REPLACING THE BATTERY
To replace the battery:
1. Turn o all connected loads, then turn o the UPS (batteries are NOT hot-swappable).
2. Use a Phillips head screwdriver to remove the two top cover screws from the back of
the UPS.
3. Slide the top then pull outward to remove it.panel backward 13mm (1/2"). Slide the
front panel upward,
4. Gently pull the batteries out of the UPS.
5. Remove the black wire from the negative (-) terminal and the red wire from the
positive (+) terminal.
6. Verify that the replacement battery matches the dimensions and battery type in the
Specifications section below.
7. Connect the battery leads to the new batteries. Be sure to reconnect the red wire to
the positive (+) terminal and the black wire to the negative (-) terminal.
Note: Small sparks may occur at the battery connectors during reconnection.
8. Slide the batteries into the UPS.
9. Reposition the front panel and slide downward until it slides into place.
Slide the top panel forward until flush with the front panel. Reinsert the two top cover
screws removed in Step 2 .
Dispose of the old batteries properly at an appropriate recycling facility.
SolutionsPossible CausesProblem
Utility power is normal, but LED 1 is not illuminated.
The UPS may not be turned on.
The power cord may not be connected properly.
The upstream mains circuit breaker may be tripped.
• Press the On/O button to turn on the UPS.
• Connect the power cord securely into a wall outlet.
•Reset the circuit breaker.
LED 2 flashes (amber) every 3 seconds, but there is
no output power.
Alarm buzzer beeps continuously although mains is
normal. The UPS may be overloaded (check LED 2).
The UPS is on and connected to input power, but fails
to operate properly.Utility power may be outside the unit’s operating range.• If mains is normal, try reconnecting mains and
restarting the UPS.
1500/9001000/600Capacity (VA/W)
11.6 (25.6)9.5 (20.9)Net Weight, lb. (kg)
12.8 (28.2)10.7 (23.6)Shipping Weight, kg (lb.)
147 × 360 × 234 (5.8 × 14.2 × 9.2)Dimensions - W × D × H, mm (in.)
160-287VACOn-Line Mains Voltage
50/60Hz ±5HzOn-Line Frequency
Typical 185-252VACOutput Voltage (Mains Normal)
230VAC ±5%Output Voltage (Battery Operation)
Stepped sinewaveOn-Battery Wave Form
12V x 9Ah x 212V x 7.2Ah x 2Battery Type - VDC × Ah × Quantity
6-8 hours to 90%Typical Recharge Time
60-100 minutesBattery Run Time*
Audible alarm / LEDAudible and Visual
IEC 320 C13 (6)Backup Sockets
IEC 320 C13 (2)Surge Sockets
0 to 40 (32 to 104)
Operating Temperature, °C (°F)
-15 to 40 (5 to 104)
Storage Temperature, °C (°F)
0%-90%, non-condensingOperating / Storage Relative Humidity
Class B
Agency
IEC62040-1-1Safety
ISTA Procedure 1A Certification
* Battery run time may vary depending on load
Steps 4 and 5
Steps 2 and 3
Transportation
The UPS battery reached end of life.UPS does not provide expected backup time. • Replace the internal battery.
• Disconnect some equipment from the UPS.
Battery voltage may be too low. • Recharge the UPS for 8 hours.
PSA1000MT3-230UModel Number PSA1500MT3-230U
EMI Classification
SPECIFICATIONS
BATTERY REPLACEMENT
• Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
•When replacing batteries, replace with the same type and number of batteries or battery packs.
CAUTION
Do not dispose of batteries in a fire. The batteries may explode.
CAUTION
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.
This product is also designed for IT power systems with phase-to-phase voltage 230V.
-
TROUBLESHOOTING
If the UPS malfunctions during operation, check the following chart for proper adjustment. For further assistance, please contact your local Vertiv representative.
800-222-5877 (Outside U.S. 614-841-6755)
Website : www.vertiv.com
1050 Dearborn Drive
United States
P.O. Box 29186
Columbus, OH 43229
© 2019 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or
registered marks of Vertiv Group Corp. All other names and logos referred to are trade names,
trademarks or registered trademarks of their respective owners. While every precaution has been
taken to ensure accuracy and completeness herein, Vertiv Group Corp. assumes no responsibility, and
disclaims all liability, for damages resulting from use of this information or for any errors or omissions.
Specifications are subject to change without notice.
Technical Support / Service