manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ABB
  6. •
  7. Relay
  8. •
  9. ABB HU Manual

ABB HU Manual

Instruction
Leaflet
41
-
347.1
S
A
mi
MINI
ABB
Power
T
&
D
Company
Inc
.
Relay
Division
Coral
Springs
,
FL
33065
Type
HU
,
HU
-
1
and
HU
-
4
Transformer
Differential
Relays
Effective
:
April
1991
Supersedes
41
-
347.1
R
,
Dated
April
1987
(
|
)
Denotes
Change
Since
Last
Issue
File
No
.
E
103204
the
restraint
transformers
of
the
HU
and
HU
-
1
relays
are
connected
in
parallel
,
and
the
I
IT
pickup
of
these
relays
is
ten
times
the
relay
tap
value
.
On
the
other
hand
,
the
rectified
outputs
of
the
restraint
transform
-
ers
of
the
HU
-
4
relay
are
connected
in
series
,
and
the
IIT
-
unit
for
this
relay
is
set
at
fifteen
times
the
tap
value
.
Otherwise
,
the
three
relays
are
identical
.
Three
-
winding
banks
normally
require
the
HU
-
1
re
-
lay
,
although
the
auto
transformer
application
uses
the
HU
if
the
tertiary
is
not
loaded
.
The
HU
-
4
is
par
-
ticularly
applicable
to
protect
a
transformer
and
bus
section
combination
.
It
also
may
be
applied
to
three
-
winding
transformers
with
one
side
connected
to
two
breakers
.
CAUTION
Before
putting
relays
into
service
,
remove
all
blocking
which
may
have
been
inserted
for
the
purpose
of
securing
the
parts
during
shipment
,
make
sure
that
all
moving
parts
operate
freely
,
inspect
the
contacts
to
see
that
they
are
clean
and
close
properly
,
and
operate
the
relay
to
check
the
settings
and
electrical
connections
.
These
instructions
apply
to
the
following
types
of
relays
:
•
HU
•
HU
-
1
The
HU
,
HU
-
1
and
HU
-
4
are
available
with
a
sensi
-
tivity
of
either
30
%
or
35
%
times
tap
.
The
30
%
sen
-
sitivity
relay
satisfactorily
handles
up
to
15
%
mis
-
match
(
e
.
g
.
,
±
10
%
transformer
tap
changing
plus
5
%
ct
mismatch
)
.
The
35
%
sensitivity
relay
handles
as
much
as
20
%
mismatch
.
See
Figures
13
and
14
for
a
comparison
of
the
characteristics
of
the
two
sensitivities
.
Any
of
the
relays
may
be
recalibrated
in
the
field
to
obtain
either
characteristic
.
•
HU
-
4
1
.
APPLICATION
The
types
HU
,
HU
-
1
,
and
HU
-
4
relays
are
high
speed
relays
used
in
the
differential
protection
of
transformers
.
These
relays
can
be
applied
where
the
magnetizing
inrush
current
to
the
transformer
is
severe
.
Current
transformer
ratio
error
should
not
exceed
10
%
with
maximum
symmetrical
external
fault
cur
-
rent
flowing
and
the
maximum
symmetrical
error
cur
-
rent
which
is
flowing
in
the
differential
circuit
on
ex
-
ternal
faults
should
not
exceed
10
times
relay
tap
setting
.
The
types
HU
,
HU
-
1
,
and
HU
-
4
relays
have
two
,
three
,
or
four
restraint
transformers
,
respectively
,
and
associated
rows
of
taps
.
The
rectified
outputs
of
Ordinarily
the
30
%
sensitivity
relay
will
suffice
;
how
-
ever
,
where
ct
mismatch
is
abnormally
high
or
where
the
transformer
tap
-
changing
range
exceeds
±
10
%
,
this
calibration
may
be
too
sensitive
.
Z
CONSTRUCTION
The
types
HU
,
HU
-
1
and
HU
-
4
relays
consist
of
a
dif
-
ferential
unit
(
DU
)
,
a
harmonic
restraint
unit
(
HRU
)
,
an
indicating
instantaneous
trip
unit
(
NT
)
and
an
All
possible
contingencies
which
may
arise
during
installation
,
operation
,
or
maintenance
,
and
all
details
and
variations
of
this
equipment
do
not
purport
to
be
covered
by
these
instructions
.
If
further
information
is
desired
by
purchaser
regarding
this
particular
installation
,
operation
or
maintenance
of
this
equipment
,
the
local
Asea
Brown
Boveri
representative
should
be
contacted
.
Printed
in
USA
Courtesy of NationalSwitchgear.com
ro
r
i
*
NI
M
&
Operating
Ckt
.
Resistor
{
DU
)
To
Restraint
Transf
.
4
I
*
Operating
Ckt
.
Resistor
(
DU
)
Hi
t
Harmonic
Restraint
Unit
(
MRU
)
ik
.
AT
-
'
L
.
.
Harmonic
Restraint
Unit
IHRU
)
m
jgj
r
*
i
t
T
.
Differential
Unit
(
DU
)
jj
R
P
?
K
s
Parallel
Reactor
{
HRU
Operate
Filter
)
Differentia
!
Unit
(
DU
)
*
*
s
<
t
T
-
^
TAP
BLOCK
B
Restraint
Transf
.
t
jig
—
Restraint
Transf
.
2
3
—
Restraint
Transf
.
3
(
HU
-
1
Only
)
!
:
-
h
t
\
x
*
TAP
Bl
OCK
Restraint
Transf
.
4
Restraint
Transf
.
t
Restraint
Transf
.
2
Restraint
Transf
.
3
1
’
f
’
VT
r
*
*
t
,
•
i
k
-
j
*
»
1
L
p
igrlt
!
•
»
!
>
§
>
§
’
'
rf
*
1
*
1
*
'
*
1
*
1
*
1
*
LL
I
si
pR
*
lvi
\
*
k
i
i
-
jj
>
li
Restraint
Transformers
{
DU
)
Indicating
Contactor
Switch
(
ICS
)
Restraint
Transformer
(
DU
)
i
w
\
t
%
*
Indicating
Instantaneous
Trip
(
IIT
)
Indicating
Contactor
Switch
(
ICS
)
>
'
:
>
!
|
«
M
Indicating
Instantaneous
Trip
(
IIT
)
To
Restraint
Transf
.
3
(
HU
-
1
Only
)
To
Restraint
Transf
.
2
To
Restraint
Transf
.
1
To
Restraint
Transf
.
3
To
Restraint
Transf
.
2
To
Restraint
Transf
.
1
Figure
1
.
Type
HU
,
HU
-
1
Relays
(
Front
View
)
Figure
2
.
Type
HU
-
4
Relay
(
Front
View
)
Courtesy of NationalSwitchgear.com
...
I
\
s
m
§
:
*
[
3
•
•
f
|
|
f
DU
Restraint
-
Scries
Filter
-
Reactor
(
MRU
Restraint
)
,
iL
*
»
Parallel
Fiiter
-
Reaotor
(
Operate
MRU
)
gif
;
''
7
a
:
.
v
-
.
v
*
-
~
Parallel
Filter
-
Reactor
(
HRU
Restraint
)
m
•
;
m
Series
Filter
-
Reactor
(
Restraint
HRU
)
&
4
7
:
l
'
1
/
t
Parallel
Filter
-
Reactor
(
HRU
Restraint
)
t
.
Operating
Transf
.
(
HRU
)
-
-
i
Operating
Transf
.
(
HRU
)
.
:
t
Operating
Transf
.
(
DU
)
:
vj
j
Operating
Transf
.
(
DU
)
ISIS
*
-
.
7
.
..
E
3
L
»
M
>
J
r
»
M
»
i
L
*
«
*
J
•
1
5
<
3
V
..
=
s
-
v
-
i
’
'
V
,
Operating
Circuit
Filter
Capacitor
(
HRU
)
(
4
MFD
)
\
S
Operating
Circuit
Filter
Capacitor
(
HRU
)
(
4
MFD
)
T
l
:
R
1
Capacitor
--
0.45
MFD
HRU
Restraint
F
liter
Circuit
r
Capacitor
0.45
MFD
HRU
Restraint
F
it
ter
Circuit
&
a
»
£
*
4
«
(
4
Figure
4
.
Type
HU
-
4
Relays
(
Rear
View
)
Figure
3
.
Type
HU
,
HUH
Relays
(
Rear
View
)
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
indicating
contactor
switch
(
ICS
)
.
The
principal
parts
of
the
relays
and
their
locations
are
shown
in
Figures
1
to
7
.
rear
with
two
brass
spacers
and
silver
solder
.
These
non
-
magnetic
joints
represent
air
gaps
,
which
are
bridged
by
two
adjustable
magnetic
shunts
.
The
windings
are
wound
around
a
magnetic
core
.
The
ar
-
mature
is
fastened
to
this
core
and
is
free
to
move
in
the
front
air
gap
.
The
moving
contact
is
connected
to
the
free
end
of
a
leaf
spring
,
which
,
in
turn
,
is
fas
-
tened
to
the
armature
.
2.1
Differential
Unit
(
DU
)
The
differential
unit
of
these
relays
consists
of
re
-
straint
circuits
,
full
wave
rectifiers
,
saturating
operat
-
ing
transformer
,
and
a
dc
polar
unit
.
The
basic
differences
in
the
differential
unit
of
the
three
relays
is
in
the
restraint
circuit
.
The
restraint
circuit
of
the
HU
-
4
relay
consists
of
four
air
-
gap
restraint
transformers
and
four
full
wave
rec
-
tifiers
whose
outputs
are
connected
in
series
.
The
restraint
circuit
of
the
HU
-
1
relay
consists
of
three
air
-
gap
restraint
transformers
and
three
full
wave
rectifiers
whose
outputs
are
connected
in
parallel
.
The
restraint
circuit
of
the
HU
relay
consists
of
two
air
-
gap
restraint
transformers
and
two
full
wave
rec
-
tifiers
whose
outputs
are
connected
in
parallel
.
Each
of
the
restraint
transformers
and
the
operating
transformer
are
provided
with
taps
to
compensate
for
mismatch
of
line
current
transformers
.
These
taps
are
incorporated
in
the
relay
in
such
a
manner
that
changing
a
tap
on
a
restraint
transformer
auto
-
matically
changes
the
same
tap
on
the
operating
transformer
.
2.4
Indicating
Contactor
Switch
Unit
(
ICS
)
The
dc
indicating
contactor
switch
is
a
small
clapper
-
type
