VTdrive FWI-SS Series User manual

www.vtdrive.com
1
Soft Starter User Manual
Safety Clauses
1. The general of FWI-SS Series Soft Starter
1.1 The main function
1.2 The main characteristics
2. Code explanation and Check-up before using
3. Usage conditions and Installation directions
3.1 The Usage condition
3.2 The Installation requirement
3.3 The Installation Directions
4. Connection and External terminal
4.1 The diagram connection
4.2 The external terminal
4.3 The diagram of Main circuit connection
4.4 The communication interface
5. Control panel and its operation
5.1 The operation of control panel
5.2 Parameter set and explanation
5.3 The functions of "Programmable relay output"
5.4 The function of Automatic Re-start
5.5 Directions for other set items
5.6 Help message and explanation
6. Protection Functions and directions
6.1 Protection functions and theirs parameter
6.2 Protection classes and explanation
7. Test run and application
7.1 Set up electricity to test run
7.2 Starting modes and application
7.3 Stopping modes and application
7.4 Application example

www.vtdrive.com
2
Safety Clauses
In the process of using the soft starter, please note the following Safety Clauses
Please check this user manual carefully before using the product.
Only the technical person is allowed to install the product.
To be sure that the motor is correctly matched with the soft starter.
It is forbid to connect capacitors to the output terminals (U V W).
Please seal the terminal switch insulation glue after finishing
connect them.
The soft starter and its enclosures must be fixedly earthed.
During the maintenance and repair, the input must be power.

www.vtdrive.com
3
1. The General of FWI-SS Series Soft Starter
FWI-SS series Soft Starter is new type start-up equipment which integrates
electric force and electron techniques computer technique and modern control
theory. It is the new generation product to replace the conventional Star-delta
Starter, Self-coupling voltage-drop Starter and Magnetic control voltage-drop
Starter.
1.1 The main function
●This Motor Soft Starter can reduce the starting current of Motor and the
power-distribution capacity to Motor effectively, so it could save the cost.
●It can reduce the starting stress of motor and other loading equipments, so that
lengthen their service life.
●The function of soft stopping can solve effectively the surging problem of inertia
system when stopping. The conventional motor starting equipments can not
realize it.
●The perfect and reliable protection features, can give the effective protection to
the operator’s safety as well as the motor and matched equipments.
●The application of intelligent and network technique make the FWI-SS type Soft
Starter meet the high -speed development of Electrical force automated technique
effectively.
1.2 The main characteristics
Perfect design
Pretty external shape and structure, perfect and unique functions, simple and

www.vtdrive.com
4
reliable operation, every technological is made in the best design.
Reliable and high-grade quality
This product is designed according to the computer analog test, has the best
electromagnetic compatibility. It is proved high quality by the high-temperature
ageing test and jigging test which done before the products out of factory.
Complete and perfect protection functions
Such as offset voltage protection, failure voltage protection, over voltage
protection, Motor overheat or starting time over long protection, input or output
failure phase and three-phase unbalanced protection, over current, over load and
short current protection, unbalanced protection, over current, over load and short
current protection.
Having the decision-making intellectual property of the product
Including exterior designing patent, decision-making software copyright, the
starting and protection techniques of Motor, and the technology of detecting and
debugging
The best service
The reliable function and quality is the basic of the best service. Even more, we
can supply the special designing and functions of product matched to your need
and the timely and perfect usage consulting service.
2. Code explanation and Check-up before using
Please check up the products before using, if in some problems; please do not
hesitate to contact us with any request for additional information. Check-up the
type of product whether it is the right one you order

