Soft Starter User Manual
Safety Precautions
1. The General Description of FWI-SS3 Series Soft Starter
1.1 The Main Function
1.2 The Main Characteristics
2. Code explanation and Check-up before installation
3. Usage Conditions and Installation Directions
3.1 The Usage Conditions
3.2 The Installation Requirement
3.3 The Installation Directions
4. Connection and External terminal
4.1 The Diagram Connection
4.2 The External Terminal
4.3 The Diagram of Main Circuit Connection
4.4 The Communication Interface
5. Control Panel and its Operation
5.1 The Operation of Control Panel
5.2 Parameter Setting and Explanation
5.3 The Functions of "Programmable relay output"
5.4 The Function of Automatic Re-start
5.5 Directions for other set items
5.6 Help Message and Explanation
6. Protection Functions and Directions
6.1 Protection Functions and Parameters
6.2 Protection Classes and Explanations
7. Electrical Test and Application
7.1 Electrical Test
7.2 Starting Modes and Application
7.3 Stopping Modes and Application
7.4 Application Examples
Safety Precautions
Before installation of the soft starter, please note the following safety precautions
Please check this user manual carefully before installing the product.
Only the technical person is allowed to install the product.
The motor should be correctly matched with the soft starter.
It is forbidden to connect capacitors to the output terminals(U V W).
Please seal the terminal switch insulation glue after finishing
connection.
The soft starter and its enclosure must be reliable grounded.
During the maintenance and repair, the input must be power off.
www.vtdrive.com
VT d ri veVT d ri ve
01 02

1. The General Description of FWI-SS3 Series Soft Starter
FWI-SS3 series Soft Starter is new type start-up equipment which integrates
electric force and electron techniques computer technique and modern
control theory. It is the new generation product to replace the conventional
Star-delta Starter, Self-coupling voltage-drop Starter and Magnetic control
voltage-drop Starter.
1.1 The Main Function
●This Motor Soft Starter can reduce the starting current of Motor and the
power-distribution capacity to Motor effectively, so it can save the cost.
●It can reduce the starting stress of motor and other loading equipments,
so that can lengthen their service life.
●The function of soft stopping can solve effectively the surging problem
of inertia system when stopping. The conventional motor starting equipments
can not realize it.
●The perfect and reliable protection features, can give the effective
protection to the operator’s safety as well as the motor and matched
equipments.
●The application of intelligent and network technique make the
FWI-SS3 type Soft Starter meet the high -speed development of
electrical force automated technique effectively.
1.2 The Main Characteristics
Perfect design
Pretty external shape and structure, perfect and unique functions, simple
and reliable operation, every technological is made in the best design.
Reliable and High-grade Quality
This product is designed according to the computer analog test, has the
best electromagnetic compatibility. It is proved to behigh quality by the
high-temperature ageing test and jigging test which done before the
products out of factory.
Complete and Perfect Protection Functions
Such as offset voltage protection, failure voltage protection, over voltage
protection, Motor overheat or starting time over long protection, input or
output failure phase and three-phase unbalanced protection, over current,
over load and short current protection, unbalanced protection.
Having The Decision-Making Intellectual Property of The Product
Including exterior designing patent, decision-making software copyright,
the starting and protection techniques of Motor, and the technology of
detecting and debugging
The Best Service
The reliable function and quality is the basic of the best service. Even
more, we can supply the special designing and functions of product matched
to your need and the timely and perfect usage consulting service.
2. Code Explanation and Check-up before Installation
Please check up the products beforeinstallation, if any problems,
please do not hesitate to contact us with any request for additional
information. Check-up the type of product whether it is the right one
you order.
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
03 04

