The Context Menu for the STATUS icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events can be sorted by
type, event ID, component, description. The touchscreen also permits filtering events by severity (Status, Alarm or Fault); or
by component (bypass, monitoring process or the module where the event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component affected and
description; same options for all access levels. The Event Log can be exported as a CSV file for record-keeping,
analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system. The Audit log can
be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Battery Run Time: Battery Cycle Monitor with duration and count
• Screen Saver: Display Sleep Mode notification (immediate entry into screen saver); screen goes dark and user is logged off;
touching the screen reactivates the interface.
• Total Run Hours: Component and hours it has operated; touching a component displays details in the right panel.
• Components: Component status, name and details
• Display Options (changes affect the view for all viewers)
• Customize Layout: Change panel content and layout (see 2.4 - Customizing the Display)
• Display Properties: Language, back-light timer, alarm timeout, auto-log-out timer, display brightness, status indicator
brightness and touchscreen calibration (see 2.4 - Customizing the Display)
• Date & Time: Drop-down lists for time zone, date, local time and UTC time (Coordinated Universal Time) (see 2.4 -
Customizing the Display)
• Formats: Drop-down lists for date and time format and measurement system (metric or imperial) (see 2.4 -
Customizing the Display)
• Custom Labels: Rename settings, serial ports and network interfaces to ease troubleshooting and refine data. (The
default name of COM1 may be adequate, but renaming it with the connected device may ease determining the cause
of an alarm).
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity, model number and
serial number.
Context Menu—OPERATE
Selecting the OPERATE icon and touching the Menu icon reveals a Context Menu that permits performing
several actions or accessing additional information (see Figure 5). Touching a Context Menu item will reveal
data or expand the menu to show additional options.
The Context Menu for the OPERATE icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events can be sorted by
type, event ID, component, description. The touchscreen also permits filtering events by severity (Status, Alarm or Fault); or
by component (bypass, monitoring process or the module where the event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component affected and
description; same options for all access levels. The Event Log can be exported as a CSV file for record-keeping,
analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system. The Audit log can
be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Battery Operations: Battery testing and charging; automatic, manual and calibration battery testing and battery equalize
charging.
• LIFE Services: Customer care assistance contact and reporting center; must be activated with assistance by calling the
listed telephone number;
• Screen Saver: Display Sleep Mode notification (immediate entry into screen saver); screen goes dark and user is logged off;
interface reactivated by touching the screen; same options for all access levels
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity, model number and
serial number