www.vtdrive.com
5
FWI-SS series Motor Soft Starter
Code
FWI-SS3 -5d5-4
Input voltage
3-phase AC460V 60Hz
Matched motor
5.5KW
Ex-factory code
Date of produce
Company Name
●Check any damage to the product because of the transport, such as the spare
parts are apart from the main body or the shell be damage etc.
●Check others, including the Certificate of Soundness, and the User Manual.
3. Usage condition and installation requirement
It is strict rule for the users to use or install the soft starter according to the
requirement; otherwise, it will be in bad result.
3.1 The usage condition
Power Supply: City power, self-provided power, diesel oil dynamotor, 3-phase
alternating current 380V, 480V or 660V±10%, 50Hz or 60Hz.The power capacity
to the soft start must meet the motor starting requirement.
Motor Matched: squirrel-case asynchronous motor whose power is matched with
the soft starter
Starting Frequency: The starting time is according to the loading equipments
Cooling Mode: Naturally wind cooling
Protective Grade: IP20
Environment Conditions: when altitude is less than 2000m, the temperature of
the environment should be between -25~40, relative humidity should be less
than 90%, no vapor, no flammable, volatile, corrosive gas. No electric dirt, indoor
installation, ventilated, vibration is less that 0.5G. Note: Over more, we can
manufacture other type soft starters which are used in special conditions, such as

www.vtdrive.com
6
explosion-proof type soft starter, low-temperature type soft starter, or high-voltage
type soft starter.
3.2 The installation requirement
●The direction and distance of installation: In order to make sure that the soft
starter be in good draft and heat dissipation, please install the product in vertical
direction, and be sure the spare around the product is enough.
(See the following diagram 3.1 and 3.2)
●If the soft starter is installed in a box, please note that the draft is very good, as
well as the above notes.
(See the following diagram 3.3)
3.3 The Installation Dimensions
The External shape and installation dimensions of 5.5KW-55KW
Specifications
Power
(KW)
External shape
dimensions(mm)
Installation
dimensions(mm)
NW
(kg)
W1
H1
D
W2
H2
d
FWI-SS3-5d5
5.5
143
270
160
129
247
M6
<3.5
FWI-SS3-7d5
7.5
143
270
160
129
247
M6
<3.5
FWI-SS3-011
11
143
270
160
129
247
M6
<3.5
FWI-SS3-015
15
143
270
160
129
247
M6
<3.5
FWI-SS3-018
18.5
143
270
160
129
247
M6
<3.5
FWI-SS3-022
22
143
270
160
129
247
M6
<3.5
FWI-SS3-030
30
143
270
160
129
247
M6
<3.5
FWI-SS3-037
37
143
270
160
129
247
M6
<3.5
FWI-SS3-045
45
143
270
160
129
247
M6
<3.5
FWI-SS3-055
55
143
270
160
129
247
M6
<3.5
Note: The rated power of motor in the above form is the maximum rated value.
generally, the values of matched motor should not be more than this value.

www.vtdrive.com
7
The External shape and installation dimensions of 75KW-560KW
Specifications
Power
(KW)
External shape
dimensions(mm)
Installation
dimensions(mm)
NW
W1
H1
D
W2
H2
d
(kg)
FWI-SS3-075
75
260
470
200
230
440
M8
<20
FWI-SS3-090
90
260
470
200
230
440
M8
<20
FWI-SS3-115
115
260
470
200
230
440
M8
<20
FWI-SS3-132
132
260
470
200
230
440
M8
<20
FWI-SS3-160
160
260
470
200
230
440
M8
<20
FWI-SS3-185
185
260
470
200
230
440
M8
<20
FWI-SS3-200
200
260
470
200
230
440
M8
<20
FWI-SS3-250
250
290
500
200
260
470
M8
<20
FWI-SS3-280
280
290
500
200
260
470
M8
<20
FWI-SS3-320
320
290
500
200
260
470
M8
<20
FWI-SS3-400
400
400
555
200
370
525
M8
<20

www.vtdrive.com
8
FWI-SS3-450
450
400
555
200
370
525
M8
<20
FWI-SS3-500
500
400
555
200
370
525
M8
<20
FWI-SS3-560
560
400
555
200
370
525
M8
<20
4. Connection and External terminal
The FWI-SS Soft Starter has three types of connection, as following Main circuit
connection: it contains the wiring of 3-phase source input, the output to motor, and
the pass -by contactor connection. External terminal connection that is the wire
comes from twelve external terminals which including control signal and analogue
output signal. Communication connection, there are two communication
interfaces; those are RJ-45 standard web line socket and Db6socket which are
connected to computer.
4.1 The diagram connection (see the diagram 4.1)

