Wavecom TNT+ User manual

REVISION 1.11 February 2005
Ph: (08) 8331 8892 Ph: (07) 3274 2466
Int: (+61) 8 8331 8892 Int: (+61) 7 3274 2466
www.wavecom.com.au
www.nesco.com.au
Australian made to
comply with the
requirements of the
Standard AS/NZS 3760

Page 2
Accessories Supplied
(With the Range of TnT Portable Appliance Testers)
•Portable Appliance Tester Instruction Manual
•Manufacturers Calibration Certificate
•IEC Lead
•Earth Lead with Alligator Clip
•Soft Carry Case
Manufacturers Recommendations
(For the Range of TnT Portable Appliance Testers)
Calibration:
The manufacturer recommends a routine calibration verification of readings
for determining the accuracy of readings on a 12 Monthly basis.

Page 3
Index
Accessories Supplied 2
Manufacturers Reccomendations 2
Index 3
IMPORTANT INFORMATION:
Safety Warning 4
The TnT Portable Appliance Tester (Diagram) 5
Competent Person 6
Disclaimer & Limited Warranty 6
TECHNICAL INFORMATION:
Class 1 (Earthed Appliance) Construction 7
Class 2 (D/Insulated) Construction 8
Testing of Electrical Equipment 9-10
To Change Test Voltage (250/500VDC Select) 10
INTEGRATED TESTS:
SUPPLY MAINS TEST 11
NCNT TEST 12
FIRST TEST:
VISUAL INSPECTION TEST 13
CHAPTER 1 – TnT Portable Appliance Tester Instructions:
TnT Test Function Flow Chart 14
EARTHED APPLIANCE TEST 15
DOUBLE INSULATION TEST 16
EXT LEAD TEST 17
CHAPTER 2 - TnT-el Portable Appliance Tester Instructions:
TnT-el Test Function Flow Chart 18
TESTS Common to ALL MODELS 19
LEAKAGE TEST 20-21
CHAPTER 3 – TnT+ Portable Appliance Tester Instructions:
TnT+ Test Function Flow Chart 22
TESTS Common to ALL MODELS 23
POWER TEST 24-25
RCD TEST 26-30
Specifications for the TnT, Tnt-el & TnT+ 31
Optional Accessories 32
Other Relevant Authorities 33
[Please note: Specific PAT Tests are noted in blue text]

Page 4
!
Safety Warning
When using any electrical appliance SAFETY must always be observed.
Testing appliances is no exception and in fact MORE care must be
taken to ensure personal safety is met.
Although the TnT range of products has been designed to meet
stringent requirements, no person can be completely protected against
the consequences of the incorrect use of an electrical device.
We advise that appliance testing should be conducted by a competent
and suitably trained person.
For maximum safety, always ensure that the following advice is
followed;
•The equipment being tested is in good repair.
•All user instructions are followed.
•Double check power supply connections (LEDs).
•Always use specified fuses and protection devices.
•Do not use leads that require repair or are damaged.
•If you are unsure, call a Licensed Engineer/Electrician.

Page 5
The TnT Portable Appliance Tester
(Diagram)
[Diagram shown is a sample only and may not be exact to each specific model of TnT Appliance Tester]
Display
Test Function F1
Test Function F2
Test Function F3
These buttons are NOT
IN USE & are reserved
for future functions
Supply
Indicator Lights
IEC Socket
Fuse
Power Lead
Device Under Test (DUT) Socket
Return/Enter Button

Page 6
!
Competent Person
To ensure that all electrical equipment or devices that are used to perform specific tasks,
are inspected and tested and tagged correctly, regulations require that a competent
person such as a Licensed Electrician be employed to perform the required tests.
A person competent to undertake Inspection and Testing of electrical equipment must
therefore have:
1. Knowledge and practical experience of electricity and its hazards.
2. A clear understanding of precautions to avoid danger.
3. The ability to recognise, at all times, whether it is safe for work to continue or not.
4. The ability to carry out visual examinations of electrical equipment.
5. The ability to distinguish between electrical equipment that is double insulated and
equipment that is earthed as well as being able to identify the
appropriate test for
each type.
6. The competency to carry out the Earthing Continuity, Insulation Resistance or
Leakage Test and RCD tests on electrical equipment safely.
7. The knowledge of how to use the relevant testing instruments, interpret and record
the results for compliance with the Standard/Workplace requirements.
8. The knowledge to be able to correctly recommend the frequency of testing
required.
Due to the potential hazards of electrical testing all care must be taken.
Disclaimer
LIMITED Warranty
The Manufacturer warrants its products against defects in materials and workmanship for a
period of 12 months from the date of purchase. During the warranty period, the manufacturer
will repair (or at its option replace at no charge) the product that proves to be defective. This
warranty does not apply if the product has been damaged by accident, abuse, misuse or miss-
application or as a result of service or modification by anyone other than Electromate TnT.
Electromate TnT product range of devices or its’ manufacturer IS NOT RESPONSIBLE FOR
INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE BREACH OF
ANY EXPRESS OR IMPLIED WARRANTY, INCLUDING DAMAGE TO PROPERTY AND TO
THE EXTENT PERMITTED BY LAW, DAMAGES FOR PERSONAL INJURY. The Distributors
of this product cannot assume liability or responsibility for any loss or damage resulting from
the use of this device.
Electromate TnT manufacturer reserves the right to discontinue models, change specification,
price or design, at any time without notice or obligation.

