Vibration Research VR9500 User manual


Notes, Notices, and Cautions
© 2021 Vibration Research Corporation is a registered trademark in the United
States and other countries.
Information in this document is subject to change without notice.
Document last revised Wednesday, March 24, 2021 - Jenison, Michigan.
Vibration Research Corporation may have patents including but not limited to
U.S. Patent No. 7,426,426, Japan Patent No. 4429358, Canada Patent No.
2,568,178, China Patent No. 058001235.2, E.U. Patent No. 1766358, and other
patent applications, trademarks, copyrights, or other intellectual propertyrights
covering subject matter in this document. Except as expresslyprovided in any
written license agreement from Vibration Research Corporation, the furnishing
of this document does not give you anylicense to these patents, trademarks,
copyrights, or other intellectual property.
Products that are referred to in this document may be either trademarks and/or
registered trademarks of the respective owners. The publisher and the author
make no claim to these trademarks.
While every precaution has been taken in the preparation of this document, the
publisher and the author assume no responsibilityfor errors or omissions, or
for damages resulting from the use of information contained in this document
or from the use of programs and source code that mayaccompany it. In no
event shall the publisher and the author be liable for any loss of profit or any
other commercial damage caused or alleged to have been caused directly or
indirectly by this document.
The NOTE icon indicates important information for better use of the
controller.
The CAUTION icon indicates the potential for propertydamage, personal
injury, or death.

Table of Contents
VR9500 Hardware Manual
................................................................................................................. 1
Hardware Overview
................................................................................................................. 3
Capabilities & Specifications
................................................................................................................. 4
Installation
................................................................................................................. 7
Connection
................................................................................................................. 11
Remote I/O
................................................................................................................. 13
Maintenance
................................................................................................................. 14
Calibration Verification
................................................................................................................. 22
Troubleshooting & Diagnostics
................................................................................................................. 26
Warranty


1
support@vibrationresearch.com
Hardware Overview
Front and Back Panel Inputs/Outputs

VR9500 Hardware Manual2
Hardware Overview CONTINUED
·
The Gigabit Ethernet port can operate at 100 or 1,000 Mbps. The port
supports auto-negotiation, full duplex, and flow control. It also supports auto
MDXoperation to eliminate any requirements for crossover network cables.
·
The front panel has four BNC input connectors that support various analog
input devices. Each input supports ±1V peak, ±10V peak, and ±20V peak
input ranges. Each input also supports single ended, differential, and capacitor
coupled operation, IEPE transducers, and smart transducers (TEDS).
·
The rear panel has two BNC output connectors that support various analog
drive devices. The DRIVE output is typically used to drive an amplifier or servo-
hydraulic controller. The COLA/AUX output is typically used to support
synchronization with constant level adapter (COLA) devices such as
stroboscopes or data acquisition devices. It can also be used for a second
amplifier output to support differential mode outputs or devices with multiple
axes.
·
The rear panel has an interbox port for loop synchronization of multiple
VR9500 units. Loop synchronization can be completed with hardware or
software clocks. Hardware clocks via interbox connection are only
recommended for systems with more than 40 input channels.
·
The rear panel has an AUX inputs/outputs DB37 connector that supports
eight digital outputs and eight analog/digital inputs. It can be used to integrate
with other systems or monitor analog signals.
System Ventilation Fan
The VR9500 has one fan for system ventilation. Make sure the fan and vent
openings remain unobstructed to allow for proper airflow.

3
support@vibrationresearch.com
Capabilities & Specifications
Item Check List
The following items are included with the VR9500:
·
VR9500 I/O
·
AC power cable
·
Drive cable
·
Network (Ethernet) cable
·
Rack-mount kit for installation
·
Software CD
·
VibrationVIEW software manual
VR9500 General Specifications
·
1 to 128 channels, 4 channel units (mix & match)
·
Total harmonic distortion < -100dB THD+N
·
24-bit resolution inputs and outputs
·
·
Compatible with VibrationVIEW control software and ObserVIEW analysis
software
Power requirements: 90VAC to 250VAC; 50/60Hz; 1.2/.7Amps
Operating temperature range: 35° to 122° Fahrenheit; 2° to 50° Celsius
Analog Inputs
·
200kHz simultaneous sample rate
·
IEPE (4mA) and TEDS
·
200V peak transient protection
·
±1V peak, ±10V peak, and ±20V peak input ranges
·
>110dB dynamic range; >130dB with tracking filters
·
Single-ended with 100k ohm impedance
·
Differential with 200k ohm impedance
·
Analog multiple pole anti-aliasing filter and digital anti-aliasing filter with >92dB
attenuation
Analog Outputs
·
200,000 samples per second
·
Analog multiple pole filter plus a digital filter and analog reconstruction filters
·
50,000Hz frequency range
·
COLA/AUX output
·
Up to 2 independent outputs for multi-shaker control