www.vtdrive.com
9
4.2 The external terminal
Please see the diagram 4.2
●Terminal ① ② are by-pass output, are used to control the by-pass
contactor. They are normal open contacts and are closed when finishing starting.
The contact capacity is Ac250V/5A
●Terminal ③ ④ are programmable relay output: it is set by FJ code .They
are normal open no-power contacts Please see the detailed information in 5.3
item. The contact capacity is AC250V/5A
●Terminal ⑤ ⑥ are fault output , they will be closed when there are any
fault matters happened to the soft starter or loose electricity, while at normal case
they are open. The contact Capacity is AC25V/0.3A
●Terminal ⑦are Instantaneous stop input, this terminal must be connected
with terminal ⑩when the starter works normally. But if these two terminals are
both open, the soft starter will stop, and at this time the starter is at the state of
fault protection. Terminal⑦can be controlled by the output contact of external
protection dives, and it is useless when the F12Key is set as 0(basic protection).
●Terminal ⑧ ⑨ ⑩ are start-up or stop input .There two ways of connections
for your choose, those are 3-wire connection and 2-wire connection.
●Please see the diagram 4.3

www.vtdrive.com
10
Terminal ⑾ ⑿ are DC 0-20mA analogue output ,they show the current value of
motor when real-time working, 20mA is full-scale value and is four times than
rated current of nominal power of soft starter, while, we can contact a 0-20mADC
current meter to check. The Max value of output load resistance is 300Ω
Note: Please make sure that external terminals are in right connection; otherwise,
the product may be damaged.
4.3 The diagram of Main circuit connection
Please see the diagram 4.4

www.vtdrive.com
11
4.4 The communication interfaces
RJ-45 is the standard web line socket
DB9 socket has Rs485 and RS232 interfaces inside
Please see the diagram 4.5
The user can choose the following software
1. Computer collector distribution control communication software
2. Device Net interface card and communication software
3. Device Net/Mod-bus/ Profi-bus gateways
4. Others
5. Control Panel and its operation
There are five working states of soft starter, those are: Ready, Run, Fault, Start
and Stop. The control panel will show the current vault of motor when in the
process of start or stop, and it will show the set and help menu at other states.
5.1 The operation of control panel

www.vtdrive.com
12
●Open state: you should not press the "run" key until the ready-lamp lights and
show “READY"
●Time-delay state: When the ready-lamp or fault-lamp is shining, it means it is
interval time delay; and when the Display screen shows "dEXXX", means staring
time-delay.
●The "Run" or "Stop" key: In the process of staring, the panel shows "XXXX" that
is the value of start-up current .At this time only "Stop" key is in use. And the
lamps of ready, run and fault are all dark, and you can not come into the "set" and
"help menu" state. While, in the process of stopping, the panel shows "XXXX" that
is the value of start-up current. At this time, only "Run" key is in use, and the
lamps of ready, run and fault are all dark, and you can not come into the "set" and
"help menu” state.
●The "Set" key: Press "Set" key to come into the Set Menu and now the panel is
showing FX: XXX. Please press "Set" key again and Colon is shining, then you
can change the Parameters under the Colon you need If you want to keep the
Parameters changed, Please press "Yes" key, and if you do nor want, please
pressing the "Set" key until the Colon stops shining, then the Parameters are
former .Having finished the above operation, please press the "Yes" key to return
or "Stop" key to return directly
●The "Yes" key: Press the "Yes" key directly; you will come into Help Menu and
the panel shows HX: XXX. When you finish reading the Help Menu, you can press
this key again or "Stop" key to return. This key not only can be used to keep the
Parameters when you set the parameters you need, but also be sued as
"Returning".

