Viconics R810 Series User manual

R810 & R811 SERIES
POWER SWITCHING MODULES
SOLID STATE RELAYS ( SSR'S )
•240 Vac up to 600 Vac models
•10 Amps up to 75 Amps models
DESCRIPTION
The Viconics R810 & R811 series power switching modules
are designed for cost effective, precise modulation of electric
loads for most electric heating applications.
( Applicable on resistive loads only )
The R810 & R811 series consists of SSR's ( solid state
relays ), c/w factory assembled heatsink for surface or in-
panel mounting.
The R811 series
integrates a special
4"×4" Nema 1
electrical junction box
cover mounting plate
for modulating electric
baseboard
applications.
FEATURES
•Complete with factory installed heatsink
•For surface or in-panel mounting
•CSA approved for Canada and USA
•UL recognized
•Pulse status led for servicing & trouble shooting
( with C24 module )
•2 years warranty
A typical application would be to control a modulating electric
duct heater with Vdc time proportioning pulsed signal from a
PI pulsed room thermostat.
POWER MODULES INSTALLATION
Important.
All external safety devices like: contactors, relays, flow
switch & thermal protections are to be supplied and
installed by other.
When the modules are installed inside a panel, the
enclosure needs to be adequately louvered for proper
ventilation and heat dissipation. Call the factory for the
derating amperage curves for these specific
applications.
Electronic controls require special care for wiring and
startup. To avoid problems, carefully follow the
procedures below.
Look at the wiring diagrams, and study them carefully. Be
sure that you understand how the system is supposed to
work.
A) Location:
1- Can be installed inside a louvered approved cabinet
or with the heatsink mounted externally.
2- Must be installed away from excessive heat source.
3- Nothing must restrain air circulation to the heatsink.
B) Installation:
1- If installed completely inside a cabinet, use the
mounting tabs on the heatsink to secure the power
module to the back plate of the panel.
2- If installed with heatsink outside the cabinet, use the
proper model mounting template for the cut out
dimensions and to check for mounting obstructions.
3- Respect mounting orientation
( this side up ).
4- Mount the heatsink vertically on the side of the
cabinet for proper heat dissipation.
5- Do not relocate the power switching modules on the
heatsink.
HOW TO ORDER
Models Available Maximum
Voltage
Maximum
Amperage Phase
R810-211 Up to 240 V. 10 A. 1 Phase Without cover
R811-211 Up to 240 V. 10 A. 1 Phase With cover
R810-321 Up to 347 V. 25 A. 1 Phase Without cover
R811-321 Up to 347 V. 25 A. 1 Phase With cover
R810-341 Up to 347 V. 45 A. 1 Phase Without cover
R810-421 Up to 480 V. 25 A. 1 Phase Without cover
R811-421 Up to 480 V. 25 A. 1 Phase With cover
R810-441 Up to 480 V. 45 A. 1 Phase Without cover
R810-471 Up to 480 V. 75 A. 1 Phase Without cover
R810-621 Up to 600 V. 25 A. 1 Phase Without cover
R811-621 Up to 600 V. 25 A. 1 Phase With cover
R810-641 Up to 600 V. 45 A. 1 Phase Without cover
R810-671 Up to 600 V. 75 A. 1 Phase Without cover
R811

2
SPECIFICATIONS HIGH VOLTAGE WIRING
Operating
Conditions:
0°C to 80°C ( 32°F to 176°F )
0 % to 95 % R.H. non-condensing
See power derating curves document
Power supply: 4-32 Vdc time proportioning signal into
2KΩresistance.
With C24 module:
24 Vac -15%, +10% 50/60 Hz; 25 mA
General cautions:
•High voltages are present on the terminals of these
devices. Please read all the instruction in this manual
carefully.
•The 45 & 75 Amps models need to be wired with the
supplied high voltage lugs. Attach the wire to the lug
first, then screw the lug to the power module.
•Have the wiring done by a qualified a skilled professional.
•High voltage and amperage can be fatal.
•All wiring must conform with national electrical code
regulations.
•The instrument must be wired before applying power.
•Protect circuits with semi conductor fuses.
•For in panel installation, derating amperage curves are
available from the factory.
Note:
These instruments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable operation in the
field. However, like other such products, they are subject to failure. It is therefore the responsibility of the installer / user / electrical
panel designer to incorporate safety features and devices ( such as relays, flow switch, thermal protections, etc….. ) to protect the
entire system from catastrophic failure.
R810 DIMENSIONS & INSTALLATION
R810 AWeight (LBS)
R810-211 3.0 " 1.80
R810-321 3.0 " 1.80
R810-341 6.5 " 2.40
R810-421 3.0 " 1.80
R810-441 6.5 " 2.40
R810-471 10.0 " 3.50
R810-621 3.0 " 1.80
R810-641 6.5 " 2.40
R810-671 10.0 " 3.50
•Mounting instructions & templates are available from the factory.
•The cutout templates includes holes position for heatsink attachment to the electrical cabinet
•Respect mounting orientation ( this side up ).
•Mount the heatsink vertically on the side of the cabinet for proper heat dissipation.
•If mounted on top or bottom of the cabinet, derate maximum usable amperage by 25%.
•Do not relocate the power switching modules on the heatsink.
R810 typical template: R810 typical installation:
A
Cutout
template
5.25"
2.00"
2.00"
2.50"
Cutout hole
Heatsink contour
Dia=0.19"
A
2.00"
2.50"
"A" Template
5.25"

3
R811 DIMENSIONS & INSTALLATION
Important: Be sure to respect directions & mounting installation to maximize the cooling airflow to the heatsink.
R811 dimensions: R811 typical installation:
5.25"
3.00"
2.00"
4.50"
4.50"
Standard 4 "x 4" junction box
not included
High voltage
wires
Low voltage
control wires
THIS SIDE UP
When the junction box is installed vertically:
If the screw retaining tabs are to the left & the right,
use the 2 outer mounting screws to mount the
heatsink with the proper side up
If the screw retaining tabs are to the top & bottom,
use the 2 inner mounting screws to mount the
heatsink with the proper side up

028-5003 R5 LIT-R8101-E03 4
TYPICAL APPLICATIONS & WIRING
R810 & R811 SSR ( Solid State Relay ) Power Switching Modules For
Temperature Control Of Resistive Electric Heaters.
Wiring
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.com
sales@viconics.com
Pulsed Signal From BAS System
Vdc Pulsed Time Proportioning Output
24 Vac Pulsed Time Proportioning Output
With The Addition Of The C24 Module
OR
Pulsed Room Thermostat
Vdc Pulsed Time Proportioning Output
24 Vac Pulsed Time Proportioning Output
With The Addition Of The C24 Module
L1 To load
( controlled leg
Time proportionning signal
24 Vac with C24 module
24 Vac
L1 To load
( controlled leg )
-+
Time proportionning signal
4-32 Vdc
- to - ( negative ) + to + ( positive )
This manual suits for next models
14
Table of contents
Other Viconics Relay manuals
Popular Relay manuals by other brands

LOVATO ELECTRIC
LOVATO ELECTRIC DCRM 2 manual

Eaton
Eaton EDR-5000 Nstallation, operation and maintenance manual

ABB
ABB TA 75 DU V1000 operating instructions

KEYLESS
KEYLESS RING PICO Terms of Use

RIESE
RIESE SAFE 2 operating instructions

MITSUBISHI ELECTRIC ENGINEERING
MITSUBISHI ELECTRIC ENGINEERING DG2BK1TB Series user manual