VR9500 Hardware Manual4
Installation
Installation Precautions
CAUTION: Before performing any of the following procedures, read and follow
the safety instructions.
CAUTION: If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be impaired.
CAUTION: Observe the following points before performing the procedures in
this section:
·
Make sure the rack or cabinet housing the device is adequately secured to
prevent instability or a fall.
·
Make sure the power source circuits are properly grounded.
·
Observe and follow the service markings. Do not service any device that is not
defined in the system documentation. Opening or removing covers marked
with a triangular symbol with a lightning bolt may cause electrical shock.
These components are to be serviced by trained service technicians only.
·
Make sure the power cable, extension cable, and plug are not damaged.
·
Make sure the device is not exposed to water.
·
Make sure the device is not exposed to radiators or heat sources.
·
Make sure the cooling vents are not blocked.
·
Do not push foreign objects into the device as it may cause a fire or electric
shock.
·
Use the device with approved equipment only.
·
Allow the device to cool before removing covers or touching internal
equipment.
·
Make sure the device does not overload the power circuits, wiring, or over-
current protection. To determine the possibility of overloading the supply
circuits, add the ampere ratings of all the loads installed on the same circuit
as the device. Compare the sum with the rating limit for the circuit.
·
Do not install the device in an environment where the operating ambient
temperature might exceed 122ºF (50ºC).
·
Make sure the airflow around the front, sides, and back of the device is not
restricted.

5
support@vibrationresearch.com
Site Requirements
The VR9500 can be mounted on a standard equipment rack or placed on a
tabletop.
Before installing the device, verify that the site selected for the device meets the
following requirements:
·
Power — The device is installed within 5ft (1.5m) of a grounded and easily
accessible outlet 220/110VAC, 50/60Hz.
·
General — The power source is correctly installed.
·
Clearance — There is adequate frontal clearance for operator access. Allow
clearance for cabling, power connections, and ventilation.
·
Cabling — Cabling is routed to avoid sources of electrical noise such as radio
transmitters, broadcast amplifiers, power lines, and fluorescent lighting
fixtures.
·
Ambient Requirements — The ambient device operating temperature range is
32° to 122°F (0° to 50°C) at a relative humidity of up to 95%RH, non-
condensing. Verify that water or moisture cannot enter the device case.
·
Do not operate the device near volatile or flammable materials.
Physical Dimensions
Height — 1.75in (44.45mm) (1U)
Width — 15in (381mm) (19in rack mount with included brackets)
Depth — 9.5in (242mm)

VR9500 Hardware Manual6
Installation CONTINUED
Installing on a Flat Surface
The surface must be able to support the weight of the VR9500 and its cables.
·
Set the device on a flat surface; leave 2in (5.08cm) on each side and 5in
(12.7cm) at the back.
·
Make sure the device has proper ventilation.
Installing on a Device Rack
CAUTION: Read the safety information in this guide as well as the safety
information for other devices that connect to or support the VR9500.
CAUTION: Disconnect all cables from the device before mounting the device
in a rack or cabinet.
CAUTION: When mounting multiple devices in a rack, mount the devices
from the bottom up.
·
Place the supplied rack-mounting bracket on one side of the device. The
mounting holes on the device should line up with the mounting holes on the
rack mounting bracket. The following figure illustrates where to mount the
brackets.
·
Remove the feet from the bottom of the device.
Other Installation Methods
CAUTION: Always mount the VR9500 horizontally.
The VR9500 requires the ventilation provided by a normal horizontal orientation;
mounting in other orientations is not recommended.

