WDT Granudos 10 Touch User manual

Item No.: --- Language: EN
Operating and Installation instructions
Control Unit
Type GRANUDOS Touch
Operating instructions Part 2: for control unit “Touch”
Part 2, for operating instructions for dosing device:
Granudos 10 Touch, No.: OI SW 002
Granudos 45/100 Touch, No.: OI SW 003

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 2 of 43
Table of contents
1About these instructions / general .......................................................................................................... 4
1.1 Scope of applicability ........................................................................................................................................4
1.2 Target group .................................................................................................................................................... 4
1.3 Symbols used ...................................................................................................................................................4
1.4 Warranty .........................................................................................................................................................5
1.5 Further information..........................................................................................................................................5
1.6 Information regarding support queries.............................................................................................................5
2Safety ...................................................................................................................................................... 6
2.1 Intended use.....................................................................................................................................................6
2.2 Safety notices ................................................................................................................................................... 6
Handling of chemicals, risks to humans and the environment ........................................................................6
Protective measures and rules of conduct ..................................................................................................... 6
3Product description - scope of delivery.................................................................................................... 7
3.1 Scope of delivery / accessories.........................................................................................................................7
3.2 Product description .......................................................................................................................................... 7
Device overview............................................................................................................................................7
3.3 Identification of device / nameplate..................................................................................................................8
3.4 Technical data .................................................................................................................................................. 8
3.5 Transport / storage .........................................................................................................................................8
4Installation ............................................................................................................................................... 9
5Commissioning ........................................................................................................................................ 9
5.1 Commissioning, - comments.............................................................................................................................9
5.2 Commissioning tasks ........................................................................................................................................9
6Operation / service............................................................................................................................... 10
6.1 General ..........................................................................................................................................................10
6.2 Control unit GRANUDOS Touch...................................................................................................................10
Operation display –Automatic operation....................................................................................................10
Start –Delay booster pump and dosing delay ..............................................................................................13
Automatic operation ...................................................................................................................................13
Alarm ..........................................................................................................................................................14
Manual dosing (emergency programme) .....................................................................................................14
6.3 The Main Menu ..............................................................................................................................................14
Main Menu Login.........................................................................................................................................15
Main Menu Settings (overview)...............................................................................................................15
Main Menu Service .................................................................................................................................22
Main Menu Log (event and data logging) ................................................................................................25
Main menu Calibration (Optional for design with buffer tank) ................................................................26
7Maintenance, care, faults ....................................................................................................................... 28
7.1 Device maintenance .......................................................................................................................................28
pH Measurement –pH electrode calibration (optional at use with buffer tank) ..........................................28
Open and close the casing ...........................................................................................................................28
7.2 Trouble-shooting............................................................................................................................................29
8Decommissioning –Storage –Disposal................................................................................................. 32
8.1 General ..........................................................................................................................................................32
8.2 Decommissioning ...........................................................................................................................................32
8.3 Disposal of used parts and operating materials...............................................................................................32
9Documents............................................................................................................................................ 33
9.1 Declaration of conformity ..............................................................................................................................33
9.2 Wiring diagrams.............................................................................................................................................34
Wiring Diagram Power pack Granudos 45/100 and Granudos 10 ............................................................34
Wiring diagram I/O board GRANUDOS 10 ..............................................................................................35
Wiring diagramm Buffer tank GRANUDOS 45/100 ..................................................................................36
Wiring diagram buffer tank GRANUDOS 10 .............................................................................................37
9.3 Commissioning protocol ................................................................................................................................38
9.4 Operation data sheet......................................................................................................................................38
9.5 Maintenance protocol.....................................................................................................................................42
9.6 Spare parts list, wear parts list, consumables..................................................................................................43
10 Appendices............................................................................................................................................ 43

