VC-6832 Conventional Fire Alarm Control Panel
Product Information
1. Overview
VC-6832 Conventional Fire Alarm Control Panel is developed based on the microprocessor technology. It has only
one detection zone, connected with one Smoke Detector and one Heat Detector. One Sounder output on Mainboard
is available for alarm control. Meanwhile, there are also one volt-free contact for common fault output, and two
volt-free contacts for re output. The panel will indicate the status of normal, fault and alarm, as well as short or
broken circuit. All the manual control could be done through ve keys of Self-test, Mute, Silence/resume, Reset and
Evacuate. As designed, using friendly of Installation and Operation is the major feature of VC-6832, which is ideal
option for the application of telecom station or data centre.
2. Technical scications
2.1 Operating Voltage
Power Supply: 48VDC
Operating Voltage: 24VDC
Current: Standby-100mA, Action-1A
Recommended Wiring:
1.5mm2or above shield cable, subject to local installation codes.
2.2 Detection Loop Parameters
Output voltage: 20VDC-28VDC
Quiescent current: 2.4mA (connecting with 2 conventional detectors)
Resistance when alarming re: 150Ω-1.5kΩ (normally 470Ω)
Terminal resistance: 4.7kΩ
Recommended Wiring: Fire cable 2 core and Earth 1.0mm2 CSA, subject to local installation codes.
2.3 Output Parameters
Recommended Wiring: Fire cable 2 core and Earth 1.0mm2 CSA, subject to local installation codes.
Sounder: Output voltage 20VDC-28VDC, output current 1A, terminal resistance 4.7k
Fault: Volt-free contact output, capacity 1A 24VDC
Fire 1: Volt-free contact output, capacity 1A 24VDC (It activates when each detector checks re condition)
Fire 2: Volt-free contact output, capacity 1A 24VDC (It activates when both two detectors check re condition)
2.4 Dimension
280mm×200mm×60mm
1