device
.
A
magnetic
armature
,
to
which
leaf
-
spring
mounted
contacts
are
attached
,
is
attracted
to
the
magnetic
core
upon
energization
of
the
switch
.
When
the
switch
closes
,
the
moving
contacts
bridge
two
stationary
contacts
,
completing
the
trip
circuit
.
Also
,
during
this
operation
,
two
fingers
on
the
arma
-
ture
deflect
a
spring
located
on
the
front
of
the
switch
,
which
allows
the
operation
indicator
target
to
drop
.
The
front
spring
,
in
addition
to
holding
the
target
,
provides
restraint
for
the
armature
and
thus
controls
the
pick
-
up
value
of
the
switch
.
2.5
Indicating
Instantaneous
Trip
Unit
(
NT
)
The
instantaneous
trip
unit
is
a
small
ac
operated
clapper
type
device
.
A
magnetic
armature
,
to
which
leaf
-
spring
mounted
contacts
are
attached
,
is
at
-
tracted
to
the
magnetic
core
upon
energization
of
the
switch
.
When
the
switch
closes
,
the
moving
contacts
bridge
two
stationary
contacts
completing
the
trip
cir
-
cuit
.
Also
,
during
the
operation
,
two
fingers
on
the
ar
-
mature
deflect
a
spring
located
on
the
front
of
the
switch
which
allows
the
operation
indicator
target
to
drop
.
A
core
screw
accessible
from
the
top
of
the
switch
provides
the
adjustable
pickup
range
.
3
.
OPERATION
The
types
HU
and
HU
-
1
relays
are
connected
to
the
protected
transformer
as
shown
in
Figures
10
and
11
.
The
HU
-
4
is
connected
to
the
protected
trans
-
former
as
shown
in
Figure
12
.
In
such
a
connection
the
relays
operate
to
protect
the
transformer
for
faults
internal
to
the
differential
zone
of
the
trans
-
former
,
but
not
for
faults
external
to
the
zone
.
Neither
do
the
relays
operate
on
magnetizing
inrush
currents
2.2
Harmonic
-
Restraint
Unit
(
HRU
)
The
harmonic
-
restraint
unit
of
the
HU
relays
consists
of
an
air
gap
operating
transformer
,
a
second
har
-
monic
block
filter
,
a
fundamental
block
second
har
-
monic
pass
filter
,
two
full
-
wave
rectifiers
,
indicating
instantaneous
trip
unit
,
varistor
,
and
a
dc
polar
unit
.
Taps
are
also
incorporated
in
this
unit
to
compen
-
sate
for
mismatch
of
the
line
current
transformers
.
Changing
a
tap
on
the
restraint
transformer
of
the
differential
unit
also
changes
the
tap
of
this
unit
.
2.3
Polar
Unit
The
polar
unit
consists
of
a
rectangular
shaped
mag
-
netic
frame
,
an
electromagnet
,
a
permanent
magnet
,
and
an
armature
.
The
poles
of
the
crescent
shaped
permanent
magnet
bridge
the
magnet
frame
.
The
magnetic
frame
consists
of
three
pieces
joined
in
the
4
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
associated
with
energization
of
the
transformer
even
though
these
currents
may
appear
as
an
internal
fault
.
To
avoid
these
false
operations
,
each
unit
of
the
relay
performs
a
separate
function
.
The
differen
-
tial
unit
(
DU
)
prevents
operation
on
an
external
fault
,
while
the
harmonic
-
restraint
unit
(
HRU
)
prevent
op
-
erations
on
magnetizing
inrush
currents
.
Hence
,
the
operation
of
the
relay
can
best
be
described
under
the
headings
of
external
fault
current
,
internal
fault
currents
,
and
magnetizing
inrush
currents
.
and
HU
-
1
relays
and
to
the
sum
of
the
restraint
cur
-
rent
flowing
in
the
HU
-
4
relay
.
The
sum
of
the
re
-
straint
current
flows
into
the
operating
transformer
and
produces
an
excess
of
operating
torque
,
and
the
differential
unit
operates
.
In
the
case
of
an
internal
fault
fed
from
one
source
only
,
the
fault
current
flows
in
one
restraint
trans
-
former
and
the
operating
transformer
.
An
excess
of
operating
torque
is
produced
on
the
differential
unit
and
it
operates
.
Faults
normally
appear
as
an
offset
sine
wave
with
a
decaying
dc
component
,
and
contain
very
few
har
-
monics
.
As
a
result
,
the
harmonic
-
restraint
unit
will
operate
during
internal
faults
to
permit
tripping
of
the
relay
.
For
heavy
internal
faults
,
the
indicating
instanta
-
neous
trip
unit
(
NT
)
will
operate
.
Since
this
unit
is
connected
to
an
air
gap
transformer
,
essentially
only
the
sine
wave
component
of
an
internal
fault
is
ap
-
plied
to
the
NT
unit
.
The
dc
component
of
the
fault
is
bypassed
by
the
transformer
primary
.
The
varistor
connected
across
the
dc
side
of
the
re
-
straint
rectifier
of
the
harmonic
restraint
unit
prevents
excessive
voltage
peaks
from
appearing
across
the
rectifiers
.
These
peaks
arise
through
transformer
ac
-
tion
of
the
harmonic
-
restraint
polar
-
unit
coils
during
heavy
internal
faults
.
The
varistor
has
a
large
value
of
resistance
for
low
voltages
,
while
presenting
a
low
value
of
resistance
for
high
voltages
.
This
character
-
istics
effectively
reduces
the
voltage
spikes
on
heavy
internal
faults
while
not
hampering
perfor
-
mance
during
inrush
,
where
the
voltage
is
consider
-
ably
lower
.
3.1
External
Fault
Currents
The
HU
family
of
relays
have
a
variable
percentage
characteristic
.
This
means
that
the
operating
current
required
to
close
the
contact
of
the
differential
unit
expressed
in
percent
of
restraint
varies
with
the
magnitude
of
the
larger
restraint
current
in
the
HU
and
HU
-
1
current
relays
and
with
the
sum
of
the
re
-
straint
current
in
the
HU
-
4
relays
.
Figures
13
and
14
illustrate
these
characteristics
.
To
use
these
curves
,
divide
each
restraint
current
by
the
appropriate
tap
and
enter
the
horizontal
axis
using
the
larger
or
larg
-
est
restraint
multiple
.
Then
enter
the
vertical
axis
,
us
-
ing
the
difference
of
the
restraint
multiples
.
With
the
relay
connected
as
shown
in
the
schematic
diagram
of
Figure
15
a
,
an
external
fault
causes
cur
-
rent
to
flow
in
the
air
-
gap
restraint
transformers
of
the
differential
unit
.
If
the
line
current
transformers
do
not
saturate
and
the
correct
ratio
matching
taps
ap
-
plied
,
no
effective
current
flows
in
the
operating
transformer
of
the
relay
.
Hence
,
only
contact
-
open
-
ing
torque
is
produced
on
the
differential
unit
.
On
heavy
external
faults
where
a
main
current
trans
-
former
saturates
,
current
flows
in
the
operating
cir
-
cuit
of
the
relay
.
With
such
a
condition
,
the
harmonic
-
restraint
unit
may
or
may
not
close
its
contacts
,
de
-
pending
upon
the
harmonics
present
in
the
false
op
-
erating
current
.
However
,
operation
of
the
relay
is
prevented
by
the
variable
percentage
characteristic
of
the
differential
unit
,
since
a
large
differential
cur
-
rent
is
required
to
close
its
contacts
during
heavy
ex
-
ternal
faults
.
3.3
Magnetizing
Inrush
Currents
Magnetizing
inrush
current
waves
have
various
wave
shapes
.
A
typical
wave
appears
as
a
rectified
half
wave
with
decaying
peaks
.
In
any
case
,
the
var
-
ious
wave
shapes
are
rich
in
harmonics
with
the
sec
-
ond
harmonic
predominant
.
Since
the
second
har
-
monic
is
always
present
in
inrush
waves
and
not
in
internal
fault
waves
,
this
harmonic
is
used
to
restrain
the
harmonic
-
restraint
unit
during
inrushes
.
The
dif
-
ferential
unit
may
or
may
not
close
its
contacts
,
de
-
pending
on
the
magnitude
of
the
inrush
.
3.2
Internal
Faults
In
the
case
of
an
internal
fault
as
shown
in
Figure
15
b
,
the
restraint
of
the
differential
unit
is
proportion
-
al
to
the
largest
restraint
current
flowing
in
the
HU
5
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
When
a
magnetizing
inrush
wave
is
applied
to
the
re
-
lay
,
the
dc
component
of
the
wave
is
bypassed
by
the
air
-
gap
operating
transformer
.
The
other
compo
-
nents
are
fed
into
the
filter
circuits
.
The
impedance
characteristics
of
these
filters
are
such
that
the
sec
-
ond
harmonic
component
flows
into