www.vtdrive.com
13
●The "Up" and "Down" ("▲"" ▲") key :In the Set Menu ,you can press these
two keys to choose the Function Code you need when the Colon is not shining
and can choose the Parameters under the Colon when Colon is shining ,It is the
same as the operation in Help Menu. When the Pass-by -lamp is lighting and the
Display Screen shows AXXX which means the operation current value of motor,
now you can press "Up" or "Down" key and the Screen will PXXXX or HXXXX i n t
u n (P X XXX means the apparent power of motor; HXXXX means the over-load
heat balance coefficient, if this value is more than 100%, the Screen shows
"Err06", that means it is at that state of over-load protection.)
Note: 1. only the operation is correct, it will be with the voice when pressing the
key. Otherwise, the operation is wrong.
● the control panel uses the super anti-interference material, so it can be state of
3 meters away.
5.2 Parameters set and explanation
The explanation for "Parameter-set "codes
Code
Explanation for
codes
The range
of value
Ex-factory
value
Special explanation
P0
This code is used
to set the “voltage
value”
30-70%
30%
This code can be used when the
starting mode is set as “Ramp
voltage to start,” and if is
“Limit-current” mode ,the value will
be fixed as 40%
P1
This code is used
to set the “soft
starting
2-60S
16S
It is invalid in“ Limit-Current”
starting mode.

www.vtdrive.com
14
time”
P2
This code is used
to set the “soft
starting
time”
0-60S
0S
If the code is set as “0”,the
motor will “staring mode”
P3
This code is used
to set the time of“
start-up time delay”
0-999S
0S
By the count-down way, If set as
“0”, the starter will start up the
motor Immediately without
time-delay.
P4
This code is used
to
time of
“programming
output
time-delay”
0-999S
0S
Be used with” programming
relay output”
P5
This code is used
to
set the “Interval
start
time-delay”
0-999S
0S
Be used when you need or have
to
Re-start the motor for several
times, or Re-start the motor after
removing the over-heat protection
for motor.
P6
This code is used
to
set the “start-up
limit
current value”
50-500%
280%
It is used when the staring mode
is “Limit-current”, and the value
will be fixed as 400% when the
starting mode is” Ramp voltage to
start”

www.vtdrive.com
15
P7
This code is used
to
set the “maximum
working current of
soft starter”
50-200%
100%
The “50-200%”is basic on the
nominal current of motor. If the set
value of this code over 200%,the
soft starter will be “inverse time
heat protection”
P8
This code is used
to set
the” the modes of
input
display”
0-3
1
Set the detailed in Item 5.5
P9
This code is used
to set
the” under-voltage
protection”
40-90%
80%
When the working voltage is
under
the value range(40%),the soft
starter will be in under-voltage
protection
PA
This code is used
to set
the “the
under-voltage
protection”
100-140%
120%
When the working voltage is
under
the value range(90%),the soft
starter will be in under-voltage
protection
PB
This code is used
to set
the ”modes of
starting”
0-5
1
0:Limi-current to start 1:Ramp
voltage to start 2:Torque control +
limit current 3:Torque control +
Ramp voltage 4:Ramp
current to start 5:Double closed
loop
PC
This code is used
to adjust protection
0-4
4
0: primary level;
1: light level;

www.vtdrive.com
16
level
2: standard level;
3: heavy level;
4: super level.
PD
This code is used
to set starting time
of output of the
programmable
relay
0-7
1
FE
This code is used
to set
the “time of re-start”
0-13
0
Set the detailed in Item 5.4
FF
This code is used
to set
the “parameter
change”
0-2
1
Set the detailed in Item 5.5
FH
This code is used
to set
the” communication
address”
0-63
0
FJ
This code is used
to set
the” programming
output”
0-19
7
Set the detailed in Item 5.3
FL
This code is used
to set
the “soft-stopping
limit
current value”
20-100%
80%
Set the detailed in Item 7.3

