
9 of 12
Viega Programmable Thermostat User Guide
UG-HC 566440 1219 Programmable Thermostat (EN)
Tech Settings LCD will
Show
Adjustment Options Factory
Default
Settings
Filter Change Reminder
This feature will flash “FILT” in
the display after the elapsed run
time to remind the user to change
the filter. A setting of OFF will
disable this feature.
You can adjust the filter change
reminder from OFF to 2000 hours
of runtime in 50 hour increments.
Tap the second button from the left
side of the thermostat to display
the current filter elapsed time.
Off
Room Temperature Calibration
This feature allows the installer to
change the calibration of the room
temperature display. For example, if
the thermostat reads 70° and you
would like it to read 72° then select +2.
You can adjust the room
temperature display to read -4°F
to +4°F above or below the factory
calibrated reading.
0
Compressor Short Cycle Delay
The compressor short cycle delay
protects the compressor from
“short cycling”. This feature will
not allow the compressor to be
turned on for 5 minutes after it
was last turned off.
Selecting ON will not allow the
compressor to be turned on for
5 minutes after the last time the
compressor was on. Select OFF to
remove this delay.
On
Cooling Swing
The swing setting often called “cycle
rate,” “differential,” or “anticipation”
is adjustable. A smaller swing setting
will cause more frequent cycles and
a larger swing setting will cause
fewer cycles.
The cooling swing setting is
adjustable from ±0.2°F to ±2°F.
For example: A swing setting of
0.5°F will turn the cooling on at
approximately 0.5°F above the
setpoint and turn the cooling off at
approximately 0.5°F Below the setpoint.
0.5
Cooling Swing
The swing setting often called
“cycle rate,” “differential,” or
“anticipation” is adjustable. A
smaller swing setting will cause
more frequent cycles and a larger
swing setting will cause fewer
cycles.
The cooling swing setting is
adjustable from ±0.2°F to ±2°F.
For example: A swing setting of
0.5°F will turn the cooling on at
approximately 0.5°F above the
setpoint and turn the cooling off
at approximately 0.5°F Below the
setpoint.
0.5
Heating Swing
The swing setting often called
“cycle rate,” “differential,” or
“anticipation” is adjustable. A
smaller swing setting will cause
more frequent cycles and a larger
swing setting will cause fewer
cycles.
The heating swing setting is
adjustable from ±0.2°F to ±2°F.
For example: A swing setting of
0.5°F will turn the heating on at
approximately 0.5°F below the
setpoint and turn the heating off
at approximately 0.5°F above the
setpoint.
0.4