Viconics VTR8300 Series User manual

VTR8300 Series Installation Guide
Room Controller with Optional PIR sensor
Commercial and Hotel/Lodging HVAC Fan Coil Applications
CONTENTS
Installation 2
Location 2
Installation 2
Terminal, Identification and Function 3
Communication wiring to VC3xxxX Relay Pack 3
BACnet®Communication Wiring (if applicable) 3
Network wiring topology 3
How to Enter Setup Screen 4
Setup Screen Display 4
Specifications 5
Drawing and Dimensions 6

VTR8300 Series
2Installation Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0 414-01 www.viconics.com | sales@viconics.com October 2014
© 2014 Viconics Technologies Inc. All rights reserved.
DISCLAIMERS
• The VTR8000 series controller is only to be used in conjuction with the VC3000 line voltage switching relay pack. Together they are
used as operating controls for high voltage fan coil units.
• If replacing an existing Line Voltage FCU Controller, label the wires before removal of the controller.
• Electronic controls are static sensitive devices. Discharge yourself properly before manipulating and installing the Terminal Equipment
Controller. A short circuit or wrong wiring may permanently damage the Terminal Equipment Controller or the equipment.
• All VTR8300 series controls are designed for use as operating controls only and are not safety devices. These instruments have
undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control
failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system
designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc…) and/or an alarm system to protect the
entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a
void of warranty.
• If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
• These devices are not serviceable and must be returned to the supplier.
• A switch or cicruit breaker must be installed. It must be suitably located, easily reached and marked as the disconnecting device.
VTR8000 Controller VC3000 Relay Pack
IMPORTANT SYMBOLS
Products marked with this symbol state that the manuals must be consulted in all cases to any hazards.
This product has been tested to the requirements of CAN/CAS-C22.2 No. 61010-1, second edition, including Amendment 1,
or a later version of the same standard incorporating the same level of testing requirements.
Alternating Current
Direct Current
Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION

VTR8300 Series 3
Installation Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0 414-01 www.viconics.com | sales@viconics.com October 2014
© 2014 Viconics Technologies Inc. All rights reserved.
INSTALLATION
•
Open unit by pulling on bottom side of Terminal Equipment Controller (
Figure
1).
• Read FCC ID and IC label installed in cover.
• Ensure wall surface is flat and clean.
Location
1. Do not install installed on outside wall.
2. Do not install in areas with exposure to direct heat source.
3. Do not install in areas near air discharge grill.
4. Do not install in areas with direct sun radiation.
5. Do not install in areas that restrict vertical air circulation.
Installation
1. Pull cables 15cm (6”) out from wall.
2. Align base and mark location of two mounting holes on the wall and ensure
proper side of base faces up.
3. Install anchors in wall.
4. Insert cable in central hole of base.
5. Insert screws in mounting holes on each side of base (Figure 2).
6. Strip each wire 0.6cm (1/4”) from end.
7. Insert each wire according to wiring chart (next page).
8. Gently push excess wiring back into hole.
9. Gently align the cover to the top of the base, then snap it in place from
bottom (Figure 3).
10. Install security screw.
• If replacing an existing Line Voltage FCU Controller, label the
wires before removal of the controller.
• Electronic controls are static sensitive devices. Discharge
yourself properly before manipulating and installing the
Terminal Equipment Controller.
• A short circuit or wrong wiring may permanently damage the
Terminal Equipment Controller or the equipment.
• All VTR8300 series controls are designed for use as operating
controls only and are not safety devices. These instruments
have undergone rigorous tests and verification prior to shipping
to ensure proper and reliable operation in the field. Whenever
a control failure could lead to personal injury and/or loss of
property, it becomes the responsibility of the user / installer /
electrical system designer to incorporate safety devices
(such as relays, flow switch, thermal protections) and/or
an alarm system to protect the entire system against such
catastrophic failures. Tampering with the devices or unintended
application of the devices will result in a void of warranty.
Figure-1 Open the cover
Figure-2 Install the base
Figure-3 Reinstall cover

VTR8300 Series
4Installation Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0 414-01 www.viconics.com | sales@viconics.com October 2014
© 2014 Viconics Technologies Inc. All rights reserved.
To other
VC3xxxX
Relay
Pack
Terminal Controller
Relay Pack
VTR83xxA VC3504E
4 - Tx / Rx
5 - 7 Vdc Power Hot
6 - Power Common
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
Relay Pack
VC3300E
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
Terminal Controller
Terminal Controller
To others
To others
13 - COM +
14 - COM -
VTR83xxA VTR83xxA
13 - COM +
14 - COM -
Terminal Identification All VTR83xxA
Terminal Equipment Controller
Terminal 4 Tx – Rx Communication
Terminal 5 Power Hot 7.0 VDC
Terminal 6 Power Common
Terminal 13 BACnet +
Terminal 14 BACnet -
Terminal 15 BACnet REF
Terminal 16 BI 1 ( Configurable )
Terminal 17 BI 2 ( Configurable )
Terminal 18 Scom
TERMINAL, IDENTIFICATION AND FUNCTION
Only ONE VC3xxxX Relay Pack with remote
monitoring inputs can be used under a single
VTR83xxA Controller. All other slave units must be
VC3xxxX Relay Pack(s) WITHOUT remote inputs.
A maximum of 10 VC3xxxX Relay Packs can be
used for a single VTR83xxA Terminal Equipment
Controller.
From the VTR83xxA to the first VC3xxxX
Relay Pack
• Uses existing or new field wires
• A minimum of 3 wires are required 14-22 Ga,
Solid or Stranded. Shield not necessary.
From the first VC3xxxX to all other slave
VC3xxxX Relay Pack(s)
• Uses existing or new field wires
• A minimum of 2 wires are required 14-22 Ga,
Solid or Stranded.
• Shield not necessary.
• Connect only wires #1 Power Common and
#2 Tx/Rx Communication
Daisy Chained Topology
Star Topology Mixed Daisy Chained & Star Topology
COMMUNICATION WIRING TO VC3XXXX RELAY PACK
Network Wiring Topology
BACnet®Communication Wiring (if applicable)
NOTE: See VTR8300 BACnet®integration manual for more details

