1. PRODUCT NAME
Viking Model M Standard Response Dry
Pendent Sprinklers
•Adjustable Recessed, Adjustable Stan-
dard, or Plain Barrel
2. MANUFACTURER
The Viking Corporation
210 N. Industrial Park Road
Hastings, Michigan 49058, USA
Telephone: (269) 945-9501
(877) 384-5464
Fax: (269) 945-9599
e-mail: [email protected]
3. PRODUCT DESCRIPTION
Viking Standard Response Dry Pendent
Sprinklers are thermosensitive glass-bulb
spray sprinklers suitable for use in areas
subject to freezing. The sprinklers are de-
signed for dry systems and preaction sys-
tems where it is necessary to prevent wa-
ter or condensation from entering the drop
nipple before sprinkler operation. They
may also be installed in spaces subject to
freezing and supplied from a wet system in
an adjacent heated area.
The pendent sprinkler is of the familiar
Model M design with a 5 mm glass bulb. Vi-
king Standard Response Dry Pendent
Sprinklers are available in several finishes
and temperature ratings, standard or large
orifice, to meet design requirements. The
large orifice dry pendent sprinkler allows
greater flows at lower pressures than stan-
dard orifice dry pendent sprinklers.
The assembly features a sealed brass inlet
and a durable, threaded steel barrel with
an electrodeposited epoxy base coating.
The seal at the threaded end of the assem-
bly is held in place by force transmitted
from the compression screw, through the
glass bulb and internal parts, onto a spe-
cial sealing spring.
During fire conditions, the heat-sensitive
liquid in the glass bulb expands, causing
the glass to shatter, releasing the internal
parts to open the waterway. Water flowing
through the sprinkler orifice strikes the
sprinkler deflector, forming a uniform spray
pattern to extinguish or control the fire.
The Viking Dry Pendent Sprinkler may be
installed with the barrel exposed, or with
one of two escutcheon styles.
•A recessed style escutcheon with up to
5/8" (15,8 mm) adjustment (see Figure
3) provides an aesthetically pleasing re-
cessed appearance.
•For standard installations, the sprinkler
is available with an adjustable surface-
mounted ceiling escutcheon, finished to
allow up to 2" (51 mm) of adjustment. Re-
fer to Figure 1.
Both styles of escutcheons slip on from be-
low the ceiling to allow installation of the
sprinkler prior to ceiling construction.
Viking Standard Response Dry Pendent
Sprinklers are available in ¼" (6,35 mm) in-
crements for the recessed style, and in ½"
(12,7 mm) increments for the “adjustable
ceiling escutcheon" style, and the plain bar-
rel style, installed with no escutcheon.
These sprinklers may be ordered in mini-
mum lengths from 1-1/2" (38,1 mm) for the
adjustable standard style, 3" (76,2 mm) for
the plain barrel style, and 3-1/4" (82,5 mm)
for the adjustable recessed style. They
have listings and approvals with a maxi-
mum length of 45-1/2" (1 156 mm) for the
adjustable standard style*, 47" (1 194 mm)
for the plain barrel style*, and 47-1/2" (1 207
mm) for the adjustable recessed style*.
* Lengths exceeding the standard lengths are avail-
able, with no approvals, on a “made-to-order” basis:
• Recessed Dry Pendent up to 65-1/2” (1 664 mm).
• Adjustable Standard Dry Pendent up to 63-1/2”
(1 613 mm).
• Plain Barrel Dry Pendent up to 65” (1 651 mm).
Contact the manufacturer for more information.
4. TECHNICAL DATA
LISTINGS AND APPROVALS
Refer to the chart on page 101 d.
Glass-bulb fluid temperature rated to
-65 °F (-55 °C).
Rated to 175 psi (1 207 kPa) water work-
ing pressure.