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 3 of 43
Imprint:
All rights reserved
© Copyright by WDT –Werner Dosiertechnik GmbH & Co KG
Edition: see footer
Reproduction of any kind and translation into other languages, even in excerpts, are only permitted with the express
authorisation of the company WDT - Werner Dosiertechnik GmbH & Co. KG.
These operating instructions are an English translation of the original German version by the company WDT.
Responsible for the content:
Co. WDT - Werner Dosiertechnik GmbH & Co. KG
Hettlinger Str. 17
D-86637 Wertingen-Geratshofen
Phone:+49 (0) 82 72 / 9 86 97 –0
Fax:+49 (0) 82 72 / 9 86 97 –19
Email: info@werner-dosiertechnik.de

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 4 of 43
1About these instructions / general
1.1 Scope of applicability
This manual describes the function, Installation, commissioning and operation of the device. Read these
operating instructions carefully prior to operating the device and keep them in close proximity to the device
for immediate use!
1.2 Target group
Only our authorised partners and people who have been trained in the functioning of the device are permitted
to work on the device, provided that they have read and understood these Operating Instructions.
Electrical connection work may only be carried out by appropriately trained specialists!
1.3 Symbols used
This document uses the following types of safety notices as well as general notices:
DANGER!
"DANGER" denotes a safety notice which, if disregarded, may lead to serious or life-threatening injuries, or
serious material damage!
CAUTION!
"CAREFUL" denotes a safety notice which, if disregarded, may lead to injuries, damage to health or material
damage!
ATTENTION!
"ATTENTION" denotes a safety notice which, if disregarded, may lead to material damage!
CORROSIVE!
"Corrosive" denotes a safety notice which, if disregarded when handling chemicals, may lead to injuries or
material damage.
ESD SENSITIVE!
"ESD SENSITIVE" denotes electronic components that may be damaged by electrostatic discharges. The
generally accepted safety precautions for ESD-sensitive devices must be observed when handling the devices!
NOTICE!
A notice denotes information which, if disregarded, may lead to malfunctions.
Tip!
A "Tip" denotes information that may result in improvements in the operating process.
Mandatory sign
Use face shield!
Mandatory sign
Use protective gloves! In accordance with DIN EN 374, protective gloves against chemicals and
microorganisms

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 5 of 43
Mandatory sign
Use protective apron!
Mandatory sign
Use protective boots!
1.4 Warranty
All WDT devices and equipment are manufactured using modern production methods and are subject to
comprehensive quality control. However, should there be a reason for complaint, any compensation claims
shall be directed to the company WDT in accordance with the general terms and conditions of warranty (see
below).
General terms and conditions of warranty
The Co. WDT assumes a 2-year warranty, starting with the commissioning, up to 27 months after delivery;
subject to correct installation and commissioning with a completed and signed commissioning protocol.
Exempt from this are wear parts such as gaskets, hoses, membranes, dosing screws, electrodes, roller
supports and other parts that are subject to mechanical or chemical wear and tear. For these we assume a
warranty of 1/2 year.
Our merchandise management programme requires an invoice for each delivery (including warranty services).
When returning a defective component, upon review you will receive a corresponding credit, if applicable.
We request a return within 14 days.
The costs for subsequent damages and for the processing of warranty claims are excluded.
There are no warranty claims for damages caused by frost, water and electrical overvoltage or by improper
handling.
Tip!
In order to protect the warranty claims, please mail the completed commissioning
protocol, along with the defective component, to the Co. WDT. Without the
commissioning protocol, we reserve the right to assert a warranty regulation.
CAUTION!
It is not permitted to make any modifications to the device. If this specification is not
observed, the warranty obligation and product liability will expire!
1.5 Further information
Further information about special topics, e.g., design of the dosing performance or description of the
operating parameters, is available from your specialist supplier.
1.6 Information regarding support queries
The GRANUDOS Touch series is a highly sophisticated electronic control unit. It is subject to continued
further development of both its firmware and hardware. We always strive to preserve the compatibility of
the components used, but we are unable to guarantee this over a period of several years!
For spare part orders, we therefore always require the following data. You can find these on the nameplate.
exact device designation
device serial number
year of manufacture
We also require the following data for technical support requests. You can find these in the menu item Menu
Service Info.
current firmware version
current hardware version

