
To disconnect the external battery from the UPS system for maintenance, use the external isolating switch. At this time,
except for the battery backup function upon mains failure, other functions and all the steady state performance of the UPS
will not be affected.
UPS module failure
In case of inverter failure and output fuse blowout, the load will automatically transfer to the bypass, and the output power
supply will not be interrupted. In this situation, please contact the local customer service center of Vertiv for technical support.
Parallel System In the event of a fault in a UPS module, it will automatically exit from the parallel system. If the system is still
capable of providing the required load, the remaining modules will continue to supply the load with no interruption. If the
remaining modules are no longer capable of fulfilling the power requirements, the load will automatically transfer to the
bypass.
Overload
If the inverter is overloaded or the inverter current remains outside the specifications (refer to Table 12.6 on page169 ) longer
than the specified time, the load will automatically transfer to the bypass without power interruption. If both the overload and
the current are reduced to a level within the specified range, then the load will be transferred back to the inverter. In case of
output short circuit, the load will be transferred to the bypass, and the inverter will shut down. Five minutes later, the inverter
will start up automatically. If the short circuit is removed at this point, the load will be transferred back to the inverter. The
transfer is determined first of all by the features of the protective device of the system.
In the above two situations, the UPS operator control and display panel will display alarm messages.
Parallel SystemThe control logic system constantly monitors load requirements and controls the power supplied by each
UPS module. In the event that an overload condition is sustained for greater than a preset time, the load will transfer to the
bypass, when the number of active modules is unable to satisfy load requirements. The load returns to the inverter if the
power is reduced to a value that can be sustained by the number of active modules in the system.
Maintenance bypass
The UPS has a second bypass circuit, i.e. maintenance bypass, which provides a safe working environment for the engineers
to provide regular maintenance or repair to the UPS system and at the same time provide unregulated mains supply to the
loads. The maintenance bypass can be manually selected through the maintenance bypass switch, and it can be
disconnected by turning the switch to OFF.
WARNING! If the UPS system is composed of two or more UPS modules and when the load capacity exceeds
the single module capacity, do not use the internal maintenance bypass switch.
2.2.4 UPS Power Supply Switch Configuration
The UPS has four switches: rectifier input switch Q1, bypass input switch Q2, maintenance bypass switch Q3, and output
switch Q5.
Figure 2.2 on the facing page describes the block diagram of the UPS module. The UPS has split bypass configuration (i.e.,
the bypass adopts independent mains input) and common input configuration. If the system adopts common input
configuration, the UPS has shorting copper bar of common input configuration, and the bypass input switch (Q2), and rectifier
input switch (Q1) would be linked together. If the system adopts split bypass configuration, just remove the shorting copper
bar of common input configuration of the UPS.
During the normal operation of the UPS, except for the maintenance bypass switch Q3, other switches shall be closed.
8 Proprietary and Confidential ©2023 Vertiv Group Corp. 2 Overview
Vertiv™ Liebert® EXM2 UPS User Manual