7
support@vibrationresearch.com
Connection
Connecting the Device to a Power Supply
CAUTION: This product must be reliably earthed and installed in accordance
with the prevailing electrical wiring regulations and safety standards.
·
Connect the standard AC power cable to the AC connector on the back panel.
·
Connect the power cable to a grounded AC outlet. When used in a control
system, all grounds must be common. This is most easily accomplished by
connecting the power cable to the amplifier's controller outlet. No operator
settings are required for voltage configuration.
·
After connecting the device to a power source, confirm that the device is
connected and operating correctly by examining the LEDs on the front panel.
·
The standard AC power cable is the primary disconnecting device. Position
the equipment so that it is easy to disconnect the AC power cord.
100/1000BASE-T CABLE REQUIREMENTS
All category 5 UTP cables used for 100BASE-TX connections also operate with
1000BASE-T provided that all four wire pairs are connected. However, an
enhanced category 5e cable or newer is recommended for all critical
connections or new cable installations. The category 5e or newer specification
includes test parameters that are only recommended for category 5 and comply
with the IEEE 802.3ab standards.
The VR9500 supports auto-detection of straight through and crossed cables on
all switching 10/100/1000BASE-T ports. The automatic correction of errors in
cable selection makes the distinction between a straight through cable and a
crossover cable irrelevant.

VR9500 Hardware Manual8
Connection CONTINUED
Connecting the Device to a Network
NOTE: Do not plug a phone jack connector into an RJ-45 port. This will
damage the Ethernet device. Use only twisted-pair cables with RJ-45 connectors
that conform to FCC standards.
·
Attach one end of a twisted-pair cable to the device's RJ-45 connector and the
other end to a switch or workstation computer.
·
Make sure the twisted pair cable does not exceed 328ft (100m) in length.
After connection, the network LED will turn green to indicate that the connection
is valid.
RJ-45 CONNECTOR
CAUTION: The terminals on the unit should only be connected to passive
load transducers or source transducers that apply no more than 10V to the
circuit that originates from the VR9500 (or a value that equates to no more than
33Vac RMS/46.7V peak or 70Vdc total on the circuit).
CAUTION: Other than the IEC inlet for input power to the unit, the terminals
on the rear of the unit should only be connected to SELV/double insulated
circuits of other equipment.
The 10/100/1000 BASE-T ports are copper
twisted-pair ports.
RJ-45 Pin Number Allocation for Ethernet Port
Pin No
Function
1
TxRx 1+
2
TxRx 1-
3
TxRx 2+
4
TxRx 2-
5
TxRx 3+
6
TxRx 3-
7
TxRx 4+
8
TxRx 4-

9
support@vibrationresearch.com
Connecting the Device to an Amplifier
CAUTION: Always connect the power cable to a grounded AC outlet prior to
connecting or disconnecting the drive cable.
Connect the supplied 50ΩBNC cable (or equivalent) between the Drive output
and input on the power amplifier.
Connecting the Device to an Accelerometer
CAUTION: Always verify that the mounting surface of the accelerometer is
floating or grounded.
CAUTION: Terminals provided on the unit shall be connected only to passive
load transducers or source transducers that apply no more than 10V to the
circuit that originates from the VR9500 (or a value that equates to no more than
33Vac RMS /46.7V peak or 70Vdc total on the circuit).
CAUTION: Other than the IEC inlet for input power to the unit, terminals
provided on the rear of the unit should only be connected to SELV/double
insulated circuits of other equipment.
CAUTION: If any sourcing transducers (accelerometers) add voltage to the
existing voltage originating from the VR9500, the total shall not exceed the
70Vdc or 33Vac (RMS).
Connect the accelerometer to the front panel input.