Thread Size: 1" NPT or 25 mm BSP
Nominal K-Factors:
For Standard Orifice Sprinklers VK150,
VK151, VK154, VK155, VK158, and
VK159: 5.6 U.S. (8,1 metric**) for all
listed and approved lengths.
For Large Orifice Sprinklers VK163, VK164,
and VK166: 8.0 U.S. (11,5 metric**) for
lengths up to 20". For lengths exceeding
20", refer to Figure 4 on page 101 d.
**Metric K-Factor shown is for use when pressure is
measured in kPa. When pressure is measured in
BAR, multiply the metric K-Factor shown by 10.0.
Min. operating pressure: 7 psi (48,3 kPa)
Factory tested pneumatically at 100 psi
(685 kPa).
SPRINKLER MATERIALS
Frame: Brass Castings UNS-C84400
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 5 mm diameter
Belleville Spring Sealing Assembly: Nickel
Alloy, coated on both sides with Teflon
Tape
Spring Base: Brass UNS-C31400 or
UNS-C31600
Displacement Ring: Brass UNS-C51000
Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C31400 or
UNS-C31600 for standard orifice sprin-
klers. Brass UNS-C36000 for large ori-
fice sprinklers
Pip Cap Adapter: Brass UNS-C36000
Seat: Copper UNS-C21000
Orifice: Copper UNS-C21000
Washer: Stainless Steel UNS-S30400
Spacer: Stainless Steel UNS-S30400
Gasket: Buna-N
Tube: ERW Hydraulic Steel Tube
Inlet: Brass UNS-C31600
Support (Internal): Stainless Steel UNS-
S30400 for standard orifice sprinklers.
Brass UNS-C36000 for large orifice
sprinklers.
Spring (Internal): Stainless Steel
UNS-S30200
Barrel: Steel Pipe UNS-G10260, Electro-
deposited Epoxy Base finish
Sleeve (for Adjustable Standard style only):
Brass UNS-C26000 or UNS-C26800
Form No. F_071591
Sprinkler 101 a
September 16, 2005
TECHNICAL DATA STANDARD RESPONSE
DRY PENDENT SPRINKLERS
Adjustable
Recessed
Adjustable
Standard
Plain
Barrel
Sprinkler Temperature
Classification
Nominal Sprinkler Temp.
Rating (Fusing Point)
Maximum Ambient
Ceiling Temp.1Bulb
Color2
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
1Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and
other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.
2Temperature rating is stamped on the deflector.
Note: Units of measure in parentheses may be approximations. Replaces page 101 a-d, dated May 13, 2005
(revised the K-Factor graph).
OBSOLETE
ESCUTCHEON MATERIALS
1. Adjustable Standard Dry Escutcheons:
Brass UNS-C26000 or UNS-C26800
2. Recessed Dry Escutcheons: Cold
Rolled Steel UNS-G10080
AVAILABLE FINISHES
Recessed Style: Chrome-Enloy®(patents
pending) or White Polyester
Standard Adjustable: Chrome-Enloy®or
White Polyester sprinkler with a Chrome-
Enloy®Sleeve and Escutcheon
Plain Barrel Style (sprinkler only):
Chrome-Enloy®or Brass
SPRINKLER TEMPERATURE RATINGS
Refer to the chart on page 101 a.
ACCESSORIES
Dry Sprinkler Wrenches:
A. Standard: Part No. 07297W/B
B. Recessed: Part No. 07565W/B†
†Requires a separate ½" ratchet (not available from
Viking).
Sprinkler Guard: Chrome, with no listings
or approvals, for installation on dry pen-
dent sprinklers manufactured after May
1994 only (Part Number 08954).
Replacement Escutcheons:
1. Adjustable Standard Dry Escutcheon:
Base Part Number 07741
2. Recessed Dry Escutcheon
Cup: Base Part Number 05459A
5. ORDERING INFORMATION
For proper shipment, specify model, orifice
size, finish, temperature rating, escutcheon
type, and length (“A” dimension). Dry pen-
dent sprinklers are ordered in specific
lengths noted as the “A” dimension (see Fig-
ures 1 through 3). The “A” dimension is the
distance from the face of the fitting (tee) to
the desired finished ceiling location. The dry