the
restraint
coil
of
the
polar
unit
,
while
the
other
harmonics
flow
into
the
operating
coil
.
The
polar
unit
will
not
close
its
contacts
unless
the
second
harmonic
content
is
less
than
15
percent
of
the
fundamental
component
.
be
approximately
1.0
volt
.
Use
Figure
17
if
the
pick
-
up
is
0.35
times
tap
.
Pickup
of
the
harmonic
-
restraint
unit
and
the
differ
-
ential
unit
is
either
30
or
35
%
of
tap
value
current
.
Pick
up
of
the
indicating
instantaneous
trip
unit
is
10
times
tap
value
current
for
the
HU
and
the
HU
-
1
re
-
lay
and
15
times
tap
value
current
for
the
HU
-
4
.
Components
of
the
harmonic
-
restraint
unit
are
se
-
lected
such
that
15
%
second
harmonic
will
prevent
operation
of
the
unit
.
This
factor
is
adequate
to
pre
-
vent
false
operation
on
inrushes
.
The
frequency
response
of
the
HU
and
HU
-
1
60
Hz
relays
is
shown
in
Figure
19
and
,
for
the
HU
and
HU
-
1
50
Hz
relays
is
shown
in
Figure
28
.
The
indicating
instantaneous
trip
unit
(
NT
)
will
not
op
-
erate
on
inrush
.
The
air
-
gap
transformer
will
bypass
Ihe
dc
component
of
the
inrush
thereby
reducing
the
magnitude
of
the
wave
applied
to
the
IIT
unit
.
If
the
inrush
has
an
initial
peak
of
16
times
tap
-
value
cur
-
rent
,
the
air
-
gap
transformer
will
reduce
this
peak
to
approximately
8
times
tap
value
on
the
secondary
of
the
transformer
.
4.1
Trip
Circuit
The
main
contacts
will
safely
close
30
amperes
at
250
volts
dc
,
and
the
seal
-
in
contacts
of
the
indicat
-
ing
contactor
switch
will
safely
carry
this
current
long
enough
to
trip
a
circuit
breaker
.
The
indicating
contactor
switch
has
two
taps
that
provide
a
pick
-
up
setting
of
0.2
or
2
amperes
.
To
change
taps
requires
connecting
the
lead
located
in
front
of
the
tap
block
to
the
desired
setting
by
means
of
a
screw
connection
3.4
Breaker
Maintenance
Before
some
of
the
ct
’
s
are
bypassed
for
breaker
maintenance
the
trip
circuit
should
be
opened
,
as
shown
in
Figures
9
through
12
.
Otherwise
the
false
-
unbalanced
current
will
cause
the
relay
to
trip
.
It
is
not
necessary
to
short
-
circuit
the
relay
operating
cir
-
cuit
since
it
has
an
adequate
continuous
-
current
rat
-
ing
.
(
See
“
Energy
Requirements
”
)
.
4
.
CHARACTERISTICS
Taps
are
incorporated
in
the
HU
family
of
relays
to
compensate
for
main
current
transformer
mismatch
.
These
taps
are
as
follows
:
2.9
,
3.2
,
3.5
,
3.8
,
4.2
,
4.6
,
5.0
,
8.7
.
To
measure
the
effective
unbalance
,
a
sensitive
low
-
reading
voltmeter
(
5000
ohms
per
volts
)
can
tempo
-
rarily
be
connected
across
the
operating
coil
resistor
(
at
top
of
case
)
.
With
a
perfect
balance
,
the
voltmeter
reading
will
be
zero
.
The
reading
should
not
exceed
the
values
indicated
by
the
15
%
mismatch
curve
at
Figure
16
when
the
relay
pickup
is
0.30
times
tap
.
If
the
amount
of
mismatch
is
measured
or
calculated
,
the
measured
voltage
can
be
checked
against
the
in
-
terpolated
value
from
the
curve
.
For
example
,
as
-
sume
that
the
larger
restraint
current
is
measured
as
1.5
tap
multiple
and
the
calculated
mismatch
is
7
%
.
Then
,
from
Figure
16
the
measured
voltage
should
5
.
SETTING
CAUTION
Since
the
tap
block
screw
carries
operating
cur
-
rent
,
be
sure
that
the
screws
are
turned
tight
.
In
order
to
avoid
opening
current
transformer
circuits
when
changing
taps
under
load
,
the
re
-
lay
must
be
first
removed
from
the
case
.
Chassis
operating
shorting
switches
on
the
case
will
short
the
secondary
of
the
current
transformer
.
The
taps
should
then
be
changed
with
the
relay
outside
of
the
case
and
then
reinserted
into
the
case
.
To
set
the
relay
,
calculations
must
be
performed
as
shown
under
“
Setting
Calculations
”
.
After
the
correct
tap
is
determined
,
connections
can
be
made
to
the
relay
transformers
by
placing
the
connector
screws
in
the
various
terminal
-
plate
holes
in
front
of
the
re
-
lay
.
Only
one
tap
screw
should
be
inserted
in
any
horizontal
row
of
taps
.
6
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
5.1
Indicating
Contactor
Switch
(
ICS
)
No
setting
is
required
on
the
ICS
unit
except
the
se
-
lection
of
the
0.2
or
2.0
ampere
tap
setting
.
This
se
-
lection
is
made
by
connecting
the
lead
located
in
front
of
the
tap
block
to
the
desired
setting
by
means
of
the
connecting
screw
.
When
the
relay
energizes
a
125
-
or
250
-
volt
dc
type
WL
relay
switch
,
or
equiva
-
lent
,
use
the
0.2
ampere
tap
;
for
48
volt
dc
applica
-
tions
set
relay
in
2
tap
and
use
Type
WL
Relay
coil
S
#
304
C
209
G
01
or
equivalent
.
Trip
Circuit
Constants
Indicating
Contactor
Switch
(
ICS
)
6.2
Definitions
of
Terms
Ip
=
Primary
current
at
(
KVA
)
M
IR
=
Relay
input
current
at
(
KVA
)
M
IRH
,
IRL
.
IRI
ate
same
as
IR
except
for
high
,
low
and
intermediate
voltage
sides
respec
-
tively
.
Is
=
ct
secondary
current
at
(
KVA
)
M
T
=
relay
tap
setting
.
TH
,
TL
,
Tl
=
are
same
as
T
except
for
high
,
low
and
intermediate
voltage
windings
,
re
-
spectively
.
N
=
Number
of
current
transformer
turns
that
are
in
use
.
Np
=
N
/
NT
(
Proportion
of
total
turns
in
use
)
Nj
=
Current
transformer
ratio
,
full
tap
VCL
=
“
C
”
accuracy
class
voltage
ZA
=
Burden
impedance
of
any
devices
other
than
the
HU
,
HU
-
1
,
or
HU
-
4
relays
,
with
maximum
external
fault
current
flowing
.
•
ext
=
max
symmetrical
external
fault
current
in
sec
-
ondary
RMS
amperes
.
Zj
=
Total
secondary
burden
in
ohms
(
excluding
current
transformer
winding
resistance
.
)
0.2
ampere
tap
-
6.5
ohms
dc
resistance
2.0
ampere
tap
-
0.15
ohm
dc
resistance
5.2
Indicating
Instantaneous
Trip
(
IIT
)
No
setting
is
required
on
the
indicating
instanta
-
neous
trip
unit
.
This
unit
is
set
at
the
factory
to
pickup
as
follows
:
•
HU
/
HU
-
1
Relays
10
times
tap
value
current
•
HU
-
4
Relay
15
times
tap
value
current
6
.
SETTING
CALCULATIONS
Select
the
ratio
matching
taps
.
There
are
no
other
settings
.
In
order
to
calculate
the
required
tap
set
-
tings
and
check
current
transformer
performance
the
following
information
is
required
.
6.3
Calculation
Procedure
a
.
Select
current
transformer
taps
,
where
multi
-
ra
-
tion
types
are
used
.
Select
a
tap
to
give
approximately
5
amperes
at
maximum
load
.
This
will
provide
good
sensitivity
and
will
produce
no
thermal
problem
to
the
ct
.
,
the
leads
,
or
the
relay
.
Better
sensitivity
can
be
achieved
by
selecting
a
tap
to
give
more
than
5
amperes
if
a
careful
check
is
made
of
the
ct
,
the
leads
,
and
the
relay
capabil
-
ity
.
For
determining
the
required
continuous
rating
of
the
relay
,
use
the
expected
two
hour
maximum
load
,
since
the
relay
reaches
final
temperature
in
this
time
.
b
.
Calculate
the
relay
currents
,
IR
.
All
relay
currents
for
relay
tap
selection
should
be
based
on
the
same
KVA
capacity
.
c
.
Calculate
the
relay
current
ratio
(
s
)
using
the
low
-
est
current
as
reference
.
6.1
Required
Information
a
.
Maximum
transformer
power
rating
(
KVA
)
M
b
.
Maximum
external
fault
currents
c
.
Line
-
to
-
Line
voltage
ratings
of
power
transformer
(
VH
.
VI
.
VJ
d
.
Current
transformer
ratios
,
full
tap
(
Nj
)
e
.
Current
transformer
“
C
”
accuracy
class
voltage
(
or
excitation
or
ratio
correction
factor
curve
)
f
.
One
way
current
transformer
lead
resistance
at
25
°
C
(
RL
)
.
When
using
excitation
curve
,
include
ct
winding
resistance
.
g
.
Current
transformer
connections
(
wye
or
delta
)
ct
secondary
winding
resistance
,
Rs
-
7
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
d
.
Select
the
tap
ratio
as
close
as
possible
to
relay
current
ratio