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 6 of 43
2Safety
2.1 Intended use
The GRANUDOS Touch control unit must only be used for the purposes described in the Product Description
in Section 3.2, Product description! The locally applicable regulations concerning accident prevention,
occupational safety and drinking water protection must also be observed!
2.2 Safety notices
Carefully read and comply with the operating instructions prior to install, maintenance and use of the device!
Work on the device and changes in the settings may only be carried out by properly instructed persons!
IT safety
The GRANUDOS Touch control unit makes remote display possible using network-enabled devices. The
operator is responsible for ensuring that only authorised persons can access the device. The operator, or his
authorised representative, is further responsible for the safety of all Internet or WLAN connections.
Handling of chemicals, risks to humans and the environment
In emergencies when handling chemicals, you can also contact the emergency poison centre!
Emergency number:
Munich Emergency Poison Centre (or any other Poison Centre)
Phone: +49 89 19240
Excerpt from the Accident Prevention Regulations, GUV-V D 5
Installation rooms for chlorination systems and storage rooms
Section 3a. (1) Chlorination systems must be installed in lockable rooms and the chemicals intended for the
chlorination must be stored in lockable rooms.
Re Section 3a Para. 1:
This requirement ensures that chlorination systems and chemicals shall be protected against weather effects
and unauthorised access.
(2) Rooms in accordance with Para. 1 must not be intended for the permanent presence of persons.
Re Section 3a Para. 2:
…… A “permanent presence” is given when persons are present in the room for more than 2 hours per day.
Repair and maintenance work on the chlorination system are exempt from this.
Protective measures and rules of conduct
CORROSIVE!
The GRANUDOS Touch control unit controls devices that dose corrosive chemicals.
For this reason, it is essential that you observe the safety information relating to the
device!
ESD SENSITIVE!
The electronic components in the device controls are sensitive to electrostatic
discharge. For this reason, the generally accepted safety precautions for ESD-sensitive
devices must be observed when handling the devices, including:
Discharge of personal static charge
Dissipative clothing
Disconnect the device from the voltage supply

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 7 of 43
3Product description - scope of delivery
3.1 Scope of delivery / accessories
The GRANUDOS Touch control unit is delivered with the dosing device GRANUDOS as standard.
In addition, customer-specific or order-related modifications are possible; e.g. remote display.
3.2 Product description
The GRANUDOS Touch control unit is intended solely for control tasks associated with the treatment of
swimming pool water. It is used for the following 2 dosing devices:
GRANUDOS 10 Touch
GRANUDOS 45/100 Touch
The control system has the following main functions:
dosing chlorine granulate with screw conveyor
Dosing acid with hose pump directly from the delivery canister
high chlorination with switching a control valve –for backwash disinfection or filling of a buffer tank with
chlorine solution for disinfecting additional small pools with dosing pumps (option)
Fault message potential-free
PC link, remote display via LAN
Remote display (optional)
Device overview
The GRANUDOS Touch control unit is delivered as a ready-assembled unit.
1. Control unit GRANUDOS Touch
2. Hose dosing pump (covered)
3. Suction sets (covered)
Figure 1, GRANUDOS 45/100 Touch and GRANUDOS 10 Touch
1
1

