreen Control Panel’s interface will display data either graphically or in text. The
Status Scroll Bar at the top of the touchscreen display summarizes system conditions. The bar
changes color to indicate status and includes an icon matched to the status. The Status Gauge
displays such details as power demand from the connected load, input power quality, output and
bypass on each phase and battery capacity.
The Touchscreen Control Panel’s mimic display shows the comprehensive system information
that the operator needs:
• Is input power connected?
• Are there any alarms?
• Which breakers are open and which are closed?
• Is the UPS on battery?
• How much battery run time is available?
Checking a particular component is as simple as touching it on the mimic display—Detailed data
appears, allowing the operator to respond.
Visual and audible alarms alert personnel to faults and alarms requiring immediate attention.
Passcodes for each level of access—Operator, Administrator and Service—secure the UPS
against unauthorized changes. Personnel without a passcode can view UPS status, but cannot
change any functions or the appearance of the interface.

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 2
Figure 1 Touchscreen Control Panel components
Speakers (not used)
Touchscreen LCD
EPO Switch
UPS Status
UPS Status LED

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 3
2.0 NAVIGATING THROUGH THE
TOUCHSCREEN CONTROL PANEL
The Touchscreen Control Panel is active whenever the UPS has input power. The touchscreen
LCD on the front of the UPS permits:
• Logging in to the system—3.1 - Log In to the Touchscreen Control Panel
• Customizing the user interface—2.4 - Customizing the Display
• Checking the status of the UPS and its external batteries, including all measured parameters, events and
alarms—4.0 - VIEWING UPS STATUS and 5.0 - VIEWING UPS COMPONENT STATUS
• Determining when users logged in and out—4.3 - Logs—Events and Log-In Times
• Silencing alarms—3.3.1 - OPERATE Menu—Silence an Alarm
• Turning the UPS On —3.3.2 - OPERATE Menu—Inverter On
• Turning the UPS Off—3.3.3 - OPERATE Menu—Inverter Off
• Resetting faults—3.3.4 - OPERATE Menu—Reset Fault
• Enabling Energy Saving Mode—3.3.6 - OPERATE Menu—Energy Saving Mode Activation
The Touchscreen Control Panel’s display default view is two panes: One-line animated mimic and
UNIT STATUS. The appearance can be changed to multiple panes that show other data.
Customizing the appearance is detailed in 2.4 - Customizing the Display.
2.1 Restrict Physical Access with Barriers or Set Log-In Codes
NOTICE
Risk of unauthorized changes to UPS operational settings. Can cause equipment damage.
Because a UPS such as the Liebert®EXL™S1 is usually installed in areas that restrict physical access, the
Touchscreen Control Panel does not, by default, require a PIN to change UPS settings and operations.
If physical access cannot be restricted with barriers and identity cards, PIN codes may be set in the
Touchscreen Control Panel to prevent unwanted changes to the Liebert®EXL™S1.
The Touchscreen Control Panel has four possible access levels—Observer, Operator,
Administrator and Service—each with different levels of authority. The Service level, which
permits configuration changes, is the only level that, by default, requires a PIN.
The default access level for the Touchscreen Control Panel is Administrator. When a PIN is set for
the Administrator, the control panel opens at the Operator level.
To set or change a PIN, refer to 3.1 - Log In to the Touchscreen Control Panel.

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 4
Figure 2 Opening screens
Default
opening
screen; no PIN
required;
Administrator
level access
for all with
Default opening screen; PIN required; Note
that the SETUP Function Menu is absent.
Operator level access for all with physical