from
Table
1
.
Choose
the
first
relay
tap
ratio
using
the
largest
current
ratio
from
step
3
.
The
other
tap
ratios
should
be
determined
us
-
ing
the
lower
tap
from
the
first
tap
ratio
as
reference
.
IR
should
not
exceed
relay
continuous
rating
as
defined
in
Energy
Requirement
Table
.
e
.
Check
IIT
operation
.
The
IIT
pickup
is
ten
times
the
relay
tap
value
for
the
HU
and
HU
-
1
,
or
15
times
tap
value
for
the
HU
-
4
.
Therefore
,
the
max
-
imum
symmetrical
error
current
which
is
flowing
in
the
differential
circuit
on
external
fault
current
due
to
dissimilar
ct
saturation
should
not
exceed
10
or
15
times
relay
tap
.
f
.
Determine
Mismatch
For
2
winding
banks
:
relay
ing
accuracy
classif
ication
.
If
the
“
C
”
accura
-
cy
is
used
,
performance
will
be
adequate
if
:
[
NpVci
-
(
lext
-
100
)
Rs
]
/
lext
is
greater
than
Zj
(
2
)
NOTE
:
Let
lext
=
100
where
maximum
external
fault
current
is
less
than
100
A
.
For
wye
-
connected
ct
:
Zj
=
lead
resistance
+
relay
burden
+
2
A
=
1.13
(
Rl
+
+
ZA
)
ohms
(
3
)
(
R
|
_
multiplier
,
1.13
,
is
used
to
account
for
0.15
temperature
rise
during
faults
.
proximation
.
Use
2
way
lead
resistance
for
single
phase
to
ground
fault
.
For
delta
-
connected
ct
:
an
ap
-
T
/
*
RL
_
\
\
VI
V
RH
0
)
%
mismatch
=
100
S
0.15
+
ZA
)
ohms
^
ZT
=
3
(
1.13
RL
+
where
S
is
the
smaller
of
the
two
terms
,
T
0.45
W
or
(
4
)
=
3.4
(
RL
+
T
+
3
Za
)
h
.
Examples
:
Refer
to
Tables
6
and
7
and
Figure
20
for
setting
ex
-
amples
.
For
3
winding
banks
:
Repeat
calculation
of
equation
(
1
)
and
apply
sim
-
ilar
equations
to
calculate
mismatch
from
the
intermediate
to
high
and
from
and
from
the
inter
-
mediate
to
low
voltage
windings
.
Where
tap
changing
under
the
load
is
performed
the
relays
should
be
set
on
the
basis
of
the
middle
or
neutral
tap
position
.
The
total
mismatch
,
includ
-
ing
the
automatic
tap
change
should
not
exceed
15
%
with
a
30
%
sensitivity
relay
,
and
20
%
with
a
35
%
sensitivity
relay
.
Note
from
Figures
13
and
14
that
an
ample
safety
margin
exists
at
these
lev
-
els
of
mismatch
.
g
.
Check
current
transformer
performance
.
Ratio
er
-
ror
should
not
exceed
10
%
with
maximum
symmetrical
external
fault
current
flowing
.
An
ac
-
curate
method
of
determining
ratio
error
is
to
use
ratio
-
correction
-
factor
curves
(
RCF
)
.
A
less
accu
-
rate
,
but
satisfactory
method
is
to
utilize
the
ANSI
t
The
factor
of
3
accounts
for
conditions
existing
during
a
phase
fault
.
Table
1
HU
Relay
Tap
Ratios
TAP
8.7
2.9
5.0
3.2
3.5
3.8
4.2
4.6
3.000
2.9
1.000
1.103
1.586
1.724
1.207
1.310
1.448
3.2
1.563
2.719
1.000
1.094
1.188
1.313
1.438
2.486
3.5
1.000
1.086
1.200
1.314
1.429
2.289
3.8
1.316
1.000
1.105
1.211
2.071
1.190
4.2
1.000
1.095
1.087
1.890
4.6
1.000
1.740
5.0
1.000
1.000
8.7
8
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
than
the
lower
polar
unit
.
However
,
if
the
pickup
val
-
ue
is
considered
to
be
too
low
,
it
should
be
checked
after
applying
a
polarizing
current
magnitude
of
20
times
tap
value
to
relay
terminals
3
and
7
.
This
will
cause
the
upper
polar
unit
to
pickup
at
a
current
of
approximately
1.65
amperes
.
7
.
INSTALLATION
The
relays
should
be
mounted
on
switchboard
pan
-
els
or
their
equivalent
in
a
location
free
from
dirt
moisture
,
excessive
vibration
and
heat
.
Mount
the
relay
vertically
by
means
of
the
four
mounting
holes
on
the
flange
for
semi
-
flush
mounting
,
or
by
means
of
the
rear
mounting
stud
or
studs
for
projection
mounting
.
Either
a
mounting
stud
or
the
mounting
screws
may
be
utilized
for
grounding
the
relay
.
The
electrical
connections
may
be
made
directly
to
the
terminals
by
means
of
screws
for
steel
-
panel
mount
-
ing
or
to
the
terminal
studs
furnished
with
the
relay
for
thick
panel
mounting
.
The
terminal
studs
may
be
easily
removed
or
inserted
by
locking
two
nuts
on
the
stud
and
then
turning
the
proper
nut
with
a
wrench
.
For
detailed
FT
case
information
,
refer
to
I
.
L
.
41
-
076
.
8.1
.
2
Indicating
Instantaneous
Trip
Pickup
.
With
switch
open
and
relay
set
on
the
number
5
tap
,
apply
current
specified
in
following
table
to
relay
.
In
-
stantaneous
trip
should
pickup
and
its
target
should
drop
freely
:
HU
/
HU
-
1
HU
-
4
50
amperes
75
amperes
The
contact
gap
should
be
approximately
0.094
inches
between
the
bridging
moving
contact
and
the
adjustable
stationary
contacts
.
The
bridging
moving
contact
should
touch
both
stationary
contacts
simul
-
taneously
.
8
.
ADJUSTMENTS
AND
MAINTENANCE
The
proper
adjustments
for
correct
operation
of
this
relay
have
been
made
at
the
factory
and
should
not
be
disturbed
after
receipt
by
the
customer
.
8.1
.
3
Indicating
Contactor
Switch
(
ICS
)
Block
contacts
of
the
polar
units
closed
.
Pass
suffi
-
cient
direct
current
through
the
trip
circuit
to
close
the
contacts
of
the
ICS
.
This
value
of
current
should
be
not
greater
than
the
particular
tap
setting
being
used
.
The
operation
-
indicator
target
should
drop
freely
.
8.1
Performance
Check
The
following
check
is
recommended
to
verify
that
the
relay
is
in
proper
working
order
.
All
checks
can
best
be
performed
by
connecting
HU
and
HU
-
1
re
-
lays
per
test
circuit
of
Figure
21
and
the
HU
-
4
relay
per
test
circuit
of
Figure
22
.
Relays
must
be
tested
in
the
case
.
8.1
.
4
Differential
Characteristic
a
.
Close
switch
to
position
1
.
Set
lac
to
zero
and
ISR
to
either
28
amperes
for
HU
/
HU
-
1
relays
or
38
amperes
for
HU
-
4
relay
.
Adjust
lac
to
20
amperes
.
Check
the
operating
point
for
the
relay
by
gradu
-
ally
adjusting
ISR
.
Operation
should
occur
between
the
following
limits
:
8.1
.
1
Minimum
Trip
Circuit
.
NOTE
:
The
moving
contact
of
the
upper
polar
unit
(
HRU
)
closes
to
the
left
-
hand
(
front
view
)
stationary
contact
.
The
moving
contact
of
the
lower
polar
unit
(
DU
)
clos
-
es
to
the
right
hand
(
front
view
)
station
-
ary
contact
.
Relay
Type
ILR
lac
With
SPDT
switch
open
and
relay
set
on
5
-
ampere
tap
,
apply
1.35
to
1.65
amperes
for
the
30
%
sensitiv
-
ity
relay
and
1.6
to
1.9
amperes
for
the
35
%
sensitiv
-
ity
relay
.
The
upper
polar
unit
(
HRU
)
should
operate
.
The
upper
polar
unit
may
operate
for
lower
currents
,
but
not
below
1.0
ampere
.
This
low
pickup
will
not
impair
its
operation
on
magnetizing
inrush
currents
and
should
not
be
disturbed
if
it
is
found
to
be
less
45
to
50
amps
.
HU
/
HU
-
1
20
amps
53
to
56
amps
.
HU
-
4
20
amps
.
b
.
For
30
%
Sensitivity
Relays
:
Close
switch
posi
-
tion
1
.
Set
lac
to
zero
and
adjust
ISR
to
either
10
amperes
for
HU
/
HU
-
1
relays
or
6
amperes
for
9
Courtesy of NationalSwitchgear.com
I
.
L
.
41
-
347.1
S
HU
-
4
relays
.
Increase
lac
to
2.8
amperes
.
If
the
lower
polar
unit
does
not
operate
,
lower
IgR
.
The
relay
should
operate
between
the
following
limits
:
9
.
IN
SERVICE
TEST
Refer
to
the
Tables
2
combinations
.
3
,
or
4
for
different
tap
All
relays
should
be
checked
at
least
once
every
year
or
at
such
other
time
intervals
as
may
be
dictat
-
ed
by
experience
to
be
suitable
to
the
particular
application
.
All
contacts
should
be
periodically
cleaned
.
A
con
-
tact
burnisher
style
#
182
A
836
H
01
is
recommended
for
this
purpose
.
The
use
of
abrasive
material
for
cleaning
contacts
is
not
recommended
,
because
of
the
_
danger
of
embedding
small
particles
in
the
face
of
the
soft
silver
and
thus
impairing
the
contact
.
All
checks
can
be
performed
by
connecting
the
relay
per
the
test
circuit
of
Figures
21
or
22
.
Relays
to
be
tested
in
their
case
.
Relay
Type
lac
*
LR
HU
/
