WAMGROUP SEPCOM SIP BED Easy User guide

2
fax
e-mail
internet
+ 39 / 0535 / 618111
+ 39 / 0535 / 618226
www.wamgroup.com
WAMGROUP S.p.A.
Via Cavour, 338
41030 Ponte Motta
Cavezzo (MO) - ITALY
Manual No. SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN
Issue: A3 Latest update: July 2022
ORIGINAL INSTRUCTIONS IN ENGLISH
®
SEPCOM
SIP BED Easy
CONTROL PANELS FOR
SEPCOM BEDDING
SCREW PRESS SEPARATORS
EN
ASSEMBLY AND
MAIN INSTRUCTIONS
FOR USE AND
MAINTENANCE

All the products described in this catalogue are manufactured according to WAMGROUP S.p.A. Quality System procedures.
The Company’s Quality System, certied in July 1994 according to International Standards UNI EN ISO 9002 and extended to
the latest release of UNI EN ISO 9001, ensures that the entire production process, starting from the processing of the order to the
technical service after delivery, is carried out in a controlled manner that guarantees the quality standard of the product.
This publication cancels and replaces any previous edition and revision.
We reserve the right to implement modications without notice.
This catalogue cannot be reproduced, even partially, without prior written consent by the Manufacturer.

III
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
QE SEPCOM SIP BED EASY
INDEX
TABLE OF CONTENTS
1.0 INTRODUCTION......................................................................................................................................1
1.1 Disclaimers........................................................................................................................................1
1.2 Symbols: meaning and use...............................................................................................................1
1.3 General features ...............................................................................................................................2
1.4 Operating principle ............................................................................................................................3
1.5 Lifting and shipment ..........................................................................................................................3
1.6 Storage and dismantling ...................................................................................................................4
2.0 APPLICATIONS .......................................................................................................................................6
2.1 Safety distances................................................................................................................................6
2.2 Emergency stop ................................................................................................................................6
2.3 Protection degree..............................................................................................................................7
2.4 Safety switches .................................................................................................................................8
2.5 Technical data ...................................................................................................................................8
2.6 Mandatory electrical connections......................................................................................................9
2.7 Pneumatic connection.....................................................................................................................10
3.0 COMMISSIONING ................................................................................................................................. 11
4.0 SETTING THE OPERATING PANEL & USE .........................................................................................12
4.1 How to use and set the operator panel ...........................................................................................12
4.2 Reset to factory settings..................................................................................................................25
4.3 How to reset the operation hours ....................................................................................................25
4.4 How to change time and date ........................................................................................................26
4.5 Alarms .............................................................................................................................................26
5.0 MAINTENANCE .....................................................................................................................................29
5.1 Personnel training ...........................................................................................................................30
5.2 Trouble-shooting .............................................................................................................................31
AANNEXES ..............................................................................................................................................36
A1 Electric layout ..................................................................................................................................36

1
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
1.0 INTRODUCTION
QE SEPCOM SIP BED EASY
1.1 Disclaimers
WAMGROUP S.p.A. cannot be held responsible in case of:
- Negligent handling of the low the voltage panels and non-compliance to the safety standards and wrong
processing.
- Lack of maintenance, non-compliance to the herein indicated Directives or improper repairs carried out with
improper tools by.
- Any type of damage incurred during shipping.
- Improper use.
- Modications to the low voltage control panels carried out by unauthorized, non trained personnel.
1.2 Symbols: meaning and use
This manual contains symbols meant to recall the user's attention as regards the safety regulations in force
and maintenance operations. Meaning of the symbols:
Danger - Warning
This symbol is used in the safety warnings or instructions, or in any case when there is a potential
hazard likely to cause injury.
Caution
This symbol is used for safety-related warnings or precautions meant to prevent damage to the electric
panel or other important messages to the operator.
Important
This symbol is used in safety-related warnings and compels the user to carefully read this manual.