pendent sprinkler must be ordered and man-
ufactured specifically for one of three styles
of installation: with the adjustable recessed
escutcheon (see Figure 3), with the adjust-
able standard escutcheon (see Figure 1), or
with the plain barrel (see Figure 2). Escutch-
eons slip on from below the ceiling to allow
installation of the sprinkler prior to ceiling in-
stallation. For limits of adjustment for the re-
cessed escutcheon, see Figure 3. Details
and limits of adjustment for the standard ceil-
ing escutcheon style, with 2” (51 mm) of ad-
justment, are shown in Figure 1.
6. INSTALLATION
WARNING: Viking sprinklers are manu-
factured and tested to meet the rigid re-
quirements of approving agencies. The
sprinklers are designed to be installed in
accordance with recognized installation
standards. Deviation from the standards or
any alteration to the sprinkler after it leaves
the factory including, but not limited to,
painting, plating, coating, or modification,
may render the sprinkler inoperative and
will automatically nullify the approval and
any guarantee made by Viking.
A. Viking sprinklers are to be installed in
accordance with the latest edition of
Viking technical data, the latest stan-
dards of the National Fire Protection
Association, Factory Mutual, Loss
Prevention Council, Assemblee
Pleniere, VdS or other similar organi-
zations, and also with the provisions
of governmental codes, ordinances,
and standards, whenever applicable.
The use of dry sprinklers may be lim-
ited due to occupancy and hazard.
Refer to the AHJ prior to installation.
B. Sprinklers must be handled with care.
They must be stored in a cool, dry place in
their original container. Never install
sprinklers that have been dropped or
damaged in any way. Never install any
glass-bulb sprinkler if the bulb is cracked
or if there is a loss of liquid from the bulb. If
a glass bulb lacks the appropriate amount
of fluid, it should be set aside and returned
to Viking (or an authorized Viking distribu-
tor) for analysis as soon as possible. If the
sprinkler is not returned to Viking, it should
be destroyed. Never install sprinklers that
have been exposed to temperatures in
excess of the maximum ambient temper-
ature allowed. Such sprinklers should be
destroyed immediately.
C. Viking dry pendent sprinklers are not in-
tended for use in corrosive environ-
ments. Use only sprinklers listed for
corrosive environments when subject
to corrosive atmospheres.
WARNING: Viking dry sprinklers are to be
installed in the 1" outlet or run of malleable
or ductile iron threaded tee fittings that
meet the dimensional requirements of
ANSI B16.3 (Class 150), or cast iron
Sprinkler 101 b
TECHNICAL DATA STANDARD RESPONSE
DRY PENDENT SPRINKLERS
For “A” Dimension: 1. Determine distance from the face of the tee to the finished ceiling.
2. Round to nearest ½" (12,7 mm) between 1-1/2" and 45-1/2" (38,1 mm and 1 156 mm).
NOTE: The deflector will be located approximately 3-7/16" (87,3 mm) below the ceiling
with 1" (25,4 mm) upward and 1" (25,4 mm) downward adjustment.
Deflector at Minimum
Distance Below Ceiling
13/16"
(20,6 mm)
3-1/16"
(77,8 mm)
NOTE:
To locate the deflector at
the maximum distance
below the ceiling, with no
downward adjustment
available, order the dry
pendent sprinkler 1"
(25,4 mm) longer than
the “A” dimension.
Finished Ceiling
1-1/2" (38,1 mm)
diameter
2-7/16"
(62 mm)
min.
4-7/16"
(113 mm)
max.
Sleeve finish
matches escutcheon
Deflector at Maximum
Distance Below Ceiling
NOTE:
To locate the deflector