HU
-
1
2.8
to
2.95
amps
11.8
to
12.8
amps
HU
-
4
2.8
to
2.95
amps
8.0
to
9.1
amps
c
.
Reverse
leads
to
restraint
transformers
and
re
-
peat
differential
test
outlined
in
paragraphs
a
and
b
.
Results
should
be
approximately
the
same
as
obtained
under
these
paragraphs
.
d
.
For
35
%
Sensitivity
Relays
:
Close
switch
to
po
-
sition
1
.
Set
lac
to
zero
and
adjust
ISR
to
either
9
amperes
for
HU
/
HU
-
1
relays
or
5
amperes
for
HU
-
4
relays
.
Increase
lac
to
2.8
amperes
.
If
the
lower
polar
unit
does
not
operate
lower
ISR
.
The
lower
polar
unit
should
operate
between
the
fol
-
lowing
limits
.
In
the
HU
relay
,
terminal
5
supplies
the
upper
tap
block
and
Terminal
7
supplies
the
lower
tap
block
.
In
the
HU
-
1
,
Terminal
5
supplies
the
first
(
upper
)
tap
block
,
Terminal
7
supplies
the
second
tap
block
and
Terminal
9
supplies
the
lower
tap
block
.
In
the
HU
-
4
,
Terminal
13
supplies
the
first
(
upper
)
tap
block
,
Ter
-
minal
5
supplies
the
second
tap
block
,
Terminal
7
supplies
the
third
tap
block
and
Terminal
9
supplies
the
lower
tap
block
.
ISR
should
be
connected
to
the
Terminal
with
the
lowest
tap
setting
.
Relay
Type
ac
ILR
HU
/
HU
-
1
2.8
to
2.95
amps
10.8
to
11.8
amps
HU
-
4
2.8
to
2.95
amps
7.0
to
7.8
amps
9.1
Minimum
Trip
9.1
.
1
Lower
Unit
(
Differential
)
With
S
.
P
.
D
.
T
.
switch
open
,
the
lower
polar
unit
in
a
30
%
relay
should
operate
with
lac
between
30
%
and
31
%
of
the
setting
of
the
tap
block
corresponding
to
the
terminal
conducting
ILR
.
For
35
%
relays
,
opera
-
tion
should
occur
between
34
%
and
36
%
of
tap
setting
.
e
.
Reverse
leads
to
restraint
transformers
and
re
-
peat
differential
test
outlined
in
paragraphs
a
and
d
.
Results
should
be
approximately
the
same
as
obtained
under
these
paragraphs
.
8.1
.
5
Harmonic
Restraint
Characteristic
Close
switch
to
position
2
.
Short
out
ILR
ammeter
.
Set
ldc
t
°
4
amperes
and
adjust
!
ac
until
upper
polar
unit
operates
.
Iac
should
read
between
6.5
and
9
amperes
.
Upper
Unit
(
Harmonic
Restraint
)
With
S
.
P
.
D
.
T
.
switch
open
,
the
upper
polar
unit
should
operate
with
lac
between
27
%
and
33
%
of
the
setting
of
the
tap
block
corresponding
to
the
terminal
conducting
ILR
.
The
application
of
a
polarizing
cur
-
rent
of
20
times
ILR
tap
value
current
between
Ter
-
minal
3
and
the
terminal
conducting
ILR
,
will
make
9.1
.
2
As
shown
in
Figure
23
,
these
values
of
alternating
current
correspond
to
17
percent
and
14
percent
second
harmonic
.
10
Courtesy of NationalSwitchgear.com
I
.
L
.
41
-
347.1
S
10
.
CALIBRATION
Use
the
following
procedure
for
calibrating
the
relay
if
the
relay
has
been
taken
apart
for
repairs
or
the
ad
-
justments
disturbed
.
This
procedure
should
not
be
used
until
it
is
apparent
that
the
relay
is
not
in
proper
working
order
.
All
adjustments
to
be
done
with
relay
inside
its
case
.
(
See
Section
8.1
,
Performance
Check
)
.
10.1
Indicating
Contactor
Switch
For
proper
contact
adjustment
,
insert
a
.
030
”
”
feeler
gauge
between
the
core
pin
and
the
armature
.
Hold
the
armature
closed
against
the
core
pin
and
gauge
and
adjust
the
stationary
contacts
such
that
they
just
make
with
the
moving
contact
.
Both
stationary
con
-
tacts
should
make
at
approximately
the
same
time
.
The
contact
follow
will
be
approximately
1
/
64
”
to
3
/
64
”
.
the
polar
unit
operate
at
the
upper
limit
of
the
mini
-
mum
trip
range
.
9.2
Differential
Characteristics
To
check
the
differential
characteristics
of
a
relay
us
-
ing
any
tap
combination
,
close
switch
to
position
1
.
Tables
2
,
3
,
and
4
give
values
of
lac
necessary
to
op
-
erate
the
relay
when
using
a
value
of
ISR
equal
to
3
times
tap
value
for
all
taps
except
the
8.7
tap
.
A
val
-
ue
of
ISR
equal
to
2
times
tap
value
was
chosen
for
the
8.7
tap
setting
in
order
to
keep
the
current
a
con
-
venient
value
for
testing
.
Table
2
refers
to
30
%
HU
relays
,
for
35
%
HU
relay
,
values
of
lac
will
be
0.1
to
0.2
amperes
higher
.
Example
:
(
for
HU
Relay
)
Upper
tap
block
tap
3.5
Lower
tap
block
tap
5.0
10.2
Polar
Units
10.2
.
1
Contacts
Since
the
upper
tap
block
has
the
smaller
tap
setting
ISR
should
be
connected
to
the
upper
tap
block
or
equivalently
into
Terminal
5
and
I
[
_
R
should
be
con
-
nected
into
Terminal
7
.
From
Table
2
under
“
Re
-
straint
”
transformer
:
tap
“
Larger
”
=
5
and
“
Smaller
”
=
3.5
find
ISR
which
in
this
case
is
10.5
and
lac
which
is
between
8.3
and
9.2
amps
.
NOTE
:
In
adjusting
either
the
stationary
contact
or
backstop
,
the
screw
in
the
elongated
holes
of
the
assemblies
should
be
loos
-
ened
,
not
removed
,
during
the
adjust
-
ment
procedure
.
a
.
Upper
Unit
(
HRU
)
Place
a
0.065
to
0.070
inch
feeler
gauge
between
the
right
hand
(
front
view
)
pole
face
and
the
arma
-
ture
.
This
gap
should
be
measured
near
the
front
of
the
right
hand
pole
face
.
Bring
up
the
right
hand
(
front
view
)
backstop
until
it
just
makes
with
the
mov
-
ing
contact
.
Tighten
the
screw
in
the
elongated
hole
of
the
backstop
and
remove
gauge
.
Place
a
0.046
feeler
gauge
between
the
moving
contact
and
the
stationary
on
the
left
hand
(
front
view
)
side
of
the
po
-
lar
unit
.
Bring
up
the
stationary
contact
until
it
just
makes
with
the
gauge
.
Tighten
mounting
screw
in
the
elongated
hole
of
the
stationary
and
remove
gauge
.
b
.
Lower
Unit
(
DU
)
Place
a
0.065
to
0.070
inch
feeler
gauge
between
the
left
hand
(
front
view
)
pole
face
and
the
armature
.
This
gap
should
be
measured
near
the
front
of
the
right
hand
pole
face
.
Bring
up
the
left
hand
(
front
To
check
the
third
restraint
winding
on
the
HU
-
1
re
-
lay
,
repeat
the
procedure
using
Terminal
9
and
ei
-
ther
Terminal
5
or
7
.
Follow
the
same
procedure
to
check
the
third
and
fourth
restraint
windings
in
the
HU
-
4
,
using
Terminal
9
with
either
Terminal
5
or
7
for
the
third
restraint
check
and
Terminal
13
with
5
or
7
for
the
fourth
restraint
check
.
9.3
Harmonic
Restraint
Characteristic
Close
switch
to
position
2
.
Short
out
ILR
meter
.
Ad
-
just
direct
current
until
l
<
jC
reads
0.8
times
tap
setting
for
the
tap
block
corresponding
to
the
terminal
which
conducted
ILR
.
Gradually
increase
alternating
cur
-
rent
(
lac
)
until
upper
polar
unit
operates
.
Iac
should
read
between
1.3
and
1.8
times
the
same
tap
set
-
ting
.
Note
that
this
test
is
responsive
to
harmonics
which
might
be
in
lac
.
Such
harmonics
will
result
in
a
different
operate
value
.
11
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
TABLE
2
Tap
Combination
Currents
30
%
AND
35
%
HU
and
HU
-
1
Relay
Restraint
Transformer
Tap
8.7
4.6
5.0
4.2
3.8
3.5
3.2
Larger
2.9
CURRENT
IN
AMPERES
Smaller
5.8
8.7
8.7
8.7
8.7
8.7
ISR
8.7
8.7
16.2
10.4
9.0
7.8
5.8
lAC
(
Min
.
)
lAc
(
Max
.
)
5.0
2.6
3.7
2.9
17.9
11.6
8.6
10.0
6.4
4.0
5.5
2.8
6.4
9.6
9.6
9.6
9.6
9.6
•
SR
9.6
9.6
15.7
6.9
8.1
4.9
lAc
(
Min
.
)
lAc
(
Max
.
)
2.7
4.0
3.2
17.3
10.6
9.0
7.6
5.4
3.1
4.4
7.0
10.5
10.5
10.5
10.5
10.5
ISR
8.3
14.5
6.9
3.8
5.7
lAC
(
Min
.
)
lAc
(
Max
.
)
3.0
3.5
16.1
9.2
6.3
7.7
4.2
3.3
7.6
11.4
11.4
11.4
11.4
•
SR
14.1
7.9
6.5
5.2
3.2
lAc
(
Min
.
)
lAc
(
Max
.
)
3.8
16.0
8.7
7.2
3.6
5.7
8.4
12.6
12.6
12.6
ISR
12.9
6.2
3.5
4.7
lAC
(
Min
.
)
lAc
(
Max
.
)
4.2
14.2
6.9
5.2
3.9
13.8
9.2
13.8
•
SR
12.4
5.3
3.9
lAC
(
Min
-
)
lAc
(
Max
.
)
4.6
13.7
5.9
4.3
10.0
15.0
ISR
11.6
4.3
lAC
(
Min
.
)
lAc
(
Max
.
)
5.0
12.9
4.8
17.4
•
SR
5.0
lAC
(
Min
.
)
lAc
(
Max
.
)
8.7
5.5
12
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
TABLE
3
Tap
Combination
Currents
30
%
HU
-
4
Relay
Restraint