2
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
1.0 INTRODUCTION
QE SEPCOM SIP BED EASY
The electric panel is intended for use by properly trained personnel: the installation must be designed and car-
ried out only by qualied technicians.
Caution
Inaccurate installation or use can cause serious damage to the electric panel, to the user and to the
persons involved.
Please be reminded that the regulations in force in the country of installation are compulsory; in case of several
legal indications, always refer to the more binding requirements.
The product has been designed and manufactured in compliance with safety regulations, for use in ordinary,
unclassied environments.
To avoid damage to property and persons, it is recommended to use all the necessary precautions and adhere
to the highest professional standards.
The dimensions of the panel for the estimation of the thermal power loss have been calculated assuming there
are no other heat sources nearby.
If installed in a space where other panels have been installed, ensure a sucient distance that allows heat
dissipation.
The electric panel has to be used only for the intended purpose, all other uses are considered improper and
therefore dangerous.
Caution
The manual shall be kept in a place accessible to operators and it has to be well preserved.
Before start-up or maintenance operations, operators have to read the manual carefully, paying a special at-
tention to messages highlighted with the danger warning symbol: they contain instructions needed for a correct
operation of the electric panel under maximum safety conditions.
Moreover, this allows verifying the regularity and frequency of the check-ups carried out.
Caution
The manufacturer is not liable for the improper functioning of the panel or any damage caused by it,
in case it is tampered with, modied, if operated improperly or inconsistently with other provisions
contained by the present manual.
The Manufacturer shall not be held responsible for possible inaccuracies contained in this instruction manual,
if due to printing or transcription errors. The Manufacturer reserves the right to bring necessary or useful modi-
cations to the product, without aecting its basic features.
1.3 General features

3
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
1.0 INTRODUCTION
QE SEPCOM SIP BED EASY
The SEPCOM®SIP BED Easy control panel manages the operating logics of the system consisting of a screw
press separator and a pneumatic presser, in coordination with other users part of a conventional separation
system, such as feeding pump, agitator and level sensors.
The SEPCOM®SIP BED Easy control panel allows keeping constant drying degree of the separated solids to
be by modulating the thrust of the pneumatic presser on the solids outlet, depending on the current absorption
set for the separator motor: the higher the absorption setpoint, the higher the drying degree of the separated
solids.
Important
The SEPCOM®SIP BED Easy of the control panel version controls directly only the pneumatic presser
and the absorption of the separator. The 24 Vdc power supply of the control panel, as well as the
power supply of all electric motors, must be provided from a main electrical panel previously installed
or already tted on the plant. The levels as well as the other users connected to a separation system
(pump and agitator) can only be managed from the main control panel interfaced with the SEPCOM®
SIP BED Easy.
1.4 Operating principle
Avoid shocks and tilting the equipment.
Observe safety distances from the lifting mean.
Prevent the presence of persons under suspended loads or within the operation area of the lifting equipment
used.
Keep the load as low as possible to ensure stability and greater visibility for the operator.
On using the lifting means (hooks, ropes, bands etc.) ensure they are in good condition and suit the safety
regulations in force.
Important
The terms “equipment”, “control panel” used in this manual refer to the same machine.
The separator, control panel and air compressor (that feeds the pneumatic presser) are to be consid-
ered as a machine and must, therefore, bear the CE marking.
It is forbidden to start the control panel unless the machine/plant in which it is to be installed has been
declared compliant with the Directive 2006/42/EC and further modications.
1.5 Lifting and shipment

4
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
1.0 INTRODUCTION
QE SEPCOM SIP BED EASY
1.6 Storage and dismantling
On storing, do not stack other items on top of the device, to avoid damaging it as well as the risk of accidental
falls.
Ensure the integrity of mechanical and electrical engineering parts of the electric panel during shipping.
The weight and overall dimensions are indicated on the ID plate of the panel and inside the documentation
enclosed to it.
On receiving the control panel, carry out a visual inspection to ensure no damages have occurred during ship-
ping and that the data on the plate correspond to those present on the acknowledgement of order.
If the panel is not to be immediately installed but it has to be stored, take the necessary some precautions not
to damage the outer casing and the internal electrical components.
Caution
Store the panel packed, indoor, covered and protected from atmospheric agents and animals; the rec-
ommended moisture level should be between 30 and 75% and the temperature between - 25 °C and +
55 °C.
Caution
At the end of it life or in the case of demolition, the device shall be disposed of according to the laws
in force in the country of destination.

