Vitodens 200-W, B2HE Quick Start-up Guide
Installation
Using the Commissioning Assistant
Using the Commissioning Assistant
23
Note: Apps for commissioning and service are available for iOS and
Android devices.
This boiler can be commissioned using the Vitoguide Mobile App or the
boilers HMI, to proceed using the app select ‘With App’ to continue with
the boilers HMI select with programming unit.
Starting the Boiler Using the Commissioning Assistant
Starting the Boiler Using the Commissioning Assistant
24
Commissioning assistant sequence Explanations and references
Commissioning
Language
With programming unit If commissioning is to be carried out at the programming unit of the heat generator.
With software tool The appliance automatically switches on the WiFi access point.
Further commissioning steps according to the instructions of the software tool used (e.g. “Vitoguide mobile”)
Altitude Set the elevation of the installation site
Units of measurement ºC/m or ºF/ft
Date and time
Operating mode
(based on boiler application)
Weather-compensated operation
The outside temperature sensor must be connected.
Constant operation
Operation with constant supply temperature
Building type Detached house
One shared vacation program and time program for DHW and heating
Apartment building
A separate vacation program can be set for each heating circuit
Gas type If operating with LPG, switch to “LPG”
Flue system type Single connection
Only one boiler is connected to the flue system (factory setting).
Multiple connections
Several heat generators are connected to the flue system.
Filling and purging
If no further settings are to be performed, the commissioning assistant can now be closed.
System scheme
Heating circuit 1
(based on boiler application)
Heating circuit without mixing valve or heating circuit without mixing valve with external hook-up (if installed)
Heating circuit 2, 3 ...
(based on boiler application)
Heating circuits with mixing valve or heating circuits with mixing valve with
external hook-up (if installed)
DHW
Not available
Tank with one sensor
Tank with one sensor and DHW
circulation pump
Tank with temperature switch
Tank with temperature switch and
DHW recirculation pump
external hook-up (if installed)
Tank equipped with DHW temperature switch (such as an Aquastat)
Tank equipped with DHW temperature switch (such as an Aquastat) and
DHW recirculation pump
Low loss header/buffer cylinder
Not available
Low loss header, heating only
DHW heating upstream of
low loss header
DHW heating downstream of low
loss header
Buffer cylinder, heating only
DHW heating upstream of buffer
cylinder
DHW heating downstream
of buffer cylinder
Settings for the consumer circuits according to the system components
There is no low loss header or heating water buffer tank in the system.
System with low loss header, without DHW heating DHW heating with
e.g. separate DHW tank connected upstream of the low loss header
DHW heating with e.g. separate DHW tank connected downstream of the low loss header
System with heating water buffer tank, without DHW heating
DHW heating with e.g. separate DHW tank connected upstream of the heating water buffer tank
DHW heating with e.g. separate DHW tank connected downstream of the heating water buffer tank
Solar
(if installed)
No solar function
Solar thermal system connected to boiler via EM-S1 extension
Setting subject to the design of the solar thermal system
EM-S1 extension installation and service instructions
Heating zone/safety input
Heating zone 1
Heating zone 2
Heating zone 3
(based on boiler application type)
Not available, or temperature controller or low water indicator
Not available or temperature controller or monitoring for excessively low gas pressure
Not available or temperature controller or monitoring for excessively high gas pressure
Turning on the Boiler for the First Time
Turning on the Boiler for the First Time
22
Upon initializing the power forthe first time, the boiler will automatically call
up the commissioning assistant.