VTR8300 Series 5
Installation Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0 414-01 www.viconics.com | sales@viconics.com October 2014
© 2014 Viconics Technologies Inc. All rights reserved.
HOW TO ENTER SETUP SCREEN
SETUP SCREENDISPLAY
Return to
home screen
General Note:
Setup
Network
Configuration
Setpoints - Display
Service view
Test outputs
Language selection
Adjustable parameter
Non-adjustable parameter
Touch and hold this point
for 3 seconds to enter setup mode
Note: If a configuration / installer
password is activated to prevent
unauthorised access to the
configuration menu parameters, a
password entry prompt will appear
to prevent access to the device
configuration components.
Discover Mode The Controller will
become discoverable on the wireless
ZigBee®network for 1 minute (this
button is hidden if ZigBee®settings are
not configured)
Enter BACnet®& ZigBee®network settings
Enter parameter configuration menu
Enter setpoint & display settings
Enter output testing mode
Enter status and service view
Note: The "Network" button will not be displayed if
no BACnet®or ZigBee®card is installed.
Enter setpoint & display settings
Enter language selection settings

VTR8300 Series
6Installation Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0 414-01 www.viconics.com | sales@viconics.com October 2014
© 2014 Viconics Technologies Inc. All rights reserved.
Specifications
Terminal Equipment Controller power requirements 7.0 VDC +/- 10% 2.4 watts minimum
Operating conditions 0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Storage conditions -30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Temperature sensor Local 10 K NTC type 2 thermistor
Temperature sensor resolution ± 0.1 °C ( ± 0.2 °F )
Temperature control accuracy
± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated
Humidity sensor and calibration Single point calibrated bulk polymer type sensor
Humidity sensor precision
Reading range from 10-90 % R.H. non-condensing 10
to 20% precision is 10%
20% to 80% precision is 5%
80% to 90% precision is 10%
Humidity sensor stability Less than 1.0 % yearly (typical drift)
Dehumidification setpoint range 30% to 95% R.H.
Occ, Stand-By and Unocc cooling setpoint range 12.0 to 37.5 °C ( 54 to 100 °F )
Occ, Stand-By and Unocc heating setpoint range 4.5 °C to 32 °C ( 40 °F to 90 °F )
Room and outdoor air temperature display range -40 °C to 50 °C ( -40 °F to 122 °F )
Proportional band for room temperature control Cooling & Heating: Default: 1.8°C ( 3.2°F )
Binary inputs Dry contact across terminal BI1,
BI2 & UI3 to Scom
Wire gauge 14 gauge maximum, 22 gauge recommended
Approximate shipping weight 0.34 kg ( 0.75 lb )
Safety Standards (all models)
LVD Directive 2006/95/EC
UL 61010-1 (2nd edition)
CSA 61010-1(3rd edition)
IEC 61010-1 (3rd edition)
EMC Standards (all models)
EMC Directive 2004/108/EC
IEC 61326-1:2005
FCC 15 Subpart B
ICES-003
Radio Standards (wireless models)
R&TTE Directive 1999/5/EC
IEC 61326-1:2005
EN 301 489-1 V1.9.2
EN 301 328 V1.8.1
FCC 15 Subpart C
RSS 210
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE
FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2)
THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY
CAUSE UNDESIRED OPERATION.
Please check with your local government for instruction on disposal of this product.

VTR8300 Series 7
Installation Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0 414-01 www.viconics.com | sales@viconics.com October 2014
© 2014 Viconics Technologies Inc. All rights reserved.
DIMENSIONAL DRAWING
86 mm (3.404”)
120 mm (4.744”)
27 mm
(1.072”)
Other manuals for VTR8300 Series
5
Table of contents
Popular Remote Control manuals by other brands

Pfeiffer Vacuum
Pfeiffer Vacuum RC 500 operating instructions

elsner elektronik
elsner elektronik Remo 8 quick start guide

Rinnai
Rinnai CNTRLDRCINW Operation and installation guide

HBC
HBC Amino Willow Remote Handbook

Panasonic
Panasonic KX-HNK102 operating instructions

Sky-Drones
Sky-Drones SMARTAP PRO user guide