FWI-SS3 series Motor Soft Starter
Code
Input voltage
Matched motor
Ex-factory code
Date of produce
Company Name
FWI-SS3 -5d5-4
3-phase AC460V 60Hz
5.5KW
● Check if any damage to the product because of the transportation,
such as the spare parts are apart from the main body or
the shell be damage etc.
● Check others, including the Certificate of Soundness, and the User Manual.
3. Usage Condition and installation requirement
It is strict rule for the users to use or install the soft starter according to
the requirement; otherwise, it will be in bad result.
3.1 The Usage Condition
Power Supply: City power, self-provided power, diesel oil dynamotor,
3-phase alternating current 380V, 480V or 660V±10%, 50Hz or 60Hz.The
power capacity to the soft start must meet the motor starting requirement.
Motor Matched: squirrel-case asynchronous motor which power is
matched with the soft starter
Starting Frequency: The starting frequency is according to the loads.
Cooling Mode: Naturally wind cooling
Protective Grade: IP20
Environment Conditions: when altitude is less than 2000m, the tempe-
rature of the environment should be between -25~ 40, relative humidity
should be less than 90%, no vapor, no flammable, volatile, corrosive gas.
No electric dirt, indoor installation, ventilated, vibration is less that 0.5G.
Note: Over more, we can manufacture other type soft starters which are
used in special conditions, such as explosion-proof type soft starter, low-
temperature type soft starter, or high-voltage type soft starter.
3.2 The installation Requirement
● The direction and distance of installation: To make suret the soft
starter be in good draft and heat dissipation, please install the product
in vertical direction, and be sure the spare around the product is enough.
(See the following diagram 3.1 and 3.2)
● If the soft starter is installed in a box, please note that the draft is very
good, as well as the above notes.
(See the following diagram 3.3)
3.3 The Installation Dimensions
The outline dimension and installation dimensions of 5.5KW-55KWk
W1
143
143
143
143
143
143
143
143
143
143
H1
270
270
270
270
270
270
270
270
270
270
D
160
160
160
160
160
160
160
160
160
160
W2
129
129
129
129
129
129
129
129
129
129
H2
247
247
247
247
247
247
247
247
247
247
d
M6
M6
M6
M6
M6
M6
M6
M6
M6
M6
3.5
3.5
3.5
3.5
3.5
3.5
3.5
4
4.5
4.5
FWI-SS3-5d5
FWI-SS3-7d5
FWI-SS3-011
FWI-SS3-015
FWI-SS3-018
FWI-SS3-022
FWI-SS3-030
FWI-SS3-037
FWI-SS3-045
FWI-SS3-055
5.5
7.5
11
15
18.5
22
30
37
45
55
GW
(kg)
Outline
dimensions(mm)
Installation
dimensions(mm)
Rated
Power
(KW)
Model
Note: The rated power of motor in the above form is the maximum rated value.
generally, the values of matched motor should not be more than this value.
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
05 06

W1
257
257
257
257
257
257
257
290
290
290
330
330
330
330
H1
530
530
530
530
530
530
530
560
560
560
590
590
590
590
D
200
200
200
200
200
200
200
250
250
250
250
250
250
250
W2
196
196
196
196
196
196
196
260
260
260
265
265
265
265
H2
380
470
470
470
500
380
380
380
380
380
380
500
500
500
d
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M10
M10
M10
M10
4 5
17
17
17
18
18
18
24
24
24
30
30
41
41
.
GW
(kg)
Outline
Dimensions(mm)
Installation
Dimensions(mm)
Rated
Power
(KW)
Model
The outlinedDimension and installation dimensions of 75KW-600KW
FWI-SS3-075
FWI-SS3-090
FWI-SS3-115
FWI-SS3-132
FWI-SS3-160
FWI-SS3-185
FWI-SS3-200
FWI-SS3-250
FWI-SS3-280
FWI-SS3-320
FWI-SS3-400
FWI-SS3-450
FWI-SS3-500
FWI-SS3-600
75
90
115
132
160
185
200
250
280
320
400
450
500
600
The FWI-SS3 Soft Starter has three types of connection, as following Main
circuit connection: it contains the wiring of 3-phase source input, the output
to motor, and the by-pass contactor connection. External terminal connection
that is the wire comes from twelve external terminals which including control
signal and analogue output signal. Communication connection, there are
two communication interfaces; those are RJ-45 standard web line socket
and Db6socket which are connected to computer.
4.1 The Diagram Connection (See the diagram 4.1)
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
07 08