VR9500 Hardware Manual10
Connection CONTINUED
Connecting the Device to Software
The user can control the VR9500 with one of the three Vibration Research
software applications. Each software package offers a different set of capabilities
when paired with the VR9500.
VibrationVIEW
To connect the VR9500 to the VibrationVIEW software for vibration control,
please refer to the VibrationVIEW Quick Start Guide. VibrationVIEW must be
configured to use the appropriate network connection after the hardware is set
up and PC communication is established.
ObserVIEW
To connect the VR9500 to the ObserVIEW software for signal analysis, please
refer to the ObserVIEW Quick Start Guide. Live Analyzer is the default
connection in ObserVIEW. In Live Analyzer, the user can access the full
spectrum of analysis controls in ObserVIEW as live data streams in from the
device.
VR Mobile
To connect the VR9500 to VR Mobile for remote monitoring, the VR9500 must
be connected to the same network as the smart phone or tablet running the
application. The smart phone/tablet serves as the user interface display following
connection and can be used to check system configuration and configure live
analyzer.

11
support@vibrationresearch.com
Remote I/O
BNC Inputs and Outputs
BNC connectors are manufactured with 50Ω and 75Ω impedance capability. 50Ω
cables are typically used for this application. BNC inputs are typically used with
an accelerometer. Nominal ranging allows for maximum 20V peak input devices.
BNC output ranging allows driving maximum 10V peak devices or maximum 1V
peak devices.
Power Connectors
The VR9500 is powered by the AC internal power supply.
Internal Power Supply Connector
The VR9500 supports a single internal power supply to provide power for
switching operations. The AC power connector is located on the back panel of
the hardware.
Aux Inputs/Outputs
The DB37 mating connector is an Amphenol L777-RR-C-37-P (or equivalent).
Inputs are 10V peak inputs with provision to read nominal TTL signals. TTL
outputs 1 to 8 are nominal TTL voltage levels and require external conditioning to
drive high voltage and high current devices.
·
TTL output 1 to TTL output 8 HIGH voltage (active): 2.5V minimum at 3mA
source current; 2.0V minimum at 32mA source current
·
TTL output 1 to TTL output 8 LOW voltage (inactive): 0.55V maximum at 64mA
sink current
FET output 7 and FET output 8 allow driving high current SELV DC devices
directly.
·
FET output 7 and FET output 8 HIGH (active): sink up to 1.5A to logic ground
·
FET output 7 and FET output 8 LOW (inactive): floating output

VR9500 Hardware Manual12
Remote I/O CONTINUED
Pinout Information
Pin
No
Function
Description
Pin
No
Function
Description
1
RDISIN1
Input #1
20
AGND
Analog Ground
2
RDISIN2
Input #2
21
AGND
Analog Ground
3
RDISIN3
Input #3
22
AGND
Analog Ground
4
RDISIN4
Input #4
23
AGND
Analog Ground
5
RDISIN5
Input #5
24
AGND
Analog Ground
6
RDISIN6
Input #6
25
AGND
Analog Ground
7
RDISIN7
Input #7
26
AGND
Analog Ground
8
RDISIN8
Input #8
27
AGND
Analog Ground
9
LGND
Logic Ground
28
N/C
No Connect
10
LGND
Logic Ground
29
DISIN_BIAS
+5 VDC
11
LGND
Logic Ground
30
LGND
Logic Ground
12
ODIS1
TTL Output #1
31
ODIS2
TTL Output #2
13
ODIS3
TTL Output #3
32
ODIS4
TTL Output #4
14
ODIS5
TTL Output #5
33
ODIS6
TTL Output #6
15
ODIS7
TTL Output #7
34
ODIS8
TTL Output #8
16
LGND
Logic Ground
35
HVHC_ODIS9
FET Output #7
17
N/C
No Connect
36
HVHC_ODIS10
FET Output #8
18
LGND
Logic Ground
37
XESTOP_MID
E-STOP IN
19
XESTOP_LOW
E-STOP IN