5
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
1.0 INTRODUCTION
QE SEPCOM SIP BED EASY
Danger - Warning
It is forbidden carrying out commissioning, maintenance operations, repairs or modications unless
entrusted to specialized personnel, under precise instructions.
It is recommended to check the electric panel for integrity after unpacking; do not use it in case of any doubts.
Before starting the installation make sure the following piece of information were checked and followed:
a) all installation operations are carried out by qualied personnel and the safety standards of the country of
installation were observed;
b) make sure that the data contained on the ID plate placed on the panel match to the plant to which it is inte-
grated; check the power, voltage, current and frequency;
c) for the electrical connection follow the wiring diagram;
d) check and provide the recommended cross section values of the power supply lines;
e) make sure the earthing is always connected to the distribution system and consistent with the regulations
in force in the country of use;
f) make sure that the auxiliary circuit conductors are connected correctly by checking their polarity.
Danger - Warning
Prior to use, check the direction of rotation of all equipment and ensure the safety of personnel during
the examination.
Install the control panel on the basis of the protection degree; it is recommended to use cable having the same
features in order to avoid a downgrading of the protection.
Danger - Warning
Electric panels must be perfectly installed; any fault, change made to the initial project conditions, the
intervention of external agents such as plants, animals, dust, mould or the like must be removed; then
restore to default values.

6
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
2.0 APPLICATIONS
QE SEPCOM SIP BED EASY
2.1 Safety distances
Danger - Warning
The control panel shall be placed at a safe distance from sources of heat, fuel depots, from ammable
materials, chemicals.
In order to limit potentially dangerous situations, isolate the area surrounding the control panel and
preclude the possibility that unauthorized persons approaches the area.
Although the devices are manufactured in compliance with the regulations on electromagnetic com-
patibility, it is recommended to NOT install the panel near equipment which represent a sources of
emissions.
Particular attention must be paid during assembly phase of the control panel to avoid the falling external ele-
ments, such as metal shavings or other materials that could damage or block the movement of the electric
components.
Danger - Warning
Incorrect installation and electrical connections can cause serious damage to persons, the equipment,
the electric panel and to plants connected thereto.
Important
The installer must issue a declaration of conformity regarding the installation of the control panel at
the end of the installation operations.
2.2 Emergency stop
Important
The control panel (located to the left) must be equipped with suitable red mushroom-shaped, stay-put
Emergency button to enable the shut-down when completely pushed.
The emergency stop has to be used only in case of danger conditions and therefore the equipment must be
immediately shut down.
Pushing one of the emergency stop buttons causes the hardware cutting of the controls and the ashing of the
red EMERGENCY led.
Prior to restoring of the operation after an emergency stop, it is necessary to:
- Remove the problem that caused the emergency stop.
- Unblock the emergency buttons which are of mechanical hold-in type.
- Push the reset button (STOP CYCLE) and ensure the EMERGENCY indicator light comes o.
- Repeat the start procedure of the machine.

7
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
2.0 APPLICATIONS
QE SEPCOM SIP BED EASY
2.3 Protection degree
In order to protect the control panel from indirect contact, overload and short circuit, it is the responsibility of
the installer to provide a protection device upstream the line, having the features and values suitable to the
installation point.
In order for the properly sizing of the protection device, check the value expressed in kA of the lcc found in the
documentation of the control panel.
Caution
It is the installer's responsibility to make sure the electrical load connected and the current values do
not exceed the designed value of the control panel
It is recommended to provide the appropriate devices for the protection of circuits fed directly from the line
voltage from overvoltage due to lightning or other particular events.
Important
Never exceed the wires length over 50 m between the control panel and end user.
Caution
Evaluate if further emergency buttons are required near the utilities.
It is recommended to include at least one emergency stop button with safety key to be used during
equipment maintenance.