Transformer
Tap
Larger
2.9
3.2
3.5
3.8
4.2
4.6
5.0
8.7
Smaller
CURRENT
IN
AMPERES
ISR
8.7
8.7
8.7
8.7
8.7
8.7
8.7
5.8
lAc
(
Min
.
)
lAc
(
Max
.
)
2.9
3.9
5.2
6.7
7.6
9.8
11.3
13.8
18.9
4.3
5.8
7.4
8.4
10.8
12.5
14.4
20.9
ISR
9.0
9.6
9.6 9.6
9.6
9.6
6.4
lAC
(
Min
.
)
lAc
(
Max
.
)
3.2
4.3
5.9
6.8
9.0
10.5
12.2
18.4
4.8
6.5
7.6
10.0
13.5
11.6
20.3
ISR
10.5
10.5
10.5
10.5
10.5
7.0
lAc
(
Min
.
)
lAC
(
Max
.
)
3.5
4.7
5.7
7.9
9.3
10.9
17.3
5.2
6.3
8.7
10.2
12.0
19.2
*
SR
11.4
11.4
11.4
11.4
7.6
lAC
(
Min
.
)
lAC
(
Max
.
)
3.8
5.1
7.4
8.8
10.5
17.1
5.6
8.2
9.7
11.6
18.9
ISR
12.6
12.6
12.6
8.4
lAC
(
Min
.
)
lAc
(
Max
-
)
4.2
5.5
6.9
8.6
15.5
6.1
9.5
7.7
17.1
ISR
13.8
13.8
9.2
lAC
(
Min
-
)
lAC
(
Max
.
)
4.6
6.1
7.8
15.2
6.8
8.6
16.8
ISR
15.0
10.0
lAc
(
Min
.
)
lAC
(
Max
-
)
5.0
6.7
14.6
16.1
7.4
ISR
17.4
lAc
(
Min
.
)
lAC
(
Max
.
)
8.7
8.0
8.8
13
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
TABLE
4
Tap
Combination
Currents
35
%
HU
-
4
Relay
Restraint
Transformer
Larger
2.9
3.2
3.5
3.8
5.0
8.7
4.2
4.6
Tap
Smaller
CURRENT
IN
AMPERES
ISR
8.7 8.7
8.7
8.7
8.7
8.7
8.7
5.8
lAC
(
Min
.
)
lAc
(
Max
.
)
2.9
3.9
5.3
6.8
13.1
7.7
9.9
11.4
19.0
4.3
5.8
7.5
8.5
14.5
21.0
10.9
12.6
•
SR
9.6 9.6
9.6
9.6
9.6
9.6
6.4
lAc
(
Min
-
)
lAc
(
Max
.
)
3.2
4.4
5.9
6.9
12.2
9.1
10.5
18.5
4.8
6.5
7.6
13.5
10.1
11.6
20.5
ISR
10.5 10.5
10.5
10.5
10.5
7.0
lAC
(
Min
.
)
lAc
(
Max
.
)
3.5
4.8
10.9
5.7
7.9
9.3
17.4
5.4
6.3
8.8
10.3
12.1
19.3
ISR
11.4
11.4
11.4
11.4
7.6
lAc
(
Min
.
)
lAC
(
Max
.
)
3.8
5.2
10.5
8.9
17.3
7.4
11.6
19.2
5.7
8.2
9.8
ISR
12.6
8.4
12.6
12.6
lAC
(
Min
.
)
lAc
(
Max
.
)
4.2
8.7
15.8
5.6
7.0
9.6
17.2
6.2
7.8
ISR
13.8
9.2
13.8
lAc
(
Min
.
)
lAc
(
Max
.
)
4.6
7.9
6.2
15.2
16.8
6.8
8.7
ISR
15.0
10.0
lAc
(
Min
.
)
lAc
(
Max
.
)
5.0
6.8
14.9
16.5
7.5
ISR
17.4
lAc
(
Min
.
)
lAc
(
Max
.
)
8.7
8.4
9.0
14
Courtesy of NationalSwitchgear.com
I
.
L
.
41
-
347.1
S
Upon
the
application
of
pickup
current
,
the
operating
ampere
turns
will
be
greater
than
the
restraint
am
-
pere
turns
and
the
bias
will
be
removed
.
If
a
lower
biasing
current
is
used
instead
of
20
times
tap
value
current
,
the
pickup
of
the
upper
unit
will
be
less
than
before
for
the
first
application
of
pickup
current
.
Pickup
will
be
further
reduced
with
the
sec
-
ond
application
of
pickup
current
,
but
the
current
will
be
stable
after
this
energization
.
However
,
this
value
of
pickup
will
be
lower
than
the
limits
of
25
%
and
33
%
of
tap
value
current
.
This
is
in
the
direction
of
making
the
sensitivity
of
the
polar
unit
lower
than
30
%
,
but
does
not
impair
the
performance
of
the
unit
on
inrush
currents
.
b
.
Differential
Unit
(
DU
)
Set
the
adjustable
resistor
at
top
of
the
relay
in
the
approximate
center
of
its
range
.
Open
the
switch
and
pass
lac
=
20
times
tap
value
current
.
This
current
should
be
applied
for
a
very
short
period
of
time
and
it
should
be
suddenly
interrupted
.
Adjust
left
hand
shunt
of
lower
polar
unit
until
it
trips
with
lac
=
30
%
of
tap
value
amperes
.
Lower
lac
gradually
to
15
%
of
tap
value
current
and
adjust
left
-
hand
shunt
until
unit
resets
.
If
polar
unit
resets
before
15
%
of
tap
value
current
,
no
adjustments
are
necessary
to
the
left
-
hand
shunt
.
Repeat
these
steps
until
the
lower
polar
unit
will
pickup
at
30
%
of
tap
value
current
and
reset
for
values
of
tap
value
current
greater
than
15
%
.
view
)
backstop
until
it
just
makes
with
the
moving
contact
.
Tighten
the
screw
in
the
elongated
hole
of
the
backstop
and
remove
gauge
.
Place
a
0.065
to
0.070
feeler
gauge
between
the
moving
contact
and
the
stationary
contact
on
the
right
(
front
view
)
side
of
the
polar
unit
.
Bring
up
the
stationary
contact
until
it
just
makes
with
the
gauge
.
Tighten
mounting
screw
in
the
elongated
hole
of
the
stationary
contact
and
remove
gauge
.
10.2
.
2
Minimum
Trip
Current
a
.
Harmonic
Restraint
Unit
(
HRU
)
Connect
the
relay
per
test
circuit
of
Figure
21
or
Fig
-
ure
22
according
to
type
.
With
the
switch
open
pass
lac
=
20
times
tap
value
current
into
the
relay
.
This
current
should
be
applied
for
a
very
short
period
of
time
and
it
should
be
suddenly
interrupted
.
Adjust
right
hand
shunt
on
upper
polar
unit
until
it
trips
with
lac
=
33
%
of
tap
value
amperes
.
Lower
lac
gradually
to
15
%
of
tap
value
current
and
adjust
left
-
hand
shunt
until
unit
resets
.
Repeat
these
steps
,
if
neces
-
sary
,
until
the
unit
operates
at
33
%
or
slightly
lower
of
tap
value
current
immediately
following
the
appli
-
cation
of
20
times
tap
value
current
and
until
the
unit
resets
at
a
value
of
current
15
%
of
tap
value
or
great
-
er
.
After
the
dropout
has
been
measured
,
the
unit
should
pickup
at
25
%
or
higher
of
tap
value
current
.
On
the
application
of
the
high
polarizing
current
the
upper
polar
unit
will
be
biased
in
the
restraining
di
-
rection
and
pickup
will
be
greater
than
the
nominal
value
of
30
%
of
tap
value
current
on
the
first
applica
-
tion
of
pickup
current
.
If
the
circuit
is
de
-
energized
and
pickups
measured
again
,
the
pickup
current
will
be
less
than
before
.
However
,
pickup
will
be
stable
after
the
second
application
of
pickup
current
.
If
20
times
tap
value
current
is
applied
again
,
the
pickup
immediately
after
applying
this
current
will
be
high
.
However
,
measuring
the
pickup
the
second
time
will
show
that
the
pickup
is
again
reduced
.
The
variation
between
these
pickups
will
be
between
25
%
and
33
%
of
tap
value
current
.
The
filter
circuits
are
charged
by
the
application
of
this
heavy
polarizing
current
and
upon
the
removal
of
the
current
,
these
circuits
will
discharge
their
en
-
ergy
.
The
element
will
be
biased
in
the
restraining
di
-
rection
because
the
restraint
coil
has
approximately
7
times
the
number
of
turns
as
the
operating
coil
.
10.2
.
3
Indicating
Instantaneous
Trip
Unit
(
IIT
)
For
HU
and
HU
-
1
relays
,
open
switch
and
pass
lac
=
10
times
tap
value
current
.
Adjust
core
of
the
instan
-
taneous
trip
unit
until
it
picks
up
.
Its
target
should
drop
freely
.
Follow
the
same
procedure
for
the
HU
-
4
relays
except
pass
lac
=
15
times
tap
.
The
contact
gap
should
be
approximately
0.094
inches
between
the
bridging
moving
contact
and
the
adjustable
stationary
contacts
.
The
bridging
contact
should
touch
both
the
stationary
contacts
simultaneously
.
10.2
.
4
Harmonic
-
Restraint
Unit
(
HRU
)
Close
switch
to
position
2
.
Short
out
ILR
ammeter
.
Adjust
direct
current
until
Idc
reads
0.8
times
tap
15
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
setting
.
Gradually
increase
alternating
current
until
upper
polar
unit
operates
with
lac
reading
between
1.3
and
1.8
times
tap
setting
.
The
percent
second
harmonic
in
the
wave
may
be
derived
by
the
use
of
the
formula
:
obtain
a
pickup
of
30
%
of
tap
value
current
and
drop
-
out
of
15
%
or
greater
of
tap
value
current
.
If
shunts
are
changed
,
check
to
see
that
above
readings
are
obtained
on
the
higher
restraint
currents
.
If
neces
-
sary
readjust
resistor
and
repeat
procedure
until
the
unit
operates
within
the
specified
limits
.
Apply
lac
=
-
56
times
tap
value
for
all
relays
and
vary
ISR
until
lower
polar
unit
operates
.
The
lower
polar
unit
should
operate
between
the
following
limits
:
471
dc
%
second
harmonic
=
'
ac
+
1
-
11
ldc
This
formula
is
plotted
in
curve
form
in
Figure
23
for
Idc
=
4
amperes
.
Relay
Type
ILR
HU
/
HU
1
2.56
to
2.24
times
tap
value
current
10.2
.
5
Percentage
Slope
Characteristics
(
DU
)
Close
switch
to
position
1
.
Set