at the minimum distance
below the ceiling, with
no upward adjustment
available, order the dry
pendent sprinkler 1”
(25,4 mm) shorter than
the “A” dimension.
Minimum ceiling opening
diameter: 1-3/4" (44,45 mm)
Maximum ceiling opening
diameter: 2-1/4" (57 mm).
Figure 1: Adjustable Standard Dry Pendent Sprinkler with up to 2" (51 mm) of adjustment.
September 16, 2005
OBSOLETE
threaded tee fittings that meet the dimen-
sional requirements of ANSI B16.4 (Class
125), even at branch line ends. The
threaded end of the dry sprinkler is de-
signed to allow the seal to penetrate and ex-
tend into the fitting to a predetermined depth.
This prevents condensation from accumu-
lating and freezing over the sprinkler seal.
1. DO NOT install the dry pendent sprin-
kler into a threaded elbow, coupling,
or any other fitting that could interfere
with thread penetration. Such instal-
lation would damage the brass seal.
2. DO NOT install the dry pendent sprin-
kler into a coupling or fitting that will
allow condensation to accumulate
above the seal, when located in an
area subject to freezing.
3. NEVER try to modify the dry pendent
sprinkler. The sprinklers are manu-
factured for a specific "A" dimension
and cannot be modified.
D. The sprinkler must be installed after the
piping is in place to prevent mechanical
damage. Before installation, be sure to
have the appropriate model and style,
with the correct “A” dimension, orifice
size, temperature rating, and response
characteristics. Keep sprinklers with
protective caps or bulb shields con-
tained within the caps or shields during
installation and testing, and any time
the sprinkler is shipped or handled.
1. Apply a small amount of pipe-joint
compound or tape to the male
threads only, taking care not to al-
low a build-up of compound over the
brass inlet and seal.
2. Install the sprinkler on the piping us-
ing the special dry sprinkler wrench
only, while taking care not to dam-
age the sprinkler. DO NOT use a
pipe wrench on the barrel of the dry
pendent sprinkler. NOTE: Sprin-
klers with protective caps or bulb
shields must be contained within the
caps or shields before applying
pipe-joint compound or tape.
3. Escutcheons for adjustable standard
and adjustable recessed dry pen-
dent sprinklers can be installed after
the sprinkler has been installed onto
the piping. Escutcheons slip on
from below the ceiling.
E. After installation, the entire sprinkler
system must be tested. The test must
be conducted to comply with the Instal-
lation Standards.
Make certain the unit has been properly
tightened. If a thread leak should occur,
normally the unit must be removed, new
pipe-joint compound or tape applied, and
then reinstalled. This is due to the fact
that when the joint seal leaks, the sealing
compound is washed out of the joint.
F. Remove plastic protective sprinkler
caps or bulb shields AFTER the ceiling
finish work is completed where the
sprinkler is installed and there no lon-
ger is a potential for mechanical dam-
age to the glass bulbs. To remove the
bulb shields, simply pull the ends of the
shields apart where they are snapped to-
gether. To remove caps, turn the caps
slightly and pull them off the sprinklers.
SPRINKLER CAPS OR BULB
SHIELDS MUST BE REMOVED FROM
SPRINKLERS BEFORE PLACING THE
SYSTEM IN SERVICE!
G. Wet pipe systems supplying dry pen-
dent sprinklers must be provided with
adequate heat. Refer to appropriate in-
stallation standards.
7. MAINTENANCE
NOTICE: The owner is responsible for
maintaining the fire-protection system and