4.2 The External Terminal
Please see the diagram 4.2
DC4-20mA
output
● Terminal ① ② are by-pass output, are used to control the by-pass
contactor. They are normal open contacts and are closed when finishing
starting. The contact capacity is Ac250V/5A
● Terminal ③ ④ are programmable relay output: it is set by FJ code .
They are normal open no-power contacts Please see the detailed inform-
ation in 5.3 item. The contact capacity is AC250V/5A
● Terminal ⑤ ⑥ are fault output , they will be closed when there are any
fault matters happened to the soft starter or power off, while at
normal case they are open. The contact Capacity is AC25V/0.3A
● Terminal ⑦ are Instantaneous stop input, this terminal must be connected
with terminal ⑩ when the starter works normally. But if these two terminals
are both open, the soft starter will stop, and at this time the starter is at the
state of fault protection. Terminal⑦can be controlled by the output contact
of external protection dives, and it is useless when the F12Key is set as 0
(basic protection).
● Terminal ⑧ ⑨ ⑩ are start-up or stop input .There two ways of connec-
tions for your choice, those are 3-wire connection and 2-wire connection.
●Please see the diagram 4.3
Terminal ⑾ ⑿ are DC 0-20mA analogue output ,they show the current
value of motor when real-time working, 20mA is full-scale value and is four
times than rated current of nominal power of soft starter, while, we can
contact a 0-20mADC current meter to check. The Max value of output load
resistance is 300Ω
Note: Please make sure that external terminals are in right connection;
otherwise, the product may be damaged.
4.3 The Diagram of Main Circuit Connection
Please see the diagram 4.4
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
09 10

4.4 The Communication Interfaces
RJ-45 is the standard web line socket
DB9 socket has Rs485 and RS232 interfaces inside
Please see the diagram 4.5
1. Computer collector distribution control communication software
2. Device Net interface card and communication software
3. Device Net/Mod-bus/ Profi-bus gateways
4. Others
5. Control Panel and its Operation
There are five working states of soft starter, those are: Ready, Run, Fault,
Start and Stop. The control panel will show the current vault of motor when
in the process of start or stop, and it will show the set and help menu at
other states.
5.1 The Operation of Control Panel
● Open state: you should not press the "run" key until the ready-lamp
lights and show “READY"
● Time-delay state: When the ready-lamp or fault-lamp is shining, it
means it is interval time delay; and when the Display screen shows
"dEXXX", means staring time-delay.
● The "Run" or "Stop" key: In the process of staring, the panel shows
"XXXX" that is the value of start-up current .At this time only "Stop" key
is in use. And the lamps of ready, run and fault are all dark, and you can
not come into the "set" and "help menu" state. While, in the process of
stopping, the panel shows "XXXX" that is the value of start-up current.
At this time, only "Run" key is in use, and the lamps of ready, run and fault
are all dark, and you can not come into the "set" and "help menu” state.
● The "Set" key: Press "Set" key to come into the Set Menu and now the
panel is showing FX: XXX. Please press "Set" key again and Colon is
shining, then you can change the Parameters under the Colon you need
If you want to keep the Parameters changed, Please press "Yes" key, and
if you do nor want, please pressing the "Set" key until the Colon stops
shining, then the Parameters are former .Having finished the above
operation, please press the "Yes" key to return or "Stop" key to return
directly
● The "Yes" key: Press the "Yes" key directly; you will come into Help
Menu and the panel shows HX: XXX. When you finish reading the Help
Menu, you can press this key again or "Stop" key to return. This key not
only can be used to keep the Parameters when you set the parameters
you need, but also be sued as "Returning".
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
11 12