Page 7
Technical Information
CLASS 1 (Earthed Appliance) CONSTRUCTION
(Single basic insulated and protectively earthed equipment)
This type of product design provides two safety barriers between all live conductors at
dangerous voltages and the equipment user.
The provision of basic insulation between exposed metal parts and live parts is the first
barrier to provide basic protection against electric shock.
The second safety barrier is by the connection of exposed (accessible) conductive (metal)
parts to the protective earthing conductor (earth wire) in the fixed wiring of the
device/Installation.
The protective earthing terminal of the equipment must be marked with the word "earth" or
the symbol "E" or the symbol for Earth Terminal or Protective
Conductor Terminal.
To perform this test a continuous earth loop must be made between the exposed
conductive material (metal) and the TnT appliance tester. This is done by means of
connecting the earth lead with the crocodile clip/probe attached to a GOOD earth point
(paint & coatings will not provide effective connections) and the DUT (Device Under Test)
plugged into the TnT appliance testers’ DUT socket. [as shown in the above picture]. The
Maximum allowable limit is 1.0Ω(ohm).
1

Page 8
1M
Technical Information
Continued
CLASS 2 (Double Insulated) CONSTRUCTION
(Double insulated equipment)
This method of construction employs two safety barriers comprising two layers of
insulation between dangerous voltages and the user of the equipment.
The first layer of insulation is formed around the live conductor and is termed ‘the
Functional Insulation’.
The second layer of insulation is termed ‘the Supplementary Insulation’. In Class II
equipment, protection against electric shock does not rely on
basic insulation only, but has additional supplementary
insulation such as double insulation or reinforced insulation
provided, there being no reliance on precautions in the fixed
wiring of installation.
Class II equipment is marked with the words "DOUBLE
INSULATION" or the symbol
For double insulated under Safety Symbols:
Note 1 – Double Insulation is insulation comprising both basic and supplementary
insulation.
Note 2 – Reinforced Insulation is a single insulation system with a degree of protection
against electric shock, which is equivalent to double insulation.

Page 9
Technical Information
Continued
Testing of Electrical Equipment
Many testing personnel have some reservations in testing sensitive, electronic equipment
using a 500V DC insulation test. There is a perceived fear of causing internal damage
from over voltage. With the introduction on the TnT Range of appliance testers, these
concerns are alleviated.
The TnT Range of electrical portable appliance testers are safe to test electronic
equipment as the tests are carried from Active-Neutral (shorted by a relay inside the
tester) to Earth. No dangerous voltages pass through in this mode to the internal
components of the DUT (Device Under Test). If these tests are done using an Insulation
Tester only and the user tests Active to Neutral, this would be a cause of potential
damage, this is why the TnT product range is far safer to use.
Some changes may be required in certain configurations where fitted surge protection
devices (MOV's) in the DUT may cause a failed test result. Applying 500V in this these
situations can cause the surge protection devices to trip, therefore conducting the applied
voltage to earth, thus showing a failure of insulation. In these instances the test voltage
should be changed to 250V then retest. If DUT still fails, check with the DUT Operators
Manual or an electrician. [Refer to page 13 for details - ‘Double Insulation Test’
250/500VDC to change test voltage].
Under these circumstances, it would be difficult for any damage to occur to either the
surge protection device or the DUT, as there is insufficient current generated by the TnT-el
appliance tester.
Leakage Test:
If there are any doubts with insulation testing of the equipment, the standard
(AS/NZ3760 since 2001) allows for an alternative test method. A Leakage Test can be
performed instead. (The TnT-el & TnT+ models are designed to perform these tests).
NOTE: 10Amps MAXIMUM Resistive Load only (Standard TnT-el & TnT+ units).
A Leakage Test applies power to the Device Under Test (DUT) and measures the
imbalance of leakage current from the DUT between the active and neutral conductors.
The leakage is tested to the limits specified in the standard and a Pass/Fail result as well
as a digital reading is provided to ensure that the user gains as much information as
necessary.
Earth Continuity Test:
The TnT-el conducts earth continuity tests at Approx 200mA. Continuity tests at
higher currents are not required and are not recommended on certain
equipment as this can cause severe damage or premature failure to the DUT (as per
AS/NZ3760).