devices in proper operating condition. For
minimum maintenance and inspection re-
quirements, refer to the National Fire Pro-
tection Association standard that de-
scribes care and maintenance of sprinkler
systems. In addition, the Authority Having
Jurisdiction may have additional mainte-
nance, testing, and inspection require-
ments that must be followed.
A. The sprinklers must be inspected on a reg-
ular basis for signs of corrosion, mechani-
cal damage, obstructions, paint, etc. The
frequency of the inspections may vary
due to corrosive atmospheres, water sup-
plies, and activity around the device.
B. Sprinklers that have been field painted,
caulked, or mechanically damaged must
be replaced immediately. Sprinklers
showing signs of corrosion shall be tested
and/or replaced immediately as required.
Installation standards require sprinklers to
be tested and, if necessary, replaced after
a specified term of service. Refer to the in-
stallation standards (e.g., NFPA 25) and
the AHJ for the specified period of time af-
ter which testing and/or replacement is re-
quired. Never attempt to repair or reas-
semble a dry pendent sprinkler. Sprin-
klers that have operated cannot be reas-
sembled or re-used, but must be re-
placed. When replacing sprinklers, use
only new sprinklers.
C. The sprinkler discharge pattern is criti-
cal for proper fire protection. Nothing
should be hung from, attached to, or
otherwise obstruct the discharge pat-
tern. All obstructions must be immedi-
ately removed or, if necessary, addi-
tional sprinklers installed.
D. When replacing existing sprinklers, the
system must be removed from service.
Refer to the appropriate system de-
scription and/or valve instructions.
Prior to removing the system from ser-
vice, notify all AHJs. Consideration
Minimum ceiling hole size:
2-1/8" (54 mm) diameter.
Maximum ceiling hole size:
2-1/2" (63,5 mm) diameter.
Adjustment:
5/16" (7,9 mm)
Minimum: 1" (25,4 mm)
Maximum: 1-5/8" (41,2 mm)
Figure 3: Adjustable Recessed Dry Pendent Sprinkler with up to 5/8"(15,8 mm) of Adjustment
For "A" Dimension:
1. Determine the distance from
face of tee to finished ceil-
ing.
2. Round to nearest ¼" (6,35
mm) between 3-1/4" and
47-1/2" (82,5 mm and 1 207
mm).
NOTE: The sprinkler will be re-
cessed approximately 5/16"
(7,9 mm) above the finished
ceiling with 5/8" (15,8 mm) of
vertical adjustment avail-
able.
Finished Ceiling
5/16" (7,9 mm)
3-1/16"
(77,8 mm)
Sprinkler 101 c
TECHNICAL DATA STANDARD RESPONSE
DRY PENDENT SPRINKLERS
1-5/8"
(48,3 mm)
Outside
diameter:
1-5/16"
(33,4 mm)
[same as
1" (25 mm)
Schedule
40 pipe].
For “A”
Dimension:
1. Determine dis-
tance from face
of tee to base of
sprinkler.
2. Round up to the
next higher ½"
(12,7 mm) in-
crement be-
tween 3" (76,2
mm) and 47"
(1 194 mm).
Figure 2
Plain Barrel Dry Pendent Sprinkler
September 16, 2005
OBSOLETE
should be given to employment of a fire
patrol in the effected area.
1. Remove the system from service,
drain all water, and relieve all pres-
sure on the piping.
2. Using the special sprinkler wrench,
remove the old sprinkler and install
the new unit. Care must be taken to
ensure that the replacement sprin-
kler is the proper model and style,
with the appropriate “A” dimension,
orifice size, temperature rating, and
response characteristics.
3. Place the system back in service
and secure all valves. Check for and
repair all leaks.
E. Sprinkler systems that have been sub-
jected to a fire must be returned to ser-
vice as soon as possible. The entire
system must be inspected for damage