● The "Up" and "Down" ("▲"" ▲ ") key :In the Set Menu ,you can press
these two keys to choose the Function Code you need when the Colon is
not shining and can choose the Parameters under the Colon when Colon
is shining ,It is the same as the operation in Help Menu. When the Pass-by
-lamp is lighting and the Display Screen shows AXXX which means the
operation current value of motor, now you can press "Up" or "Down" key
and the Screen will PXXXX or HXXXX i n t u n (P X XXX means the apparent
power of motor; HXXXX means the over-load heat balance coefficient, if
this value is more than 100%, the Screen shows "Err06", that means it is
at that state of over-load protection.)
Note: 1. only the operation is correct, it will be with the voice when pressing
the key. Otherwise, the operation is wrong.
● the control panel uses the super anti-interference material, so it can
be state of 3 meters away.
5.2 Parameters Setting and Explanation
The explanation for "Parameter-set "codes
Code Codes Name Setting
Range
Factory
Default Eexplanation
P0
P1
This code is used
to set the “voltage
value”
This code is
used to set the
“soft starting
30-70%
2-60S
30%
16S
This code can be used when
the starting mode is set as
“Ramp voltage to start,” and
if is “Limit-current” mode ,the
value will be fixed as 40%
It is invalid in“ Limit-Current”
starting mode time”
Code Codes Name The range
of value
Factory
Default Explanation
P2
P3
P4
P5
P6
This code is
used to set the
“soft starting time” 0S
0S
0S
0S
280%
This code is used
to set the time of
“start-up time delay”
This code is used
for time of
“programming
output
time-delay”
This code is used
to set the
“Interval start
time-delay”
This code is used
to set the
“start-up limit
current value”
0-60S
0-999S
0-999S
0-999S
50-500%
It is free stop if set P2=0,
if use the soft starter for 2
motors, please set P2=0
By the count-down way, If
set as “0”, the starter will
start up the motor
Immediately without
time-delay.
Used with” programming
relay output”
It will also delay when the
overheating mode removed,
The indicator will be on
during delay mode.
as reminder
It is used when the staring
mode is “Limit-current”,
and the value will be fixed
as 400% when the starting
mode is” Ramp voltage
to start”
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
13 14

Setting the value as 7
means forbid to start or
stop operation, refer to
the details in item 5.5
Code Codes Name Setting
Range
Factory
Default Explanation
P7
P8
P9
PA
PB
100%
1
80%
120%
1
50-200%
0-3
40-90%
100-140%
0-5
This code is for
overload protection
This code is used
to set the” the
modes of input
display”
This code is used
to set the” under
-voltage
protection”
This code is used
to set the “the
under-voltage
protection”
This code is used
to set the ”modes
of starting”
P6, P7 programming
parameters are decided
by P8
Refer to the details in item 5.4
When the working voltage
is under the value range
(40%),the soft starter will
be in under-voltage protection
When the working voltage is
under the value range(90%),
the soft starter will be in
under-voltage protection
0:Limit-current to start
1:Ramp voltage to start
2:Torque control + limit current
3:Torque control + Ramp voltage
4:Ramp current to start
5:Double closed loop
Code Codes Name Setting
Range
Factory
Default Explanation
PC
PD
PE
PF
PH
PJ
PL
This code is
used to adjust
protection level 0-4
0-7
0-13
0-2
0-63
0-19
20-100%
4
1
0
1
0
7
80%
This code is used
to set starting
time of output of
the programmable
relay
This code is used
to set the “time
of re-start”
This code is used
to set the
“parameter
change”
This code is used
to set the”
communication
address”
This code is used
to set the”
programming
output”
This code is used
to set the “soft-
stopping limit
current value”
Refer to the details in Item 5.4
Refer to the details in Item 5.5
Refer to the details in Item 5.3
Refer to the details in Item 7.3
0: primary level;
1: light-load level;
2: standard level;
3: heavyoload level;
4: super level.
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
15 16