13
support@vibrationresearch.com
Maintenance
An annual calibration verification is recommended for continued accuracy of the
VR9500. Before calibration, debris should be blown out of the ventilation slots
and fan. Verify the fan's operation and make sure ventilation is maintained as
defined in Installation .
Cleaning
CAUTION: Remove power from the VR9500 prior to cleaning near the
ventilation slots.
Functionality of the fan should be checked monthly. Clean the fan as needed in
a high dirt and dust environment. Clean enclosures with one of the following:
·
A soft, dry cloth
·
A soft cloth moistened with water
·
A soft cloth moistened with a solution of water and a gentle, non-scratch
household cleaner that does not contain ammonia
Servicing
HIGH VOLTAGE WARNING
CAUTION: Dangerous voltages are present within the power supply.
Disconnect power supply before servicing.
CAUTION: Never use a fuse with a higher current rating, lower voltage rating,
or slower time delay than the specified fuse. Replace the fuse with same type
and rating as fitted.
·
All servicing, repairing, and testing of these products must be carried out by
competent personnel who are conversant with the particular hazards of AC line
operated equipment and the dangers of switch mode power supplies.
·
After disconnecting the AC source, wait 5 minutes before touching the unit to
allow capacitors within the unit to discharge.
·
Heatsinks within this product may be live. Test before touching.
·
This product must be reliably earthed and professionally installed in
accordance with the prevailing electrical wiring regulations and safety
standards.
·
The internal power supply uses a 3.15A fast acting 250V LBC fuse 5 x 20mm
(F1). This fuse is only accessible to qualified service personnel.
·
The VR9500 is protected by a fuse between the power cord and the power
switch. The power cord must be removed to replace the fuse. Replace the
main fuse with the same type (usually a LittleFuse 0218002.HXP) to maintain
protection against overheating, hardware damage, and possible fire.
4

VR9500 Hardware Manual14
Calibration Verification
Calibration verification for the VR9500 should be performed annually. The
recommended sequence for calibration verification is as follows:
1. Run the preliminary verification procedure to verify that the VR9500 arrived at
the calibration lab within the specified 1-year tolerance levels.
2. Run the full verification procedure to verify that the VR9500 is within the
specified 24-hour tolerance levels when it leaves the calibration lab.
Hardware Specifications
·
24-Hour Accuracy: Indicates the VR9500’s relative accuracy over its
measurement range for short time intervals and within a stable environment.
Short-term accuracy is specified for a 24-hour period and a ±2°C temperature
range.
·
1-Year Accuracy: Long-term accuracy specifications valid for a 23°C ±5°C
temperature range. Include the initial calibration errors and the VR9500’s long-
term drift errors.
·
Temperature Coefficients: Accuracy is specified for a calibration
temperature ±5°C temperature range. This is a common temperature range for
many operating environments. You must add additional temperature coefficient
errors to the accuracy specification if operating the VR9500 outside a 23°C
±5°C temperature range.
Terminal Specifications
·
Analog Inputs 1 to 4: General purpose analog inputs typically used to
measure mV accelerometer signals. The four inputs are functionally identical
with user-selectable ranges of ±1V, ±10V and ±20V and a configurable
constant current power source for accelerometers. Each input can be
individually configured for single ended or differential modes and with or without
capacitor coupling.
·
Drive Output: The Drive output is dedicated to drive an amplifier or servo-
hydraulic valve controller. The output has a user-selectable range of ±1V or
±10V.
·
COLA/AUX Output: The COLA/AUX output is dedicated to trigger a strobe or
other external equipment. The output has a user-selectable range of ±1V or
±10V. It is also used as an analog output in special purpose applications.