Page 10
Technical Information
Continued
Testing of Electrical Equipment
3 Phase Testing:
3 Phase appliances can be tested by the TnT, TnT-el, TnT+ or the TnT-3PL appliance
tester. This test is carried out by using the adaptor connection sockets. As the insulation
tests are from Phase to Earth, only a 500V insulation test is required. These adaptors can
be made by your electrician or purchased as an accessory. [See ‘Optional Accessories’ on
page 18 for details - when ordering please state plug configuration of 3 phase plug. E.G.
5 pin Clipsal 56 series 20A].
CAUTION: Ensure that these adaptors are used only for appliance testing.
To Change Test Voltage
(250/500 VDC Select - To Change the Insulation Test Voltage on all models)
Procedure:
Step 1: Hold down the Return/Enter Key
Step 2:
Press the F2 Key
(F2 function – Note screen flashes)
Step 3:
For 250v – Press the F3 Key
For 500v – Press the Return/Enter Key
Finish: The display will confirm the change and return to the
Main Menu automatically. The desired voltage has
now been selected.
TO CHANGE VOLTAGE BACK, REFER TO STEP 1.
Please Note:
1. In earlier models the Return/Enter Key may need to be pressed 3 times to change
Voltages.
2. The TnT will automatically default to 500v when restarted.

Page 11
Integrated Tests
Information
SUPPLY MAINS TEST
A-N, A-E
If the N-E (red) light is on and you need to conduct load/leakage tests
DO NOT CONTINUE. If you are carrying out standard Insulation and
Earth Bond tests, it is generally safe to continue.
This light will glow if a voltage difference lies between the neutral and
the earth, or if no earth is connected to the TnT-el supply. (If working
with a generator or inverter, this is most likely to occur and you may
need to consult an electrician before proceeding).
If both the A-E & A-N (green) lights are on but not the N-E (red);
Mains Supply is OK.
Continue to Test.
If both of the N-E (red) & A-E (green) lights are on,
Consult an Electrician, as there is a fault with the Mains Supply.
N
-
E
A
-
E
A
-
N
A
-
E
N
-
E
A
-
N
The Supply Mains TEST checks the Polarity & Connectivit
y of the mains
supply by LED’s (see below). This test is also a part of all of the testing
functions of this unit.

Page 12
Integrated Tests
Information
NCNT TEST
(No Connection No Test)
This test function ensures that the Device Under Test (DUT) is plugged into the TnT
appliance tester and that it is switched on.
If the DUT is not plugged in and the TnT appliance tester detects that no DUT is present,
plug in the DUT to continue the test. Confirm or ‘QUIT’ to return to the main menu.
If for some reason the NCNT circuit does not detect the DUT but it is actually plugged in
and turned on, the operator will need to override the TnT appliance tester to continue the
test.
To do this - press the F3 Key.
With an emphasis in the standard AS/NZ3760 for carrying out the live testing the TnT
appliance tester will indicate for you to check if the DUT is plugged in and switched on. If
the DUT is not plugged in and/or recognised, it may require a live test therefore making it
necessary for the operator to carry out a full functional Leakage Test (TnT-el & TnT+
appliance tester models only).
This function is to ensure that correct testing procedures are carried out in accordance
with the Standard AS/NZ3760.
TO NOTE:
i. When using 3-Phase adaptors the NCNT function will need to be over ridden by
pressing the ‘OK’ key prior to the TnT appliance tester performing the assigned
test.
Some single Phase appliances controlled by contactors will require manual over
ride also. In some instances holding the ‘ON’ button of the DUT will enable the
NCNT function to work normally.
The TnT appliance tester ensures that the De
vice Under Test (DUT) is
plugged in and switched on. This test is also a part of all of the testing
functions of this unit.