Code Codes Name Setting
Range
Factory
Default Explanation
PP
PU
This code is used
to set the” rated
current-of Motor”
Rated
value
Prohibition
“The rated current of motor”
is the same as the current
nominal current of motor
This code is used
to set the “motor
under-load
protection”
Refer to the details in Item 5.5
Note:
● F7 the "Max working current”, it is based on the nominal current of motor.
● If you have no operation for 2 Minutes after you come into the
"set" state, you will return from "set" state.
● You can not set any parameters in the process of starting or stopping.
● If you press the "Yes" key to start the soft starter, you can make the
parameters setting(except PJ) to f
5.3 The Function of "Programmable Relay Output"
This function has two kinds of operation way, those are programmable
time sequence output and programmable state output.
● When the PJ is set as 0-4(or 10-14), the programmable operation way
is time sequence output, As the following form:
actory default.
If need programmable relay output time-delay, the delay time is set
by P4 code.
●When the PJ is set as 5-9(or 15-19), the programmable operation way
is time sequence output, As the following form:
● The way of programmable state output is used to show the working
state of soft state, and under this way, the P4 code is invalid,The factory
default value of PJ code is "7"showing the ready state of soft starter and
at this time the motor can be started up, when the programmable output
is in fault state, the faults m> > mean the fault of motor, such as fault of
Err05, Err06, Err12, Err15,and they are different of the terminals ⑤⑥
output fault.
● When PJ>9,the reset state of programmable output is normal closed ,
that is” inverse phase output"
5.4 The Function of Re-start
When the PE item is not set as "0", the automatic re-start function is in
use. This function is affective only the external control connection is 2-
wire way and is not controlled by the PD item (External Control allowed).
When it is 2-wire way you can:
● Having got electricity and delay time for 60 seconds, the soft starter
will re-start automatically.
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
17 18

● Having stopped because of any fault and delay time for 60 seconds,
the soft starter will re-start automatically
● The total automatic re-start times is "n" ,"n" is setted by
PE parameter.
● The function of automatic re-start is valid only with the power on,
and it will be revalidated when the power on again.
Warning: The soft starter has the under-voltage
hen the power off, the soft starter will
not re-start no matter which state of the control terminals
But if the automatic re-start is allowed, the under-voltage is invalid.
protection function.
To avoid any danger to the operator, w
when power on again.
protection
5.5 Directions for Other Setting
You can use P8 code to choose the Input and Display Way.
As the following form (Form 5.2)
Note:
If the P6, P7 items input the percentage numerical value, the percentage
is the current Percentage set by PP itemPD item used to set the control
ways of soft starter
As the following form (Form 5.3)
Numerical value
keyboard
External control
Communication
0
1
0
0
1
1
1
0
2
0
1
0
3
0
1
1
4
1
1
1
5
1
0
1
6
0
0
1
7
0
0
0
Note: In the above form,"1"is allowing,"0"is forbidding. For e example,
if you forbid any unexpected stopping or starting whether starting is
running or in maintenance, you can set the Numerical Value as"7"which
means forbidding any starting or stopping operation. If the "External
Control" is used, you must contact a NC button switch between the
terminal ⑧ and terminal ⑩, otherwise, the soft starter can not start-up
the motor.
● PJ item is used to set the starting time of output of the Programmable
relay As the following form (Form 5.4)
5.6 Help Message and Explanations
When the product is not starting or stopping ,or not at the "set" state, you
can press "Yes" key and come into Help menu ,then press the "Up" or
"Down" key to choose the help message. Please press "Yes" or "Stop"
key to return.
Help message Form
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
19 20