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 8 of 43
3.3 Identification of device / nameplate
For spare part orders and troubleshooting, it is useful to know the device serial number and the firmware version. The
device serial number is located on the nameplate on the right side of the control casing. The firmware version can be
found using the menu item Menu Service Info.
Nameplate see OI Part 1 for the dosing devices
for Granudos 10-Touch, No.: BA SW 002
for Granudos 45/100-Touch, No.: BA SW 003
3.4 Technical data
GRANUDOS 45/100 Touch Control
Unit
GRANUDOS 10 Touch Control Unit
Connection data
Electric connection data
230VAC/50Hz ± 10%, 35W, I max.
0.2A, standby 22VA, safety (Schuko)
plug
230VAC/50Hz ± 10 %, 35W, I max.
0.2A, standby 22VA, safety (Schuko)
plug
Protection class
Casing IP54
Casing IP54
Interface connection
Modbus TCP, USB for data export
Modbus TCP, USB for data export
Operating data:
Measuring range
pH value: 2.00 to 12.00
pH value: 2.00 to 12.00
Medium temperature
Ambient temperature
Humidity engineering room
0°C to 40°C
5°C to 35°C
max. 80% non-condensing
0°C to 40°C
5°C to 35°C
max. 80% non-condensing
Concentration hypochlorous acid
max. 0.4%
max. 0.2%
Room ventilation (in and out)
According to DIN 19643
According to DIN 19643
Material
Casing: PS
Casing: PS
Firmware version
---
---
Hardware version
---
---
3.5 Transport / storage
Please check the devices immediately upon receipt for potential transport damage.
ATTENTION!
The systems and devices can be damaged by frost or high temperatures. Avoid
exposure to frost during transport and storage! Do not store systems and devices
next to objects with strong heat emission or in direct sunlight. The device may only
be transported and stored in its original packaging. Please ensure careful handling.

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 9 of 43
4Installation
See operating instructions Part 1 Dosing technology, regarding the respective dosing device.
for Granudos 10-Touch, No.: BA SW 002
for Granudos 45/100-Touch, No.: BA SW 003
5Commissioning
5.1 Commissioning, - comments
The work described here may only be carried out by trained specialist personnel from a specialist company.
Prior to commissioning, the installed devices must be checked for proper installation and leaks.
The device has been delivered with specific factory settings. The settings can be found in the operation data
sheet in Section 9.4.
NOTICE!
Check all of the screw connections on the device. Plastic screw connections may only
be fastened hand-tight!
5.2 Commissioning tasks
The mechanical commissioning is now completed. The device is assigned with predefined parameters at the
factory. Please adjust the parameters to your pool, taking into account the required dosing performance and
target values.

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 10 of 43
6Operation / service
NOTICE!
The nationally applicable accident prevention regulations must be observed.
6.1 General
Once all the preparations for commissioning have been completed, the settings can be made on the
GRANUDOS Touch dosing system.
6.2 Control unit GRANUDOS Touch
The GRANUDOS Touch control unit is equipped with a touch-sensitive display. Settings can be made by
tapping on a symbol. The adjustment menus come with additional text-based instructions.
Operation display –Automatic operation
The control unit of the GRANUDOS Touch is simple and easy to operate using a 7" touch display. The
operating modes and faults are displayed directly in the start screen: see Figure 2, Automatic operation.
In automatic operation, the current operating status, fill levels, and active inputs and outputs are displayed (IN
–OUT). The inputs and outputs can be operation messages or fault messages.
Operating notes:
The operating status is displayed in the status line. The following operating states are available:
Dosing delay
Automatic
Manual dosing
Menu
Adjustment
Output test
Input test
The device is operated using a resistive touch display. Desired parameter changes, calibrations and tests can
be done simply by lightly touching the corresponding symbol or the numeric value.
1. Fill level chlorine granulate
2. Dust extraction (optional)
3. IN list
4. OUT list
5. Status line
6. Measuring value pH (optional)
7. Switch over “start screen/buffer tank”
8. Acid fill level
9. Cancel alarm
10. Start / Stop dosing device
11. Activate / deactivate dosing manually
12. Menu button
13. Date / time bar
14. User level (0=guest, 1=end user, 2=technician 1)
Figure 2, Automatic Operation, Start Screen
1
2
3
4
5
6
7
8
14
9
10
11
12
13