www.vtdrive.com
17
FP
This code is used
to set
the” rated
current-of Motor”
Rated
value
“The rated current of motor”
is the same as the current nominal
current of motor
FU
This code is used
to set
the “motor
under-load
protection”
Prohibition
Set the detailed in Item 5.5
Note:
●F7 the "Max working current”, is basic on the nominal current of motor.
●If you have no any operation for 2 Minutes after you come into the "set" state,
you will return from "set" state.
●You can not set any parameters in the process of starting or stopping.
●If you press the "Yes" key to open the soft starter, you can make the set
parameters recovery to Ex-factory values.
5.3 The function of "Programmable relay output"
This function has two kinds of operation way, those are Programmable time
sequence output and output and Programmable state output.
●When the FJ is set as 0-4(or 10-14), the programmable operation way is time
sequence output, As the following form:

www.vtdrive.com
18
If need programmable relay output time-delay, the delay time is set by F4 code.
●When the FJ is set as 5-9(or 15-19), the programmable operation way is time
sequence output, As the following form:
●The way of programmable state output is used to show the working state of soft
state, and under this way, the F4 code is un-useful; The ex-factory value of FJ
code is "7"showing the ready state of soft starter and at this time the motor can be
started up; when the programmable output is in fault state, the faults m>>mean
the fault of motor, such as fault of Err05, Err06, Err12, Err15,and they are different
form the faults come from the terminals⑤⑥ output.
●When FJ>9,the reset state of programmable output is normal closed ,that is”
inverse phase output"
5.4 The function of Re-start
When the FE item is not set as "0", the Automatic Re-start function is in use. This
function is affective only the External Control connection is 2-wire way and is not
controlled by the FD item (External Control allowed). When it is 2-wire way you
can:
●Having got electricity and delay time for 60 seconds, the soft starter will Re-start

www.vtdrive.com
19
automatically.
●Having stopped because of any fault and delay time for 60 seconds, the soft
starter will Re-start automatically
●the total number of times of automatic re-start is "n" times,"n" is set by FE item.
●the function of automatic re-start is effect only when getting electricity and
opening again
●The soft starter has the protection function of under-voltage ,so when the
electricity be cut off and then get on again ,the soft starter will not Re-start no
matter which state the control terminals at, in case of the danger to operator. But if
the Automatic Re-start is allowed, the Protection function of under-voltage is no
use.
5.5 Directions for other set items
You can use F8 item choose the Input way and Display Way.
As the following form (Form 5.2)
Note: If the F6, F7 items input the percentage numerical value, the percentage
is the current Percentage set by FP item FD item used to set the control ways of
soft starter
As the following form (Form 5.3)

www.vtdrive.com
20
Numerical value
0
1
2
3
4
5
6
7
keyboard
1
1
0
0
1
1
0
0
External control
0
1
1
1
1
0
0
0
Communication
0
0
0
1
1
1
1
0
Note: In the above form,"1"is allowing,"0"is forbidding. For e example, if you forbid
any unexpected stopping or starting whether starting is running or in maintenance,
you can set the Numerical Value as"7"which means forbidding any starting or
stopping operation. If the "External Control" is used, you must contact a NC button
switch between the terminal ⑧and terminal ⑩, otherwise, the soft starter can
not start-up the motor.
●FJ item is used to set the starting time of output of the Programmable relay
As the following form (Form 5.4)
5.6 Help message and explanation
When the product is not starting or stopping ,or not at the "set" state, you can
press "Yes" key and come into Help menu ,then press the "Up" or "Down" key to
choose the help message. Please press "Yes" or "Stop" key to return.
Help message Form
This manual suits for next models
23
Other VTdrive Controllers manuals
Popular Controllers manuals by other brands

Jung
Jung 2501 HZUP Operation manual

Muller Elektronik
Muller Elektronik SPRAYER-Controller Orchard/Vineyard MIDI 3.0 Installation and operating instructions

AUMA
AUMA PROFOX PF-M100X manual

Siemens
Siemens FC18 Series operating manual

TECHCON SYSTEMS
TECHCON SYSTEMS TS550R user guide

CMC
CMC Airmaster R1 Hardware installation guide