6. Protection Functions and Explanations
We make our soft starters have all kinds of protection functions to protect
the soft starter and the motor using. Please choose the correct protection
class and parameters according to your application conditions!
Over-heat protection: when the temperature inside soft starter is up to
80℃±5℃,the starter will be into over-heat protection, when it down to
55℃,this protection invalid.
○ Input failure-phrase protection: the delayed time<3s
○ Output failure-phrase protection: the delayed time<3s
○ Three-phrase unbalanced protection: the delayed time<3s,when the
different current value among three phrases is more than 50%±10%,the
protection be used.
○ Starting over-current protection: the diagram 6.1 shows the protection
time when the current is 5 times than the rated working current.
○ Working over-load protection: the starter will be in inverse time thermal
protection on
more
Base of the Max working current of motor (Set by F6 Item),
(The diagram 6.1 s how)
○ Power voltage failure protection: the delayed time is separately less
than 0.5s or 3s when the power voltage is less than half of limited value
or less than setted value.
○ Over-voltage protection: the delayed time is separately less than 0.5s
or 3s when the power voltage is more than 130% of limited value or more
than the setted value.
○ Loading short-current protection: when the current is 10 times
than the motor rated current, it will be short circuited, and the short-
current protection will be take effect, the time is less than 0.1s.
○ The time parameters above start from the time receiving the message till
the protection take effect. The parameters are for reference only, all the protection
function can be proved by the applicaiton or the simulated test, If it is not meet
your demand, the special protection is needed to guarantee the safety.
6.2 Protection Classes and Explanations.
According different usage conditions, FWI-SS3 Soft Starter has five
protection classes, as following:
a. Primary Protection Level
b. Light-load Protection Level
c. Standard Protection Level
d. Heavy-load Protection Level
e. The Super Protection Level
● Primary protection level includes the protection functions of over-heat,
short -current protection and input failure-phrase protection when starting,
but no protection of internal connector instantaneous-shop. we can set the
protection level when the motor don’t need to be stopped urgently, such
as fire pump.
more
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
21 22

● The light-load level protection, standard protection level and heavy-load
protection level all have the protection function of soft standard.
The difference among them is the surges of motor overload heat-protection.
See the diagram of 6.1 and Form 6.1.
● When the motor in the super protection level starting, it can be
protected.
The protection classes and the time of heat protection Form (Form 6.1)
most
perfectly
Diagram 6.1
Motor heat protection curve diagram (Heat state)
7. Electrical Test and Application
Please do the following checking before the :
○ If the rated power of soft starter is matched with the Motor or not,
○ If the insulation of motor is meet the demand or not,
○ If the main circuit connection of input or output is correct or not,
○ If all the screws of terminals are twisted tightly or not.
7.1 Electrical Test
● When the power on, the soft starter displays the words of
" CSZPU " or “READY ", and the ready-lamp is on, then press
the "Run" key to start.
● Please set the rated current of the motor of PP parameter.
● Before startting the motor, you should check whether the motor
rotation direction is correct or not, If not, please press the “stop” key
immediately, after cut off the input power,reversing the wiring of motor.
electrical test
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
23 24

● If the soft starter starts n o t g o o d , y ou c an c he ck w he th er t he starting
mode you choose is suitable for your motor.
Please refer to the detailed explanation at 7.2: the starting mode and application
● If the starting torque of the motor is not big enough, you can increase the
starting voltage ( in voltage control mode) or enlarge the limit-current value
( in current control mode) to enlarge the starting torque.
● It is forbidden to open the upper cover after powered on,
otherwise electric shock may be caused.
● If there is any abnormal voice, smoke or smell , please cut off the electricity
immediately to check and find out the reasons.
● After power on or starting, if the fault-lamp is onand screen displays” Err××",
Please check the Form 7.1 to find out the reason according to the error code.
restoration external stop key
Note : When the temperature is below -10℃, the starter should be started
after preheated for 30 minute with power on.
●It can back to the to press the stop or the
Fault and Solution (Form 7.1)
Note:When the motor starts successfully , the by- -lamp will be l
ighting, that means the by- contactor is running . At this time,
if the contactor is not closed, the motor will stop running, please
check if the connection of the pass contactor is right or not.
7.2The starting mode and application
There are six starting modes for the user to choose according the motor
and load equipments, as the following:
pass
pass
by-
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
25 26