Page 13
Visual Inspection (FIRST TEST)
Information
In regard to the Device Under Test (DUT), please ensure that;
1. There is no damage or component defect to the accessories, plugs, outlet sockets
or connectors (physical).
2. There are no cracks &/or abrasions.
3. There are no exposed inner cores or conductors (flexible) and that the supply cords
are not twisted or distorted.
4. Any Fuse / Over load protection components (if fitted) are checked.
5. All labels, markings and warning indicators (of the maximum load to be connected
to the device) are legible and intact.
6. The insulation is not damaged in any way i.e. melted, cuts or abrasions. There are
no iron filings in the insulation. There is no insulation tape on the lead.
7. Any flexible cords and/or leads are effectively anchored (glands and grommets
intact).
8. All covers/guard are in place and secure as intended by the supplier/manufacturer.
9. All safety devices and systems are in good working order. (ie. overload latches &
buttons).
10.No dust &/or dirt obstructs any exhausts or ventilation outlets.
11.All controls are working properly and are secure and aligned.
Important:
IF RESULT IS A FAIL
If a Device Under Test (DUT) fails any
of the above, it should be deemed to have
FAILED the Visual Test, and therefore no other tests need be performed. If this is
the case the DUT should be tagged with a danger tag and removed from service.
It is recommended by the manufacturer a
nd distributor of this product that if a
DUT has failed a test it SHOULD NOT BE RETURNED TO SERVICE.
To do so
would be considered unsafe.
THIS TEST IS TO OCCUR BEFORE ANY OTHER TEST
IS CARRIED OUT USING ANY OF THE RANGE OF
TnT APPLIANCE TESTERS.

Page 14
Chapter 1 – TnT Portable Appliance
Part No: WCM-TNT
Test Instructions
TnT Test Function Flow Chart
Main Menu 1
F1 Earth Test
F2 D/Ins Test
F 3Ext Lead Test
F1 Earth Test
Supply Mains Test
NCNT Test
Earth Bond Test
Insulation Test
Results Summary
F2 D/Ins Test
Supply Mains Test
NCNT Test
Double Ins Test
Results Summary
F3 Ext Lead Test
Supply Mains Test
Earth Bond Test
Insulation Test
Continuity & Polarity
Test
Results Summary
Please note:
Menu 1 is
common to all models
[TnT, TnT-el & TnT+]

Page 15
Chapter 1 – TnT Portable Appliance
Test Instructions
EARTHED APPLIANCE TEST
Menu 1
Note: 250v insulation testing applies to Class 1 appliances if selected [refer to page 10 for details -
250/500VDC to change test voltage].
PROCEDURE:
1. Complete a VISUAL INSPECTION on the DUT (Device Under Test)
[refer to page 13 for details – ‘Visual Inspection’].
IF THE DUT PASSED THE ‘VISUAL INSPECTION’, CONTINUE WITH THE FOLLOWING
INSTRUCTIONS [if not, refer to page 13 ’IF RESULT IS A FAIL’ ]:
2. Plug DUT into the DUT Socket.
3. Connect Earth Clip to any exposed metal on DUT.
4. Press the F1 key and wait for results (Ensure that the DUT’s Mains
switch is ON).
RESULTS ARE DISPLAYED
5. Read the result and record appropriately.
6. Unplug the DUT.
7. Press the Enter key to return to the Main Menu.
IF THE RESULT OF THE TEST WAS A ‘PASS’ - Tag the DUT with the appropriate tag,
including ‘Next test Due’ date and return to service.
IF THE RESULT OF THE TEST WAS A ‘FAIL’ - Tag the DUT with a DANGER TAG AND
REMOVE THE DUT FROM SERVICE.
In some situations if the DUT is labelled with “Surge Protection Fitted” or if it is electronic and fails, conduct a
250V-insulation test. Should it still fail, remove it from service. [refer to page 10 for details - 250/500VDC to
change test voltage]
PLEASE NOTE: ENSURE THAT THE DUT TO BE TESTED IS ISOLATED FROM ANY POTENTIAL
GROUND LOOP.
The EARTHED APPLIANCE TEST completes the following sequence as part of its testing procedure:
1. Integrated SUPPLY MAINS TEST
[see page 11 for details]
2. Integrated NCNT TEST (APPLIANCE)
[see page 12 for details]
3.
EARTH BOND TEST
(@200ma)
:200Ma Test Current. Pass Level LESS than 1 Ω
ΩΩ
Ω
4. INSULATION TEST (@ 250v or 500v) :Pass Level GREATER than 1M Ω
ΩΩ
Ω
For Earthed Appliances CLASS 1
PLEASE NOTE: A VISUAL INSPECTION MUST BE CARRIED OUT
BEFORE ANY OTHER TESTS.
[refer to page 13 for more details]