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 11 of 43
The IN list shows the input signals to the control unit.
The OUT list shows the active output signals of the control unit.
Symbols used:
The symbols depend on the firmware installed i.e. on the device version
The function buttons on the start screen
Switch to buffer tank view
Reset chlorine consumption counter
Reset acid consumption counter
Dosing device on/off
Deactivate dosing manually e.g. for for servicing works
Deactivate alarm relay
View main menu
IN list (general)
red = pH level (container for pH regulation empty)
yellow = disinfection level (container for disinfectant empty)
blue = flocculation level (container for flocculant empty)
High chlorination (e.g. for filter disinfection) active
The controller is deactivated by the central control technique.
No dosing, no alarm message given.
The dosing is blocked by an optional flow switch in the clean water line.
No dosing takes place
A dynamic dosing time has been exceeded. The respective output is blocked.
Dosing deactivated manually
red = Input signal external acid control active
yellow = Input signal external chlorine control active
The pressure at the GRANUDOS booster pump is too low. The booster pump is being stopped
The level in the GRANUDOS flushing tank is too low. The booster pump is being stopped
The level in the GRANUDOS flushing tank is too high. The dosing of chlorine and acid is stopped

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 12 of 43
The flow in the GRANUDOS is too low. The dosing of chlorine and acid is stopped.
The fuse of the chlorine dosing motor has tripped.
OUT –List
red = acid dosing output active
yellow = chlorine dosing output active
The alarm relay is active.
Chemical reserve
Advice notice for container exchange, check chemicals status and prepare new chemical
The booster pump is active
The knocker is active. This symbol is only displayed very briefly
The following symbols relate only to the buffer filling OPTION.
IN List (optional, design with buffer tank) )
Buffer tank filling is starting
Buffer tank filling is ending
The buffer tank level has dropped too low. Chlorine dosing is stopping
The buffer tank level is too high.
Chlorine dosing, acid dosing and the booster pump have stopped.
Alarm collecting basin (leaking)
Chlorine dosing, acid dosing and the booster pump have stopped.
The optical sensor on the cyclone did not detect any chlorine while the buffer tank was being filled. Filling has
been stopped.
Buffer tank filling has been deactivated by the system. Filling was performed too slowly or the optical sensor
on the cyclone was triggered.
OUT List (optional, design with buffer tank)
Buffer tank filling is active.

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 13 of 43
Operation display:
Depending on the operation state, the display shows different views. The following illustrates and describes the main display
views.
Start –Delay booster pump and dosing delay
If the device is restarted, the start delay circuit booster pump and
dosing delay runs while no dosing output is triggered.
Software alarms are suppressed during this time.
The device then switches to automatic operation
In the event of a booster pump delay, the indicated delay runs out and
the booster pump then starts.
(Serves to vent the supply line.)
The icon (top right) can be used to switch to the "Buffer tank
operation" display.
If the dosing device is reset externally, dosing stops and the booster
pump runs on for a short time afterwards, so that there is no chlorine
remaining in the suction line.
Automatic operation
The device is in automatic operating mode. The device doses when
requested.
There is no disruption.
The OUT list shows the currently active outputs and/or actuators as an
example.