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 5
2.2 Touchscreen Control Panel Components
The main areas of the Touchscreen Control Panel are shown in Figure 3. The display
arrangement and the information displayed can be changed.
At log-in for all access levels, the Touchscreen Control Panel opens to the STATUS screen in graphic
display. The status of Unit 0 will be shown if the system is a single-unit configuration. In a parallel
setup, the STATUS screen shows the unit where the HMI is installed or the system view. The STATUS
screen will show the animated mimic and system status readings at each log-in level. The
appearance will differ only in the function menus displayed (see Figure 4).
Figure 3 Interface overview—STATUS screen; graphic display
UPS Status Bar
(Scrolls through
status
LogIn/Out
Icon
Parameter Icons
(Maximum of four visible
if the Status Gauge is
Edit
Interfac
e Icon
Graphic
or Text
View
Interface
Function Menu
Icons (Varies by
access level)
Context
Menu Icon
Status Gauge
Animated Mimic
Display (Unit 1 mimic Legend Drawer
(See Figure 6)
SERVICE ACCESS LEVEL SCREEN SHOWN
Other access levels will show different function menu
icons, but the rest of the screen will be the same.
Status
Bar
Function Menu
Icon
(Service is
visible only when
LIFE Services
Menu Icon
System link
(When active,
output shows
system values)

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 6
Figure 4 Control display by access level—if PIN’s are required
Each Function Menu offers different information and control choices.
If PIN’s are not required, the user will see the STATUS, OPERATE, SETUP and LIFE Services
Function Menus.
If PIN’s are required, the user’s access level determines which Function Menu icons are
displayed. For example, logging in as Operator will show the STATUS, OPERATE and LIFE
Services Function Menus; logging in as Administrator will show those menus as well as the
SETUP Function Menu (see Figure 4).
• STATUS: Condition of the UPS modules and components and data affecting operation and performance;
visible at all access levels.
• OPERATE: UPS operation controls, such as Inverter On, Inverter Off and Energy Saving Status; visible to
Operator, Administrator and Service
• SETUP: Manage permissions through PIN’s; visible to Administrator and Service
• SERVICE: Input wiring and breaker configuration, parallel status, protocol used and battery charging
method; visible only to Service
• LIFE Services: Information for assistance to enable LIFE customer care. LIFE Services requires a
maintenance contract. The service must be activated with assistance by calling the listed telephone
number; visible to all, including Observers.
Observer Level Operator Level Administrator Level
Service Level
STATUS
OPERATE
SETUP
SERVICE
LIFE
Services
Function Menu icons are orange and white when selected, except
the LIFE Services icon; it remains dark gray with green text, if LIVE

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 7
2.2.1 Context Menus
The Context Menus, available by touching the Menu icon at the top left corner of the
interface, display information about the UPS and permit changing various settings.
The functions possible through the Context Menus are determined by the user’s
access level and on the Function Menu that is active (see Figure 5).
The items under Display Options on the STATUS Context Menu, for example, differ
for each access level.
Some information available through the Context Menu, such as alarms and run hours, are
available through other areas of the Touchscreen Control Panel.
Figure 5 Context Menus
Context Menu—STATUS
Selecting the STATUS icon and touching the Menu icon reveals a Context Menu that permits
performing several actions or accessing additional information (see Figure 5). Touching a
Context Menu item will reveal data or expand the menu to show additional options.
The Context Menu for the STATUS icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events
can be sorted by type, event ID, component, description. The touchscreen also permits filtering events by
NOTE
The LIFE Services Function Menu icon has no associated Context Menu. Commands and
operations related to LIFE Services are found on the OPERATE Context Menu.
Menu Icon
STATUS Function Menu
OPERATE Function Menu
SETUP Function Menu Selected
(Not shown to Observer or
Operator