8
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
2.0 APPLICATIONS
QE SEPCOM SIP BED EASY
2.4 Safety switches
Caution
When required by the nature of the equipment connected to the control panel, it is necessary to pro-
vide specic safety switches.
On opening a safety device, all dangerous movements of the equipment need to be stopped and the equip-
ment must be prevented from accidentally getting restarted.
If so, no safety device can be by-passed or tampered with.
Some applications require the movable guards to remain blocked during a hazardous production cycle.
Caution
On choosing the number and features of the switches to be provided (magnetic sensors, mechanical
interlocks, ..) take into account the environment in which the machine operates as the switch have to
ensure an appropriate protection degree (IP).
2.5 Technical data
Supply voltage [Vdc] 24
No. of phases 2
Maximum rated operating current [A] 2
Protection degree IP65
Danger - Warning
Make sure the micro-switches are correctly positioned and locked.
Check that the electrical drawing regards the components on which the operations are carried out.
Check that the voltage matches the one envisaged for the operation.
Important
Check that the voltage value of the motors stays between ranges +/- 10% of the rated value.
Check that the movements matches the indications on the related buttons.
Caution
Provide the necessary protection from lightning during operation and the related devices to ground
any electrical discharge.

9
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
2.0 APPLICATIONS
QE SEPCOM SIP BED EASY
2.6 Mandatory electrical connections
The SEPCOM® SIP BED Easy control panel can be installed in two congurations:
MASTER = the SIP BED Easy control panel manages the plant users via the customer’s main control panel.
SLAVE = the SIP BED Easy control panel manages only the pneumatic counter-pressure system.
For more details check the wiring diagram, sheet 91.
Important
For the connection of the control panel to the three-phased motor of the separator, it is necessary to
drill holes in the at the bottom of the control panel box to allow the cable to go in and then out. The
holes must be adequately protected with cable glands that follow local standards, to prevent dust and
moisture from entering the control panel. This operation must be carried out by trained technical per-
sonnel only.

10
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
2.0 APPLICATIONS
QE SEPCOM SIP BED EASY
2.7 Pneumatic connection
The pressure switch box is supplied already connected to the control panel, which powers it. On the other
hand, the air hoses for pressure regulation in the presser cylinders must be connected.
Item Description
APID controller
BAir lter
1Air outlet towards the pneumatic presser
2Air inlet from the compressor
3Air outlet from the PID controller
4Condensation drain lter
5PID controller power cable input
6Pressure switch power cable input

11
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
QE SEPCOM SIP BED EASY
3.0 COMMISSIONING
Danger - Warning
It is forbidden carrying out commissioning, maintenance operations, repairs or modications unless
entrusted to specialized personnel, under precise instructions. All operations must be performed in
accordance with the safety regulations.
Caution
Do not disassemble or force electrical components when the panel is powered.
Danger - Warning
Check the suitability of the supporting plane as well as the support structures on which the control
panel is to be installed. Check the suitability of manoeuvring space, paths, corridors, passageways
and escape routes around the equipment to avoid situations that could lead to falling hazards.
Important
Check the suitability and the proper operation of the electrical system: power line, power plug, distri-
bution board, safety switches meant to cut o the short circuit current, cross-section, power, length of
the power cable and of the earthing system (CEI EN 60204 -1; CEI EN 61439-2).

12
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
4.1 How to use and set the operator panel
no. Description
1PLC touchscreen panel
2Emergency button
3Power on white indicator light
4General alarm red warning light
5Two-position AUTOMATIC/ MANUAL switch
6START and STOP/RESET cycle button
7Pressure switch box
4.1.1 FIRST START-UP OF THE CONTROL PANEL
Once the control panel has been connected according to the indications given in the attached wiring diagram,
it is possible to start it up the rst time. Follow the procedure below (refer to the safety instructions before car-
rying out these manoeuvres):
1. Push the STOP cycle button.
2. Push the START cycle button.
If the emergency mushroom-shaped button is pressed, follow the same procedure described above.