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 14 of 43
Alarm
If an alarm occurs, this will be indicated by the symbol in the OUT list.
The alarm relay is activated.
The alarms are distinguished from each other (software alarms e.g. dosing
time monitoring and faults (switch inputs)).
In the event of measuring value alarms, the respective measuring value is
additionally illustrated in red.
In the event of disruptions, the corresponding symbol appears in the IN list.
Alarms or faults must be pending for approx. 5 seconds before an alarm is
triggered.
The button can be used to deactivate the alarm relay temporarily,
without rectifying the fault.
The GRANUDOS starts now with the „start routine“
If a fault occurs again, or the fault is not rectified, the alarm relay will
be reactivated.
Tip!
An alarm will be automatically deleted when its cause has been remedied. When, for
example, the empty chemical container has been replaced.
However, the alarm switch-off time monitoring must be acknowledged manually!
Manual dosing (emergency programme)
In the event of a fault with the external measurement technology that
cannot be rectified, for a limited period of time, the disinfection dosing
and the dosing of the pH value regulation can be performed via the
emergency function Manual operation.
If this operating mode is selected (see Section 6.3.2.1), the display in the
status line changes from automatic to manual dosing.
6.3 The Main Menu
Automatic
Leads to start screen and into automatic operation; switches
automatically to user level 0 or 1. In manual operation mode,
a different symbol is displayed here.
Settings
For adapting parameters and system settings
Service
Input and output test, info
Login
For password assignment; no password is assigned in the
delivery state.
Log
For query of events and data logging
Calibration
Calibration of pH electrode
manual dosing

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 15 of 43
Main Menu Login
Passwords are given under Settings System Password. The
control unit is protected from unauthorised access by a personal
password. Settings, calibration, output tests etc. cannot be performed
without a password. You can still browse the menu and view the data
logging.
If no password has been assigned in user level 1, then it immediately
switches to user level 1!
For future changes and adjustments, you must sign in with your
personal password under Login. If you switch to the start screen, the
password must be re-entered.
NOTICE!
Once a password has been assigned, unauthorised persons will be denied access to the
control unit. The setting buttons will appear in grey. Desired changes can only be made
after the password has been entered. Once a password has been assigned, make a note
of the password and keep it in a secure location.
Main Menu Settings (overview)
The settings menu is used to implement the desired settings for the dosing device. Using the white arrow keys on the side,
you can navigate to the next screen menu. The 2nd page is only displayed in user level 2 (technician 1).
Dosing performance chlorine/acid (6.3.2.1)
Adjust the dosing performance to the basin size
Reserve indication chlorine (6.3.2.2)
Set reserve message for disinfectant
Reserve indication acid (6.3.2.3)
Set reserve message for pH reducer
Shock chlorination (6.3.2.4)
Set dosing performance for the Shock chlorination function
System (6.3.2.5)
Set date, time, password, display, network and language
Determining dosing performance chlorine (6.3.2.6)
Dosing performance (dosing quantity) is being detected
Dust extraction (optional) (6.3.2.7)
Set parameters for dust extraction
Buffer (buffer tank) (6.3.2.8)
Set dosing performance for buffer tank filling function
pH Supervision (6.3.2.9)
Set parameters for pH monitoring
Delay booster pump (6.3.2.10)
Set delay time for the start of the booster pump
Dosing performance cl granulate (customer service
technician only) (6.3.2.11)
Set device-specific dosing parameters
Dosing performance acid (customer service technician
only) (6.3.2.12)
Set device-specific dosing parameters