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 8
severity (Status, Alarm or Fault); or by component (bypass, monitoring process or the module where the
event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component
affected and description; same options for all access levels. The Event Log can be exported as a CSV
file for record-keeping, analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system.
The Audit log can be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Battery Run Time: Battery Cycle Monitor with duration and count
• Screen Saver: Display Sleep Mode notification (immediate entry into screen saver); screen goes dark and
user is logged off; touching the screen reactivates the interface.
• Total Run Hours: Component and hours it has operated; touching a component displays details in the right
panel.
• Components: Component status, name and details
• Display Options (changes affect the view for all viewers)
• Customize Layout: Change panel content and layout (see 2.4 - Customizing the Display)
• Display Properties: Language, back-light timer, alarm timeout, auto-log-out timer, display brightness,
status indicator brightness and touchscreen calibration (see 2.4 - Customizing the Display)
• Date & Time: Drop-down lists for time zone, date, local time and UTC time (Coordinated Universal
Time) (see 2.4 - Customizing the Display); permits synchronizing time to network time.
• Formats: Drop-down lists for date and time format and measurement system (metric or imperial) (see
2.4 - Customizing the Display)
• Custom Labels: Rename settings, serial ports and network interfaces to ease troubleshooting and
refine data. (The default name of COM1 may be adequate, but renaming it with the connected device
may ease determining the cause of an alarm).
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity,
model number and serial number.
Context Menu—OPERATE
Selecting the OPERATE icon and touching the Menu icon reveals a Context Menu that permits
performing several actions or accessing additional information (see Figure 5). Touching a
Context Menu item will reveal data or expand the menu to show additional options.
The Context Menu for the OPERATE icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events
can be sorted by type, event ID, component, description. The touchscreen also permits filtering events by
severity (Status, Alarm or Fault); or by component (bypass, monitoring process or the module where the
event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component
affected and description; same options for all access levels. The Event Log can be exported as a CSV
file for record-keeping, analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system.
The Audit log can be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Battery Operations: Battery testing and charging; automatic, manual and calibration battery testing and
battery equalize charging.
• LIFE Services: Customer care assistance contact and reporting center; must be activated with assistance
by calling the listed telephone number;
• Screen Saver: Display Sleep Mode notification (immediate entry into screen saver); screen goes dark and
user is logged off; interface reactivated by touching the screen; same options for all access levels
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity,
model number and serial number

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 9
Context Menu—SETUP
Selecting the SETUP icon and touching the Menu icon reveals a Context Menu that
permits performing several actions or accessing additional information (see
Figure 5). Touching a Context Menu item will reveal data or expand the menu to
show additional options.
The Context Menu for the SETUP icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events
can be sorted by type, event ID, component, description. The touchscreen also permits filtering events by
severity (Status, Alarm or Fault); or by component (bypass, monitoring process or the module where the
event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component
affected and description; same options for all access levels. The Event Log can be exported as a CSV
file for record-keeping, analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system.
The Audit log can be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Manage Permissions: Change or require PIN for users of Administrators or Operators.
• Network: Modify communication settings.
• Configure Status Gauge: Modify information shown on Status Gauge.
• UPS Settings: Enable or disable audible alarm and modify energy saving configuration (Eco Mode or
Intelligent Parallel).
• Display Options (Changes affect view for all access levels)
• Customize Layout: Change panel content and layout (see 2.4 - Customizing the Display).
• Display Properties: Language, back-light timer, alarm timeout, auto-log-out timer, display brightness,
status indicator brightness and touchscreen calibration (see 2.4 - Customizing the Display).
• Date & Time: Drop-down lists for time zone, date, local time and UTC time (Coordinated Universal
Time) (see 2.4 - Customizing the Display); permits synchronizing time to network time.
• Formats: Drop-down lists for date and time format and measurement system (metric or imperial) (see
2.4 - Customizing the Display).
• Custom Labels: Rename settings, serial ports and network interfaces to ease troubleshooting and
refine data. (The default name of COM1 may be adequate, but renaming it with the connected device
may ease determining the cause of an alarm).
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers.
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity,
model number and serial number.
2.3 SYSTEM PANE—Mimic Display Components
The animated mimic display, the default view for the control, shows each configured major
component of the UPS system, for both single-module and multi-module systems. The mimic
display is the same for all access levels. The power path is shown by animated lines; moving
dashes show the active power path. Touching a component (except a breaker) brings up details
about the component’s status. Breakers are shown as open or closed (see Figure 6), but they are
not interactive.
Components in the mimic display signify their operational status by their color, green, amber or
red. Tables 9 through 11 describe the various states of the indicators.
The animated mimic display can be changed to any of five other views: Status, Alarms, Run Hours,
Event Log and Battery Cycle Monitor Summary (see 2.4 - Customizing the Display).