Page 16
Chapter 1 – TnT Portable Appliance
Test Instructions
DOUBLE INSULATION TEST
Menu 1
PROCEDURE:
1. Complete a VISUAL INSPECTION on the DUT (Device Under Test)
[refer to page 13 for details – ‘Visual Inspection’].
IF THE DUT PASSED THE ‘VISUAL INSPECTION’, CONTINUE WITH THE FOLLOWING
INSTRUCTIONS [if not, refer to page 13 ’IF RESULT IS A FAIL’]:
2. Plug DUT into the DUT Socket.
3. Connect Earth clip to any exposed metal on DUT (if any, or device can be wrapped
in foil or use metal mesh braid [Part No: TnT-ES 500]
4. Press the F2 key and wait for results (Ensure that the DUT’s Mains switch is ON).
RESULTS ARE DISPLAYED
5. Read the result and record appropriately.
6. Unplug the DUT.
7. Press the Enter key to return to the Main Menu.
IF THE RESULT OF THE TEST WAS A ‘PASS’ - Tag the DUT with the appropriate
tag, including ‘Next test Due’ date and return to service.
IF THE RESULT OF THE TEST WAS A ‘FAIL’ - Tag the DUT with a DANGER TAG AND
REMOVE THE DUT FROM SERVICE.
In some situations if the DUT is labelled with “Surge Protection Fitted” or if it is electronic and fails, conduct a
250V-insulation test. Should it still fail, remove it from service. [refer to page 10 for details - 250/500VDC to
change test voltage]
For Double Insulated Appliances CLASS 2
The DOUBLE INSULATION TEST
completes the following sequence as part of its testing procedure:
1. Integrated SUPPLY MAINS TEST
[see page 11 for details]
2. Integrated NCNT TEST (APPLIANCE)
[see page 12 for details]
3. DOUBLE INSULATION TEST (@ 250v or 500v)
Pass Level GREATER than 1 M Ω
ΩΩ
Ω
PLEASE NOTE: A VISUAL INSPECTION MUST BE CARRIED OUT
BEFORE ANY OTHER TESTS.
[refer to page 13 for more details]

Page 17
Chapter 1 – TnT Portable Appliance
Test Instructions
EXT LEAD TEST
Menu 1
PROCEDURE:
1. Complete a VISUAL INSPECTION on the DUT (Device Under Test)
[refer to page 13 for details – ‘Visual Inspection’].
IF THE DUT PASSED THE ‘VISUAL INSPECTION’, CONTINUE WITH THE FOLLOWING
INSTRUCTIONS [if not, refer to page 13 ’IF RESULT IS A FAIL’ ]:
2. Plug in IEC adaptor lead into IEC socket ( Remove Earth lead if inserted - Please
read note below)
3. Plug Male end of Extension lead or Power board into TnT tester DUT
socket
4. Plug IEC adaptor lead into Extension lead /Power board socket.
5. Press the F3 key and wait for results.
RESULTS ARE DISPLAYED
6. Read the result and record appropriately.
7. Unplug the Extension lead /Power board.
8. Press the Enter key to return to the Main Menu.
IF THE RESULT OF THE TEST WAS A ‘PASS’ - Tag the DUT with the appropriate tag,
including ‘Next test Due’ date and return to service.
IF THE RESULT OF THE TEST WAS A ‘FAIL’ - Tag the DUT with a DANGER TAG AND
REMOVE THE DUT FROM SERVICE.
PLEASE NOTE:
1. Extension leads should always be uncoiled before using or testing.
2. Please ensure that the IEC Adaptor & the IEC socket are inserted firmly or it may
result in a continuity/polarity fail.
[Illustration above is for demonstration only]
The Ext. Lead TEST completes the following sequence as part of its
comprehensive testing procedure:
1. Integrated SUPPLY MAINS TEST
[see page 11 for details]
2.
EARTH BOND TEST
(@200ma)
:200Ma Test Current. Pass Level LESS than 1 Ω
ΩΩ
Ω
3.
INSULATION TEST (@ 250v or 500v) Pass Level GREATER than 1M Ω
ΩΩ
Ω
4. CONTINUITY & POLARITY TEST 250VAC Checks continuity & polarity of leads
For Extensions Lead/Power Board
& IEC Leads
PLEASE NOTE: A VISUAL INSPECTION MUST B
E CARRIED OUT
BEFORE ANY OTHER TESTS.
[refer to page 13 for more details]