and repaired or replaced as necessary.
Sprinklers that have been exposed to
corrosive products of combustion or
high ambient temperatures, but have
not operated, should be replaced. Re-
fer to the AHJ for minimum replace-
ment requirements.
Sprinkler 101 d
TECHNICAL DATA STANDARD RESPONSE
DRY PENDENT SPRINKLERS
Form No. F_071591
Approval Chart
Standard Response Dry Pendent Sprinklers
Standard Orifice
Thread Size Sprinkler Description Nominal K-factor3Order Length
Increment Listings and Approvals2
NPT BSP Style Base Part Number1SIN U.S. metric Inches mm cULus5FM NYC4LPCB
1" – Adjustable
Standard
07740 VK154 5.6 – ½" 12,7 A1 A2 A1 –
– 25 mm 07854 VK154 – 8,1 ½" 12,7 A1 A2 – –
– 25 mm 09341 VK155 – 8,1 ½" 12,7 – – – A2
1" – Adjustable
Recessed
06530 VK158 5.6 – ¼" 6,35 B3 B3 B3 –
– 25 mm 07853 VK158 – 8,1 ¼" 6,35 B3 B3 – –
– 25 mm 09342 VK159 – 8,1 ¼" 6,35 – – – B3
1" –
Plain Barrel
07852 VK150 5.6 – ½" 12,7 A4 A4 A4 –
– 25 mm 07855 VK150 – 8,1 ½" 12,7 A4 A4 – –
–25 mm 09343 VK151 –8,1 ½" 12,7 – – – A4
Large Orifice
Thread Size Sprinkler Description Nominal K-factor7
Order Length
Increment Listings and Approvals2
NPT BSP Style Base Part Number1SIN Inches mm cULus5FM NYC6LPCB
1" –Adjustable
Standard
12810 VK163 8.0 U.S. (11,5
metric) for lengths
up to 20". For
lengths exceeding
20", refer to Fig. 4
on page 101 d.
½" 12,7 A1 – A1 –
–25 mm 12813 VK163 ½" 12,7 A1 – A1 –
1" –Adjustable
Recessed
12811 VK164 ¼" 6,35 B3 – B3 –
–25 mm 12814 VK164 ¼" 6,35 B3 – B3 –
1" –Plain Barrel 12741 VK166 ½" 12,7 A4 – A4 –
–25 mm 12812 VK166 ½" 12,7 A4 – A4 –
Approved Temperature Ratings
A - 155 °F (68 °C), 175 °F (79°C), 200 °F (93 °C), and 286 °F
(141 °C)
B - 155 °F (68 °C), 175 °F (79°C), and 200 °F (93 °C)
Approved Finishes and "A" Dimensions
1- Chrome-Enloy®or White Polyester sprinkler with a Chrome-Enloy®Sleeve
and Escutcheon with "A" dimensions 1-1/2" to 45-1/2" (38,1 mm to 1 156 mm)
2 - Chrome-Enloy®with "A" dimensions 1-1/2" to 45-1/2” (38,1 mm to 1 156 mm)
3 - Chrome-Enloy®or White Polyester with "A" dimensions 3-1/4" to 47-1/2"
(82,5 mm to 1 207 mm)
4 - Chrome-Enloy®or Brass with "A" dimensions 3" to 47" (76,2 mm to 1 194 mm)
Footnotes
1Base part number is shown. For complete part number, refer to Viking's current price schedule.
2This table shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for
any additional approvals.
3K-factor applies for standard lengths ("A" Dimensions indicated above). Metric K-Factor shown is for use when pressure is measured in kPa.
When pressure is measured in BAR, multiply the metric K-Factor shown by 10.0.
4Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. II.
5Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
6Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. XV.
7Metric K-Factors shown are for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K-Factor shown by 10.0.
Metric K-Factors are for use when pressure is measured in kPa.
When pressure is measured in BAR, multiply the metric K-Factor shown by 10.0.
Lengths exceeding the standard length are available, with no approvals,
on a “made-to-order” basis. Contact the manufacturer.
U.S. K Factor
Metric K-Factor
Temperature KEY
Finish
A1X Escutcheon (if applicable)
September 16, 2005
Replaces page 101 a-d, dated May 13, 2005
(revised the K-Factor graph).
Figure 4: K-Factor/Length Graph for Large Orifice Dry Pendent
Sprinklers for lengths from 20" to 48" (508 mm to 1 219 mm).
Note: For lengths up to 20" (508 mm), the nominal
K-Factor is 8.0 U.S. (11,5 metric).
OBSOLETE