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 10
Figure 6 Mimic display, normal operation, default view/unit view
Output Power
(interactive)
Input Power
(interactive)
Internal Static Bypass
(interactive)
DC Source
(Batteries)
(interactive
Rectifier
Feed
Touching the arrowhead reveals the
Maintenance
Bypass
Breakers in a system are
determined during setup and can
be installed or removed by
Service.
Breakers shown are:
BCB: Battery Isolation Switch
BIB/RBB: Bypass Isolator
RFB: Input Isolator
MBB: Maintenance Bypass
Inverter
Charger/Boost
er
Battery Cabinet
Remote Back-Feed
Breaker; may be
replaced with
optional Back-Feed
Maintenance Isolation
Module Output
Rectifier
(interactiv
Maintenance
Bypass Path

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 11
Figure 7 Mimic display, normal operation, system view
2.3.1 UNIT STATUS Pane Components
The UNIT STATUS pane is identical for all PIN access levels (see Figure 8), if PIN’s are required.
Observers will not have the edit icon (pencil). In the default graphic view, the UNIT STATUS pane
shows:
• Status Gauge—Connected load shown in kW and as a percentage of capacity; input, output and bypass
voltage for each phase (default data may be changed; see 4.1 - Viewing UPS Data with the Status Gauge).
• Load Detail Icon
•InputDetailIcon
• Bypass Detail Icon
• Battery Detail Icon
The detail icon for Environmental may be added to the UNIT STATUS pane if there is space.
Touching any of the detail icons reveals additional data about that selection in the opposite pane.
The data pane may be closed by touching the Close button or by touching any detail icon. The
read-only information is available to all access levels (see Figures 9 through 13).
NOTE
If the Status Gauge is showing, no more than four detail icons will be visible. Removing the Status
Gauge permits showing all five detail icons. The view may be customized to show fewer than four.
Touching the arrowhead reveals the
Green outline
indicates
communication is
active and operating
normally.
White outline indicates
no communication
occurring.
Yellow indicates the
unit is communicating
but in a warning state.
System view is
obtained by touching
SYSTEM in the
default mimic view.
To return to default
view, touch Unit 1 or

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 12
Figure 8 UNIT STATUS pane components—Graphic display
Figure 9 UNIT STATUS pane—Load details; graphic display
Status
Detail Icons for
Input, Battery,
Bypass and Load
(Touch an icon to
see details about
the linked
component [see
Figure 9].)
No more than four
detail icons will be
visible when the
Status Gauge is
Edit icon
Touch this icon to
switch to Text Display.
Touch Close or
the Load icon to
close the Load
detail pane and
return to the
Load icon
touched to
show data in

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 13
Figure 10 UNIT STATUS pane—Input details; graphic display
Figure 11 UNIT STATUS pane—Bypass details; graphic display
Input detail icon
touched to show
data in the left
Touch Close or
the Input icon to
close the Input
detail pane and
return to the
animated mimic.
Bypass detail
icon touched
to show data
in the left
Touch Close or
the Bypass icon to
close the Bypass
detail pane and
return to the
animated mimic.

Vertiv™| Liebert® EXL™S1 Touchscreen Control User Manual | 14
Figure 12 UNIT STATUS pane—Battery and cabinet details; graphic display
Figure 13 UNIT STATUS pane—Environmental details; graphic display
2.4 Customizing the Display
The Touchscreen Control Panel’s default appearance will be adequate for most installations, but
the Status panels can be altered to show additional or different data. The layout selected will be
Battery detail icon
touched to show
data in the left
Touch Close or
the Battery icon to
close the Battery
detail pane and
return to the
Environmental
detail icon
touched to show
Touch Close or the
Environmental icon
to close the
Environmental
detail pane and
return to the
Other manuals for Liebert EXL S1
3
Table of contents
Other Vertiv Control Panel manuals
Popular Control Panel manuals by other brands

Eaton
Eaton Greengate ControlKeeper CK4A-SSRC installation instructions

Tennant
Tennant IPC PW-E101 instruction manual

AAON
AAON MHGRVX-B2 Field Technical Guide

Beckhoff
Beckhoff CP29xx-0000 Series Installation and operating instructions

Teletek electronics
Teletek electronics CA60Plus installation manual

Beckhoff
Beckhoff CPX3915-0010 Installation and operating instructions