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 16 of 43
Main Menu Settings dosing performance chlorine/acid
The dosing performance menu serves for adjusting the dosing
performance to the expected consumption of chemicals in the pool.
Especially in case of lower water content, it is very important to adjust
the dosing performance.
The required dosing performance depends on several factors, e.g., the
basin volume, location, type of use and of course the frequency of use
by pool visitors.
Explanation of setting parameters
Chlorine: Dosing time of chlorine granulate adjustable from 1-15 seconds
Acid: Dosing time of acid in seconds adjustable from 1-8 seconds
ATTENTION!
The use of sulphuric acid is generally possible up to a concentration of 50%. For higher
concentrations or when using other acids (e.g. hydrochloric acid, dissolved sodium
bisulphate, etc.), the changed dosing performance and/or increased corrosiveness must
be observed! We recommend to consult with the company WDT!
Cycle: Length of complete dosing cycle adjustable from 30-360 seconds
Dosing time limit acid: Dosing time monitoring for external control adjustable from 0-100 minutes
Dosing time limit chlorine dosing time monitoring for external control adjustable from 0-100 minutes
Manual dosing off / on: Switch between automatic and manual dosing
Explanations of the dosing process
Chlorine and acid are dosed at intervals with pauses between the dosings.
The dosing is organised in dosing cycles (time from dosing interval to dosing interval) and dosing times (dosing times for
chlorine and acid dosing motors).
A dosing cycle proceeds like this:
1. Chlorine dossing - 1-15 sec.
2. Pause - 3.5 sec.
3. Acid dosing - 1-8 sec.
4. Pause until end of cycle
This cycle runs continuously with "manual dosing".
In "Automatic" mode, the cycle will also run, but the dosing will only be activated if the control command for dosing (chlorine
or acid) is pending. If the control command hits for a pause, the corresponding dosing will be activated in the next dosing
cycle.
Example for setting the dosing performance
Prerequisite: Indoor pool with a circulation capacity of 200m³/h. In accordance with DIN 19643, in indoor pools 2g of
chlorine must be added per each 1m³/h circulation capacity.
Calculation: 200m³/h x 2g chlorine = 400g/h chlorine dosing
Maximum dosing performance GRANUDOS 45 = 2000g/h = 100%
That means that the dosing performance must be set to 20% for a chlorine dosing of 400g/h.
The acid dosing is initially set to the same value, i.e., at 20%.
A readjustment may be necessary during ongoing operation.
Explanation of dosing time monitoring
If the GRANUDOS is controlled by a measuring and control device, the dosing performance must be set sufficiently high so
that even large loads can be regulated without large deviations from the target value. This means that the pause times must
always be greater than the dosing times. If, however, the dosing times are longer than the pause times, there is a fault with
the measuring and control device (e.g. control relay hanging) or the dosing performance is too low (set too weak or motor
or dosing screw faulty) or the input relay on the GRANUDOS control plate hangs. The dosing time monitoring totals the
dosing times against the pause times and if the set dosing time limit is exceeded, dosing is deactivated and indicated as a fault.
Both the chlorine-control and pH-control or -dosing is monitored.

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 17 of 43
Explanation regarding the operation with external acid control (pH)
If a (existing) external dosing pump is to be operated for regulating the pH-Value, it must be remembered that the acid
dosing in the GRANUDOS is always active in order to avoid deposits in the solvent system.
In this case the acid control input can be clamped parallel on the chlorine control input (wire bridge).
With 230V control: on pin connector Nr. SL7 on the power plate NT-GRD, clamp 1+3 and clamp 2+4 is to brigde.
With potential-free control: on the I/O plate on pin connector Nr. SL10, clamp 1+3 and clamp 2+4 is to bridge.
Thus, during each chlorine dosing the acid dosing is activated as well. The dosing performance for the acid dosing must be
set to a low value here for the required cleaning function. However, it must also be checked whether the set dosing
performance is sufficient for the cleaning: the cyclone may not get turbid. See also Section 6.3.2.12, Page 22.
Tip!
It is urgently recommended to connect the pH-control at the GRANUDOS to avoid
acid overdosing in the event of a fault in the chlorine dosing.
Manual dosing Off/On
It is possible to change over to continuous manual dosing. This may be
required in the event of a fault with the measurement technology, e.g.
electrode failure, that cannot be rectified. For a limited period of time,
both the disinfection dosing and the dosing of the pH regulation may
be performed via the emergency function Manual operation.
After activation of Manual dosing, the display in the start screen
changes.
CAUTION!
In the operation mode Manual dosing, the operating personnel must continually check
the water quality and adjust the dosing amounts. Non-compliance with this may result
in significant incorrect dosing!
Main Menu Settings Reserve indication chlorine
The quantities for which a reserve message will be displayed after
dosing are indicated here, as well as the size of the full container.
The message indicates that the chemical container will soon be empty.
The reserve message function can also be deactivated.
Main Menu Settings Reserve indication acid
The quantities for which a reserve message will be displayed after
dosing are indicated here, as well as the size of the full container.
The message indicates that the chemical container will soon be empty.
The reserve message function can also be deactivated.