lac
to
zero
for
all
re
-
lays
and
ISR
either
to
5.5
times
tap
value
current
for
the
HU
/
HU
-
1
relays
or
6.9
times
tap
value
current
for
the
HU
-
4
relays
.
Then
adjust
lac
to
4
times
tap
value
current
for
all
relays
.
HU
-
4
1.82
to
1.54
times
tap
value
current
10.2
.
6
Calibration
(
35
%
-
Sensitivity
Relays
)
The
differential
unit
(
DU
)
,
should
first
be
calibrated
as
outlined
under
Section
10
,
Calibration
.
Next
the
right
hand
shunt
of
the
lower
polar
unit
should
be
turned
in
until
the
relays
operate
at
the
following
val
-
ues
of
current
.
Adjust
resistor
at
top
of
relay
until
polar
until
oper
-
ates
.
The
lower
polar
unit
should
operate
between
the
following
values
:
Relay
Type
lac
ILR
Relay
Type
lac
"
LR
HU
/
HU
-
1
4
times
tap
value
current
10
to
9
tap
value
current
HU
/
HU
-
1
1.64
times
tap
value
current
.
45
times
tap
HU
-
4
1.5
times
tap
value
current
.
56
times
tap
HU
-
44
times
tap
value
current
11.2
to
10.6
tap
value
current
This
changes
the
percentage
slope
curve
of
the
re
-
lay
to
that
shown
by
the
35
percent
sensitivity
curve
of
Figure
14
.
Pickup
of
the
relay
is
increased
from
30
%
to
approximately
35
%
of
the
tap
value
current
and
the
curve
is
changed
at
low
values
of
restraint
current
.
At
large
values
of
restraint
current
the
per
-
centage
slope
characteristics
is
essentially
the
same
as
shown
in
Figure
13
.
As
shown
in
Figure
14
,
the
margin
of
safety
between
the
relay
calibration
for
a
35
%
sensitivity
and
the
20
%
mismatch
curve
is
the
same
as
that
of
the
relay
calibrated
for
a
30
%
sensitivity
and
the
15
%
mis
-
match
curve
.
This
margin
of
safety
is
also
shown
in
the
voltage
differential
characteristics
of
Figure
17
for
the
35
percent
sensitivity
relay
.
For
HU
relays
,
interchange
lead
position
to
terminals
5
and
7
and
repeat
the
above
test
.
Also
repeat
test
for
HU
-
1
relay
with
ILR
to
terminal
9
and
for
HU
-
4
re
-
lay
with
ILR
to
terminals
9
and
13
.
Trip
condition
can
best
be
determined
by
holding
lac
at
4
times
tap
value
current
and
varying
ISR
.
If
ISR
is
too
low
the
contacts
will
be
closed
when
the
currents
are
first
applied
.
Hence
,
ILR
should
be
increased
un
-
til
the
contacts
open
and
then
decreased
until
con
-
tacts
close
.
The
adjustment
of
the
resistor
will
have
some
effect
on
the
pickup
of
the
unit
.
Hence
,
polarize
and
re
-
check
the
pickup
.
If
necessary
readjust
shunts
to
16
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
10.2
.
7
Electrical
Checkpoints
The
following
electrical
checkpoints
may
be
used
to
assist
in
troubleshooting
if
the
relay
will
not
calibrate
using
the
above
calibration
procedure
.
The
values
listed
are
approximate
for
current
production
and
might
change
due
to
a
minor
change
in
design
or
a
change
in
components
.
However
,
periodic
checks
of
a
given
relay
should
reproduce
very
closely
the
same
values
produced
when
the
relay
was
new
.
b
.
Operating
Circuit
Apply
30
percent
tap
-
value
current
to
terminal
3
and
tap
screw
.
Using
a
high
-
resistance
voltmeter
,
the
ac
voltage
across
the
operating
coil
bridge
and
the
ac
voltage
output
of
the
operating
transformer
(
top
two
coil
terminals
)
should
be
within
the
range
given
in
Table
5
.
10.2
.
8
Harmonic
Restraint
Unit
(
HRU
)
Apply
30
percent
tap
-
value
current
to
terminal
3
and
a
tap
screw
.
The
voltages
obtained
by
using
a
high
resistance
ac
voltmeter
should
be
within
the
range
given
in
Table
5
.
(
Refer
to
Figure
24
or
Figure
25
for
bridge
location
depending
on
relay
type
.
)
10.2
.
9
Diode
Check
Check
for
open
or
shorted
diodes
using
the
electrical
checkpoints
of
Table
5
.
11
.
RENEWAL
PARTS
Repair
work
can
be
done
most
satisfactorily
at
the
factory
.
However
,
interchangeable
parts
can
be
fur
-
nished
to
customers
who
are
equipped
for
doing
re
-
pair
work
.
When
ordering
parts
,
always
give
the
complete
nameplate
data
.
10.2
.
7.1
Differential
Unit
(
DU
)
a
.
Restraint
Circuit
Apply
two
times
tap
-
value
current
successively
to
each
restraint
transformer
.
This
is
done
by
connect
-
ing
leads
to
a
tap
screw
and
to
terminals
5
,
7
,
9
(
HU
-
1
only
)
and
13
(
HU
-
4
only
)
in
turn
.
The
ac
voltage
across
the
appropriate
restraint
rectifier
bridge
using
a
high
resistance
voltmeter
(
5000
ohms
per
volt
)
should
be
within
the
range
given
in
Table
5
.
Location
of
the
appropriate
bridges
is
shown
in
Fig
-
ure
24
for
HU
and
HU
-
1
relays
and
in
Figure
25
for
the
HU
-
4
relays
.
17
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
TABLE
5
Voltage
Range
50
Hz
60
Hz
Rated
Frequency
DU
Restraint
Circuit
HU
and
HU
-
1
2.10
-
2.40
1.78
-
2.03
3.55
-
4.05
HU
-
4
3.16
-
3.60
Voltage
Range
HU
/
HU
-
1
/
HU
-
4
50
Hz
60
Hz
Rated
Frequency
DU
Operating
Circuit
Operate
Coil
Bridge
Operate
Transformer
HRU
1
.
Output
of
operate
transformer
(
top
coil
terminals
)
2
.
4
MFD
capacitor
(
HRU
Operate
)
3
..
45
MFD
capacitor
(
HRU
Restraint
)
Rectifier
Bridges
4
.
Operating
5
.
Restraint
6
.
Series
-
Filter
Reactor
2.50
-
3.10
2.17
-
2.69
3.60
-
7.00
2.40
-
4.75
3.90
-
4.80
3.98
-
4.89
2.27
-
3.13
2.41
-
3.33
3.20
—
4.40
2.89
-
3.97
1.95
-
3.00
1.87
-
2.88
<
1.0
<
1.2
<
1.0
<
0.5
18
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
TABLE
6
TWO
-
WINDING
TRANSFORMER
CALCULATIONS
(
See
Figure
20
)
LOW
HIGH
1
.
Select
ct
Ratio
20
,
000
12.4
^
3
20
,
000
<
KVA
)
M
=
930
Amps
=
167
Amp
69
73
3
S
(
KV
)
V
3
P
1000
/
5
(
N
=
200
)
200
/
5
(
N
=
40
)
Select
ratio
2
.
Calculate
Relay
Current
:
Ip
930
167
=
4.65
Amp
=
4.18
Amp
S
N
200
40
=
4.65
«
/
3
=
8.05
Amp
'
R
=
=
4.18
Amp
RL
RH
'
RL
8.05
3
.
Calculate
Current
Ratio
:
1.93
s
I
4.18
RH
TL
8.7
4
.
Select
Tap
Ratio
from
Table
1
:
IR
>
relay
continuous
rating
5
.
Check
I
IT
Operation
Max
.
Symmetrical
error
current
>
10
times
relay
tap
6
.
Determine
Mismatch
:
%
Mismatch
=
—
=
1.890
TH
4.6
NO
No
No
8.05
8.7
4
/
18
~
4
^
6
100
T
8.7
u
V
4.6
RH
100
TL
(
1.92
-
1.89
)
100
=
1.6
%
TH
1.89
7
.
Check
ct
Performance
0.45
0.15
Zj
=
3.4
(
RL
+
)
=
1.13
(
RL
+
)
=
TT
0.45 0.15
3.4
(
0.4
)
+
=
1.36
+
0.05
=
1.13
(
04
+
)
=
0.45
+
0.03
=
8.7
4.6
1.41
ohms
0.48
ohms
N
200
40
Np
=
=
0.833
=
0.333
NI
240
120
(
NPVCL
)
0.833
(
200
)
0.333
(
200
)
1.67
=
0.67
100
100
100
V
CL
)
>
z
(
N
-
ioo
Yes
Yes
T
Conclusion
:
TL
=
8.7
TH
=
4.6
30
%
sensitivity
Relay
is
adequate
19
Courtesy of NationalSwitchgear.com
I
.
L
41
-
347.1
S
TABLE
7
THREE
-
WINDING
TRANSFORMER
CALCULATIONS
(
See
Figure
20
)
HIGH
INTERMEDIATE
LOW
1
.
Select
ct
Ratio
:
(
KVA
)
M
40
,
000
161
400
/
5
(
N
=
80
)
40
,
000
69
J
3
600
/
5
(
5
N
=
120
)
10
,
000
=
143
Amp
=
334
Amp
=
465
Amp
p
~
(
KV
)
73
Select
Ratio
12.4
„
/
3
1000
/
5
(
N
=
200
)
2
.
Calculate
Relay
Current
:
143
334
465
P
=
2.78
Amp
=
1.79
Amp
=
2.33
Amp
s
N
120
80
200
40
lR
|
=
2.7873
=
4.82
Amp
=
1.7973
=
3.10
Amp
I
R
(
At
40
MVA
)
=
'
RL
=
T
^
2
-
33
)
=
9.32
Amp
.
RH
*
RL
4.82
9.32
Rl
3
.
Calculate
Current
Ratios
:
=
1.55
=
3.01
I
3.10
I
3.10
RH
RH
4
.
Select
Tap
Ratio
from
Table
1
:
Ti
4.6
8.7
—
=
1.586
T
,
=
^
=
3.00
L
2.9
TH
2.9
IR
>
relay
continuous
rating
5
.
Check
I
IT
Operation
Max
.
symmetrical
error
current
>
10
times
relay
tap
.
No
No
No
No
No
No
6
.
Determine
Mismatch
:
T
I
T
T
I
/
'
RH
_
1
H
\
MRL
V
V
^
*
Rl
U
V
RH
%
Mismatch
100
100
100
TH
TL
*
RI
T
I
TH
I
RL
3.10
2.9
4.82
4.6
4.82
4.6
.
032
8
/
T
9.32
8.7
3.10
2.9
()
100
100
100
2.9
4.82
8.7
4.6
9.32
2.9
0.643
-
0.630
0.517
-
0.529
3.01
-
3.00
100
(
)
=
100
(
)
=
)
=
100
(
0.630
0.517
3.00
2.1
%
-
2.3
%
0.33
%
20
Courtesy of NationalSwitchgear.com