Note:It is normal that the starting time is less than the setted time under
the light load.This mode generally fits for the occasions where the motor
must be started smoothly
This mode is often used in the conditions which require strict limitation to
the current when starting.
7.2.3 Torque control to start (The P9 item is set as "2"or"3",this starting
mode is valid) Diagrams 7.3 and 7.4 show the output changing waveform
of torque control mode. When the static friction force in the state of heavy
load is too stronger to start the motor, this starting mode can be used,
When starting, the motor needs a very high voltage for a limited time
to remove the static friction force of heavy load, then the ramp voltage
mode or limit-current mode can be used to start the motor.
Note:This mode will cause big-current shock to the motor, so if the ramp
voltage or limit-current mode can be used, please do not choose to use the
torque control mode to start.
7.2.4 Ramp Current to start (The P9 item is set as"4", this starting mode
is valid)
7.2.5 Double closed loop (Both Ramp Voltage and Limit-current)to start
(The P9 items set as"5",this starting mode is valid) This starting mode
uses the control mode of Ramp voltage starting and Limit-current starting
Double Closed Loop circuit, it is a composite starting mode. The Output
voltage waveform is changed as Motor and the load equipments.
7.3 The Stopping Mode and application
The soft starter has two Stopping Modes: Soft-stopping mode
and Free-stopping mode.
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
27 28

7.3.1 Soft-stopping Mode (The P2 item is not set as"0",this stopping mode
is valid) When using this mode to stop the motor, the power to
motor will be transferred from the by-pass contactor to the controlled
silicon of soft starter, and the output voltage of starter will be reduced
gradually so that the running speed of motor can be cut down smoothly
in case of the mechanical shock. The output ending voltage is the same
as the initial voltage. Soft-stopping mode can reduce or remove the surge
of the loading equipments such as the water pump. You can set the soft-
stopping limit-current value through the PF item to reduce the big-current
shock to the motor when stopping. This limit-current value is a percentage.
7.3.2 Free-stopping Mode (The P2 item is set as"0",this stopping mode
is valid) When using this mode to stop the motor, the Soft Starter will
cut off the connection to the by-pass contactor and forbid the controlled
silicon outputting voltage as soon as receiving the order of stopping.
The motor stops gradually because of its Inertia. Generally, if the soft-
stopping mode is not necessary, please choose the free-stopping mode
to length the service life of the soft starter. This mode will completely
forbids the instantaneous output, in case the instantaneous big-current
shock to the motor in special application state.
supply
7.4 Application Examples
The parameters of the different loadings are different, please see the
Form 7.2
The parameters above is for reference only.
VT d ri veVT d ri ve
www.vtdrive.com www.vtdrive.com
29 30
This manual suits for next models
24
Other VTdrive Controllers manuals
Popular Controllers manuals by other brands

Grundfos
Grundfos Vaccuperm VGA-111 Installation and operating instructions

Victron energy
Victron energy BlueSolar MPPT 150/70 manual

V2
V2 AZIMUT manual

SunDisc
SunDisc Slimline Installation instructions and user manual

Resol
Resol DeltaSol MX manual

Mitsubishi Electric
Mitsubishi Electric MELSERVO-J4 series instruction manual

Orton
Orton AutoFire Plus user guide

Plexon
Plexon Optogenetic Controller manual

RMG
RMG RMG 610 Operation and Maintenance, Spare Parts

Lennox EMEA
Lennox EMEA SDI-V Installation, operation & maintenance manual

BIFFI
BIFFI HLAS-C Series Installation, operation and maintenance manual

Samson
Samson TROVIS 5724-8 Mounting and operating instructions