15
support@vibrationresearch.com
Accuracy Specifications ± (% of reading + % of range)
Function
Range
Input
Frequency
(Hz)
Analog Inputs 1, 2, 3 and 4
24 Hour
Tcal ±2°C
1 Year
Tcal ±5°C
Temperature
Coefficient/°C
0°C to
(Tcal -5°C)
(Tcal +5°C) to
50°C
Voltage
±10V,
±20V
1-10
±2.0 + 0.0005
±2.0 + 0.0005
0.1 + 0.0000
±10V,
±20V
10-2000
±0.5 + 0.0005
±1.0 + 0.0005
0.1 + 0.0000
±10V,
±20V
2000-8000
±0.7 + 0.0005
±1.2 + 0.0005
0.1 + 0.0000
±10V,
±20V
8000-10000
±1.0 + 0.0005
±1.5 + 0.0005
0.1 + 0.0000
±10V,
±20V
10000-15000
+1.5 + 0.0005
-(1.0 + 0.0005)
+2.0 + 0.0005
-(1.5 + 0.0005)
0.1 + 0.0000
±10V,
±20V
15000-20000
+3.0 + 0.0005
-(1.0 + 0.0005)
+3.0 + 0.0005
-(1.5 + 0.0005)
0.1 + 0.0000
±10V,
±20V
20000-25000
+4.0 + 0.0005
-(1.0 + 0.0005)
+4.0 + 0.0005
-(1.5 + 0.0005)
0.1 + 0.0000
±10V,
±20V
25000-33000
+5.0 + 0.0005
-(1.0 + 0.0005)
+5.0 + 0.0005
-(1.5 + 0.0005)
0.1 + 0.0000
±1V
1-10
±2.0 + 0.0025
±2.0+ 0.0025
0.1 + 0.0000
±1V
10-2000
±0.5 + 0.0025
±1.0+ 0.0025
0.1 + 0.0000
±1V
2000-8000
±0.7 + 0.0025
±1.2 + 0.0025
0.1 + 0.0000
±1V
8000-10000
±1.0 + 0.0025
±1.5 + 0.0025
0.1 + 0.0000
±1V
10000-15000
+1.5 + 0.0025
-(1.0 + 0.0025)
+2.0 + 0.0025
-(1.5 + 0.0025)
0.1 + 0.0000
±1V
15000-20000
+3.0 + 0.0025
-(1.0 + 0.0025)
+3.0 + 0.0025
-(1.5 + 0.0025)
0.1 + 0.0000
±1V
20000-25000
+4.0 + 0.0025
-(1.0 + 0.0025)
+4.0 + 0.0025
-(1.5 + 0.0025)
0.1 + 0.0000
±1V
25000-33000
+5.0 + 0.0025
-(1.0 + 0.0025)
+5.0 + 0.0025
-(1.0 + 0.0025)
0.1 + 0.0000

VR9500 Hardware Manual16
Calibration Verification CONTINUED
Function
Range
Output
Frequency
Hz
Drive Output and Cola/Aux Output
24 Hours
1 Year
Temperature
Coefficient/°C
Voltage
±1V, ±10V
1-10
±2.0 + 0.0005
±2.0 + 0.0005
0.1 + 0.0000
±1V, ±10V
10-10000
±1.0 + 0.0005
±1.5 + 0.0005
0.1 + 0.0000
±1V, ±10V
10000-15000
±1.5 + 0.0005
±2.0 + 0.0005
0.1 + 0.0000
±1V, ±10V
15000-20000
+1.5 + 0.0005
-(3.0 + 0.0005)
+2.0 + 0.0005
-(3.0 + 0.0005)
0.1 + 0.0000
±1V, ±10V
20000-25000
+1.5 + 0.0005
-(5.0 + 0.0005)
+2.0 + 0.0005
-(5.0 + 0.0005)
0.1 + 0.0000
±1V, ±10V
25000-33000
+1.5 + 0.0005
-(10.0 + 0.0005)
+2.0 + 0.0005
-(10.0 + 0.0005)
0.5 + 0.0000
Frequency
±1V, ±10V
3-40
±0.1 + 0.0000
±0.5 + 0.0000
0.01 + 0.0000
±1V, ±10V
40-33000
±0.05 + 0.0000
±0.5 + 0.0000
0.01 + 0.0000
Other manuals for VR9500
2
Table of contents
Other Vibration Research Controllers manuals
Popular Controllers manuals by other brands

Newport
Newport ESP300 Series user manual

gefran
gefran IR-12 Installation and operation manual

Datasensor
Datasensor LB SERIES instruction manual

BFT
BFT ICARO SMART AC A2000 Installation and user manual

Koei Industry
Koei Industry Unic Series Operation manual

Central Boiler
Central Boiler FireStar Operation manual

Carrier
Carrier KVBCN0101CLT Installation instructions and instructions for use

RESEARCH CONCEPTS
RESEARCH CONCEPTS RC2000A DUAL AXIS instructions

Trio
Trio MC508 P848 quick start guide

elgris
elgris ZERO Export manual

Raven
Raven UltraGlide Autoboom Calibration & Operator's Manual

LMI
LMI LIQUITRON DP5000 Series instruction sheet