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 18 of 43
Main menu Settings ECO –shock high chlorination
This menu lets you adjust the dosing performance during a high
chlorination –e.g. for buffer tank filling of filter disinfection. For
monitoring purposes, the concentration must be analysed
photometrically during shock chlorination!
Main menu Settings System
Date/ Time
Set date and time
Password
Assign a password
Display brightness
Adjust the display brightness to the ambient conditions
Network
Set network parameters
Reset
Select the user language
Language
Select the user language
System ID
For factory customer service only
Internal
For factory customer service only
a) Main menu Settings System Date/ Time
Adjust date and time.
You can activate automatic switching from winter to summer time.

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 19 of 43
b) Main menu Settings System Password
Guest (user level 0)
No password, read-only rights
End user (user level 1)
There is no factory setting for an end user password. We recommend
the assignation of an end user password to protect the system against
unauthorised access. Enter the password in the operation data sheet.
The individual end user password must contain four digits between
0000 and 9999. In the second line, the password must be entered once
again.
Technician 1 (user level 2)
The Technician 1 password consists of five digits and has a factory
default setting of 01234. This password is intended for service
partners. We recommend that you change this password as well and
enter it in the operation data sheet.
If you place a green check mark next to Clear text, the entered
numbers are shown instead of white dots.
To change an active end user password, it must be entered in the upper
line. The new password must be entered in the two following lines.
If you wish to delete the end user password completely, simply enter the active password in the upper line.
The other two lines remain clear.
If an incorrect password is entered, an error message appears.
NOTICE!
Please store the individually chosen passwords safely in the operation data sheet. Lost
passwords can only be reset by the factory customer service!
c) Main menu Settings System Display
The screensaver dims the background lighting after the set delay time
to the selected brightness.
The Test button can be used to test the settings.
The Backlight setting permanently reduces the background lighting in
the operating mode.
The boot logo may be displayed when the control unit is activated.
The screensaver may be activated or deactivated.
Save settings using OK and confirm instruction using OK .

GRANUDOS Touch, control unit
Index: 02 Date modified: 11/06/2019 OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx Page 20 of 43
NOTICE!
Please reduce the background lighting to the minimal brightness required by you. This
increases the service life of the display significantly.
d) Main menu Settings System Network
The touch panel has a LAN interface with RJ45 socket. The current
status messages can be transferred to an external display via this
interface. The terminal device can be a PC monitor, a tablet PC or a
smartphone, e.g.
Further information about this topic is available upon request. The
operator must establish the necessary IT requirements for remote
access! (e.g., VNP connection, data security, etc.)
e) Main menu Settings System Reset
This order can only be performed in user level 2.
All of the set parameters are reset here to the factory settings.
The factory settings are listed in the operation data sheet in Section 9.4.
After “reset” all individual setting must be set again!
f) Main menu Settings System Lanuage
Select the desired operating language.
Main menu Settings Determining dosing performance
The effective dosing performance must be determined in order to
calculate chemical consumption and thereby the reserve message.
Follow the menu prompts. A dosing sample is taken 3 times.
NOTICE!
Place a shallow collecting vessel under the dosing pipe and follow the menu prompts.
Weigh the dosing sample.
This manual suits for next models
1
Table of contents
Other WDT Control Unit manuals
Popular Control Unit manuals by other brands

Burkert
Burkert 2030 quick start

Rockwell Automation
Rockwell Automation Allen-Bradley 1734-232ASC Original instructions

Watts
Watts IntelliFlow A2C-M1 operating instructions

Victor
Victor DRAC2 manual

Gebwell
Gebwell G-Power 2/100 Installation and maintenance manual

National Instruments
National Instruments PXI-2568 manual