Other manuals for HU

1

This manual suits for next models

2

Other ABB Relay manuals

ABB KLF-1 Manual

ABB

ABB KLF-1 Manual

ABB SSR32 User manual

ABB

ABB SSR32 User manual

ABB CWC Manual

ABB

ABB CWC Manual

ABB RELION REF610 Product manual

ABB

ABB RELION REF610 Product manual

ABB RELION REX640 User manual

ABB

ABB RELION REX640 User manual

ABB CR324GXNS User manual

ABB

ABB CR324GXNS User manual

ABB KLF Manual

ABB

ABB KLF Manual

ABB CVQ Manual

ABB

ABB CVQ Manual

ABB T 900 DU V1000 User manual

ABB

ABB T 900 DU V1000 User manual

ABB Relion 615 series User manual

ABB

ABB Relion 615 series User manual

ABB Relion 615 series Instructions for use

ABB

ABB Relion 615 series Instructions for use

ABB Relion REB500 User manual

ABB

ABB Relion REB500 User manual

ABB E 320 DU User manual

ABB

ABB E 320 DU User manual

ABB REL-300 User manual

ABB

ABB REL-300 User manual

ABB CT-AHS Firmware update

ABB

ABB CT-AHS Firmware update

ABB CM Series User manual

ABB

ABB CM Series User manual

ABB CKO-5 User manual

ABB

ABB CKO-5 User manual

ABB 41-101U Manual

ABB

ABB 41-101U Manual

ABB 630 series User manual

ABB

ABB 630 series User manual

ABB RELION REF615R Installation and operation manual

ABB

ABB RELION REF615R Installation and operation manual

ABB RELION REL670 User manual

ABB

ABB RELION REL670 User manual

ABB HCB-1 Manual

ABB

ABB HCB-1 Manual

ABB REX 521 Use and care manual

ABB

ABB REX 521 Use and care manual

ABB RELION 650 SERIES User manual

ABB

ABB RELION 650 SERIES User manual

Popular Relay manuals by other brands

Simons Voss SMART RELAY manual

Simons Voss

Simons Voss SMART RELAY manual

Prime Power EDR 12 75 manual

Prime Power

Prime Power EDR 12 75 manual

Haseman Electric RS-10PM user manual

Haseman Electric

Haseman Electric RS-10PM user manual

Black Box IC905C quick start guide

Black Box

Black Box IC905C quick start guide

Kyongbo Electric GDR-M02 user manual

Kyongbo Electric

Kyongbo Electric GDR-M02 user manual

Eaton Cutler-Hammer FP-5000 instructions

Eaton

Eaton Cutler-Hammer FP-5000 instructions

FANOX SIA-B Series user manual

FANOX

FANOX SIA-B Series user manual

GE IFC95AD instruction manual

GE

GE IFC95AD instruction manual

Dantel 46032-15 Installation & operation manual

Dantel

Dantel 46032-15 Installation & operation manual

NAPCO NP-RB1224VDC/6 installation instructions

NAPCO

NAPCO NP-RB1224VDC/6 installation instructions

CAMDEN CX-12 PLUS installation instructions

CAMDEN

CAMDEN CX-12 PLUS installation instructions

Chtce ZHRV5 Series operating instructions

Chtce

Chtce ZHRV5 Series operating instructions

Intellitec 00-00629-120 instruction manual

Intellitec

Intellitec 00-00629-120 instruction manual

Pilz PNOZ s6 operating instructions

Pilz

Pilz PNOZ s6 operating instructions

resideo R8845U manual

resideo

resideo R8845U manual

MULTISPAN VR-3KN manual

MULTISPAN

MULTISPAN VR-3KN manual

Thytronic NV10P manual

Thytronic

Thytronic NV10P manual

F&F BIS-410-24V manual

F&F

F&F BIS-410-24V manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.