13
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
4.1.2 DESCRIPTION OF THE MAIN CONTROLS
Using the operator panel, the operator can select, ll in and set the various data necessary for a correct opera-
tion. He can also check on the status of users and see when maintenance must be performed.
no. Control
1Access to manual operation
2Access to automatic operation
3Access to operator settings
4Access to technical settings
5Access to the alarms screen
These buttons control dierent functions, depending on the page shown on the display. Their use is enabled by
entering user name and passwords, which are divided into end-user (CLIENT) and Technical User (ADMIN).
4.1.2.1 Manual cycle
Use this key (no password required) to intervene on each user connected to the control panel to carry out an
operation test. Pressing this key takes you to the following page:
1
2
3
4
5

14
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
no. Control
1Change page (main menu)
2Absorption detected [Amps]
3Pneumatic system pressure [bar]
4Separator ON/OFF status
5Active alarms
6Date
7Time
8Agitator ON/OFF status
9Pump ON/OFF status
Tap the buttons on the users side to start the corresponding electric motor:
Tap the separator image to start the separator; the indicator light on the side
will turn from dark green (o) to bright green (on).
Tap the pump image to start the pump; the indicator light on the side changes
from dark green (o) to bright green (on).
Press the agitator icon to start the agitator; the indicator light on the side
changes from dark green (o) to bright green (on); the AGITATOR option will
also be lit (check the screen 5 shown at page 23).

15
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
4.1.2.2 Automatic cycle
no. Control
1Change page (client settings)
2Cycle status
3Change page (main menu)
4Absorption set [Amps]
5Absorption detected [Amps]
6Separator ON/OFF status
7Pneumatic system pressure [bar]
8Timer progress (minutes of operation)
9Active alarms
10 Date
11 Time
12 Timer setting (running minutes)
13 Total operation hours of the plant
14 Minimum level of the tank
15 Maximum level of the tank
16 Pump and agitator ON/OFF status
Use this button (no password required) to enter the automatic operation mode:

16
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
On the main screen press the “change page” icon at the top is right side to access the maintenance page;
here you can check the current operating hours of each user and the maximum operating hours after which
maintenance is required for the separator (general check), screen, grease nipple.
Press again the “change page” icon at the top is right side to enter the maintenance page; here you can
check the current operating hours of each user and the maximum operating hours after which maintenance is
required for the screw, pump and agitator.
Use the arrow to go back to the previous page.
Check the page 20 for default values.
When the components are managed in automatic mode, the use can check the maintenance status and select
the language Only trained personnel authorized by WAM can access the maintenance and settings menu.
If you have selected the option management by level (check screen 5, page 23): when the max. tank level
is active, the users will be activated according to the logics of the plant.
When the min. tank level is active, the users are stopped according to the logics of the plant and stay in stand-
by until a the max. level is reached again.
If you have selected the option external input management (check screen 5, page 23): the users will be
activated according to the logics of the plant on the basis of the status of the external input (PRESENT=ON
ABSENT=OFF).

17
2
SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
4.1.3 SETTINGS
The settings are essential for the correct operation of the machine; they are divided into:
• Operator settings, meant to modify the separator absorption;
• Technician settings, meant to modify all settings of the system (trained personnel required).
By default, the main menu looks like in picture below, with THE OPERATOR SETTINGS and TECHNICIAN
SETTINGS keys o:
To access the settings you need to rst log in using the credentials provided by the Manufacturer.
4.1.3.1 Access to the settings
1) Tap the “OPERATOR SETTINGS” or “TECHNICIAN SETTINGS” key; the user name and password entry
window opens automatically.
2) Tap the “Name” eld and type your user name: CLIENT for access to operator settings or ADMIN for full ac-
cess to technician and operator settings. Tap Enter to conrm.
Table of contents