Other manuals for M

6

This manual suits for next models

9

Other Viking Irrigation System manuals

Viking MICROMATIC VK106 Instruction manual

Viking

Viking MICROMATIC VK106 Instruction manual

Viking VK960 Instruction manual

Viking

Viking VK960 Instruction manual

Viking VK530 Instruction manual

Viking

Viking VK530 Instruction manual

Viking FREEDOM VK495 Instruction manual

Viking

Viking FREEDOM VK495 Instruction manual

Viking MicrofastHP VK315 Instruction manual

Viking

Viking MicrofastHP VK315 Instruction manual

Viking MICROFAST M-4 Instruction manual

Viking

Viking MICROFAST M-4 Instruction manual

Viking FREEDOM VK484 Instruction manual

Viking

Viking FREEDOM VK484 Instruction manual

Viking MICROFAST VK326 Instruction manual

Viking

Viking MICROFAST VK326 Instruction manual

Viking Microfast M Instruction manual

Viking

Viking Microfast M Instruction manual

Viking MICROFAST VK302 Instruction manual

Viking

Viking MICROFAST VK302 Instruction manual

Viking MICROFAST VK306 Manual

Viking

Viking MICROFAST VK306 Manual

Viking VK2022 Instruction manual

Viking

Viking VK2022 Instruction manual

Viking VK520 User manual

Viking

Viking VK520 User manual

Viking MICROFAST VK354 Instruction manual

Viking

Viking MICROFAST VK354 Instruction manual

Viking MICROMATIC VK202 Instruction manual

Viking

Viking MICROMATIC VK202 Instruction manual

Viking V-SD Instruction manual

Viking

Viking V-SD Instruction manual

Viking FREEDOM VK4840 Instruction manual

Viking

Viking FREEDOM VK4840 Instruction manual

Viking VK514 Instruction manual

Viking

Viking VK514 Instruction manual

Viking VK206 Instruction manual

Viking

Viking VK206 Instruction manual

Viking VK2001 Instruction manual

Viking

Viking VK2001 Instruction manual

Viking VK531 Instruction manual

Viking

Viking VK531 Instruction manual

Viking SIN VK500 Instruction manual

Viking

Viking SIN VK500 Instruction manual

Viking VK800 Instruction manual

Viking

Viking VK800 Instruction manual

Viking MICROFAST VK345 Instruction manual

Viking

Viking MICROFAST VK345 Instruction manual

Popular Irrigation System manuals by other brands

RainPoint TTV102B user manual

RainPoint

RainPoint TTV102B user manual

Reliable F156 Series Bulletin

Reliable

Reliable F156 Series Bulletin

brendz Valera manual

brendz

brendz Valera manual

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Homesafe F1 Res 44 quick guide

Homesafe

Homesafe F1 Res 44 quick guide

Rain Bird GRDNERKIT instruction sheet

Rain Bird

Rain Bird GRDNERKIT instruction sheet

claber POP-UP 0-350 user manual

claber

claber POP-UP 0-350 user manual

Sime MERCURY Operation, Installation, Maintenance, Spare Parts

Sime

Sime MERCURY Operation, Installation, Maintenance, Spare Parts

ATIKA VT 36 Original instructions

ATIKA

ATIKA VT 36 Original instructions

Eden 94152EDAMZ quick start guide

Eden

Eden 94152EDAMZ quick start guide

Globe GL-QR/DC Series quick start guide

Globe

Globe GL-QR/DC Series quick start guide

Tyco Fire Product Star SuperNova S120 instruction manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S120 instruction manual

Tyco Fire Product Gem F892QR instruction manual

Tyco Fire Product

Tyco Fire Product Gem F892QR instruction manual

IrriGreen 2 Quick install guide

IrriGreen

IrriGreen 2 Quick install guide

Reliable DH56 HSW-PL manual

Reliable

Reliable DH56 HSW-PL manual

Tyco Fire Product S1810 manual

Tyco Fire Product

Tyco Fire Product S1810 manual

Tyco WS TY3388 operating instructions

Tyco

Tyco WS TY3388 operating instructions

Gardena OS 140 operating instructions

Gardena

Gardena OS 140 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.