Page 18
Chapter 2 - TnT-el Portable Appliance
Part No: WCM-TNT-EL
Test Instructions
TnT-el Test Function Flow Chart
Main Menu 1
F1 Earth Test
F2 D/Ins Test
F 3Ext Lead Test
Menu 2
F1Earthed Leakage Test
F2 D/Ins Leakage Test
F3 RCD Appliance
Leakage Test
F1 Earthed Leakage Test
Mains Supply Test
NCNT Test
Earth Bond Test
Earth Leakage (5mA)
Results Summary
F1 Earth Test
Mains Supply Test
NCNT Test
Earth Bond Test
Insulation Test
Results Summary
F2 D/Ins Test
Mains Supply Test
NCNT Test
Double Ins Test
Results Summary
F3 Ext Lead Test
Mains Supply Test
Earth Bond Test
Insulation Test
Continuity & Polarity
Test
Results Summary
RCD Appliance Leakage Test
Mains Supply Test
NCNT Test
Earth Bond Test
Earth Leakage (2.5mA)
Results Summary
D/Ins Leakage Test
Mains Supply Test
NCNT Test
Earth Leakage (1mA)
Results Summary
Please note:
Menu 1 is
common to all models
[TnT, TnT-el & TnT+]

Page 19
Chapter 2 - TnT-el Portable Appliance
Test Instructions
TESTS COMMON TO ALL MODELS
Menu 1
EARTHED APPLIANCE TEST [refer pg 15]
DOUBLE INSULATION TEST [refer pg 16]
EXT LEAD TEST [refer pg 17]
Please note:
Menu 1 is
common to all models
[TnT, TnT-el & TnT+]

Page 20
Chapter 2 - TnT-el Portable Appliance
Test Instructions
LEAKAGE TEST
Menu 2
This test determines errors of leakage not otherwise detected in a normal insulation test.
If there are any doubts with insulation testing of the equipment, the Standard (AS/NZS
3760 since 2001) allows for a leakage test to be carried out instead. The TnT-el & TnT+
appliance testers have been designed to perform these tests. The Leakage Test applies
power to the Device Under Test (DUT) and measures any imbalance or leakage current.
The leakage is tested to the limits of the class types specified in the Standard AS/NZS
3760 ie. Class 1 = > 5mA as Fail.
The Limit of imbalance measured on the TnT-el appliance tester will read well in excess of
the limits set in mA. However, should the supply circuit be protected by an RCD this
device will trip any where between 10 to 30mA and trip the mains supply switch OFF.
PROCEDURE:
1. Complete a VISUAL INSPECTION on the DUT (Device Under Test)
[refer to page 13 for details – ‘Visual Inspection’].
IF THE DUT PASSED THE ‘VISUAL INSPECTION’, CONTINUE WITH THE FOLLOWING
INSTRUCTIONS [if not, refer to page 13 ’IF RESULT IS A FAIL’]:
2. Press Return Key to view Menu 2.
3. Press a Function Key (as follows) to start the test/s. Press F1, F2 or F3 (depending
on the type of DUT you are testing).
1. F1 Earth Leakage
Limit set to MAXIMUM then 5mA Fail
2. F2 D. Insulated Leakage & Ext leads
Limit set to MAXIMUM than 2.5mA Fail
3. F3 RCD Leakage
CONFIRM SAFE TO CONTINUE? OK/QUIT. IF OK, DEVICE WILL TURN ON.
ENSURE SAFE OPERATION!
RESULTS ARE DISPLAYED
4. Read the result and record appropriately.
5. Unplug the DUT
6. Press the Enter key until you return to the Main Menu.
IF THE RESULT OF THE TEST WAS A ‘PASS’ - Tag the DUT with the appropriate tag,
including ‘Next Test Due’ date and return to service.
IF THE RESULT OF THE TEST WAS A ‘FAIL’ - Tag the DUT with a DANGER TAG AND
REMOVE THE DUT FROM SERVICE.
Note: Test will PASS even if DUT is not plugged in.
The Leakage Test is an alternate method to performing insulation resistance
tests. Leakage testing is a major function of the TnT-el & Tnt+ models
!
PLEASE NOTE: A VISUAL INSPECTION MUST BE CARRIED OUT
BEFORE ANY OTHER TESTS.
[r
efer to page 13 for more details]
This manual suits for next models
2
Table of contents