Weinzierl KNX ENO 634 User manual

WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 1/11
KNX ENO 634 (32-channel AP)
Bidirectional-Gateway between EnOcean and KNX-Bus
Operating and installation instructions
Fig. 1: KNX ENO 634
Application
The KNX ENO 634 is a bidirectional gateway between
EnOcean radio devices and the KNX bus. It transfers
commands and measured values of EnOcean wire-
less sensors to the KNX bus, for example, to control
KNX actuators. EnOcean wireless actuators can also
be controlled via KNX. The EnOcean communication
is based on the EnOcean Equipment Profiles (EEP).
This profile is usually specified in the data sheet of the
EnOcean device. For the controlling of EnOcean ac-
tuators corresponding EEPs are emulated. This
means that the gateway sends radio telegrams like a
push button or a window contact. In addition the
gateway supports logical and control functions and in-
cludes radio-repeater functionality. The KNX ENO 634
is divided in 32 channels. Each channel can be as-
signed to one of the following functions:
•Link from EnOcean sensor to KNX
Switch functions
- Switching
- Dimming
- Shutter
- Scene
Window handles
Window contacts
Access card switches
Press switches
Temperature sensors
Humidity sensors
Light sensors
Presence sensors
Gas sensors
Room control panels
Automated meter devices
Environmental sensors
Digital inputs
•Link from KNX to EnOcean actuator
Switch
Dimmer
Shutter
HVAC actuators (valves)
•Control / logic
Timer
- Switch-on delay
- Switch-off delay
Control
- 2-point regulator
- Continuous regulator
- Heat requisition
- Lighting control
Logical functions
- Gates (e.g. AND, OR, XOR)
- Flip-flop (Toggle)
Special
- Trigger
- Valuator
- Watchdog
The configuration of the device and the channels is
performed using the ETS software via the KNX-Bus.
To configure the wireless components the keys and
the display in the device are used.

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 2/11
Mounting and connection
The mounting can be done on a wall surface (e.g.
brick-work or wood). The mounting holes match those
of a 55 mm flush-mounted box.
When choosing the installation location the RF range
of EnOcean devices to be associated with the gate-
way has to be considered. Shielding objects (e.g.
metal cabinets) or interfering transmitters (e.g. com-
puters, electronic transformers, ballasts) near the
gateway should be avoided.
More information on range planning and RF interfer-
ence can be found in the data sheets of the devices
and on www.enocean.com.
The connection to the KNX bus is made with a bus
connector. The correct polarity of the terminal referred
to the printing inside the unit has to be considered.
The device is powered by the bus, and does not re-
quire an external or additional power supply.
Settings before commissioning
A gateway ex-factory has the default individual ad-
dress 15.15.255. There are no group addresses and
no connections to RF sensors and actuators pro-
grammed.
Button functions
The buttons inside the device are only needed for the
commissioning phase and are not accessible when
closed.
Key press T1 long (Del.): Delete the stored device
from the current channel (Refer to chapter “Deleting
links for RF sensors” and “Deleting links for RF actua-
tors”)
Key press T1 short (Exit): Leave channel/linking
mode
Key press T2 long (Add): Start linking mode (Refer
to chapter “Linking mode for sensors” and “Linking
mode for actuators”)
Key press T2 short (Active): Activate or change the
channels 1-32
Key press T3: Activate “KNX Prog. mode” – The
KNX device can now receive a new individual ad-
dress. (Refer to Chapter “Programming the physical
address”)
A long key press is detected when a button is pressed
for longer than 2 seconds.
Fig. 2: View of the open unit
LCD Display
The integrated display is used for commissioning and
system diagnostics. In normal operation, it is not re-
quired and is not visible when the device is closed.
The main menu shows the device name, the opera-
tion mode (e.g. RUN) and the KNX individual-address
(Fig. 3).
Fig. 3: Main menu display
The signal strength of received radio telegrams is vis-
ualized as a bar at the bottom of the display. If the re-
ceived telegram corresponds to one or more chan-
nels, it will be shown in a channel matrix on the dis-
play.
When a channel is selected the first line of the display
shows the channel number and the text configured in
the ETS (“1 Rocker” in fig. 4). In the second line the
channel type (sensor/actuator) and associated
EnOcean equipment profiles (EEP) is shown.
In the third line, the number of the allocated and
available channel links together with a symbol is dis-
played. The signal strength bar is displayed in the last
line.

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 3/11
Fig. 4: Channel setting display
Programming the individual address
Programming the KNX individual address with ETS
requires that the programming button T3 ("KNX Prog.
mode") be pressed. If the programming or learning
mode is active, the red LED ("KNX Prog. mode LED")
will be on. It turns off once the device has successfully
received the individual address. Afterwards, Group
Addresses and Parameters can be programmed by
the ETS.
Linking to EnOcean-devices
Before linking to EnOcean devices, the functions have
to be programmed for each channel with the ETS. Per
channel typically only one EnOcean device can be
linked. For switches, window handles and window
contacts up to four links per channel are possible.
For actuator channels any number of RF actuators
can be learnt.
Linking mode for RF sensors
The operation of the gateway during the teach-in of
wireless sensors is done using the two buttons below
the display.
If the device is in normal mode,
the push button T2
activates, by short key presses, the channel mode
and changes to the next channel. The display shows
the current channel number and the number of con-
nected devices. Also the ETS configured text will be
shown for every channel (Fig. 4).
With a long press of T2 on the visible channel, the
linking mode is activated. If the device matches the
selected function via the parameter configuration, a
transmitting device can be connected to the current
channel. A connection is created by pressing the
learn-button of the sensor.
Window handles and
switches must be operated for teach-in because they
do not have a separate learn button.
To avoid that other transmitting devices are stored by
accidental activation during the programming phase,
devices can be programmed only after 3-times activa-
tion. For this purpose in the general parameters ‘Link
switches/handles (RPS) after 3 tel.’ must be selected.
The sensor has to send three telegrams within 10 se-
conds to be linked.
The link mode is terminated by a short press of the
left key T1, as well as automatically after 5 minutes
without operation.
Quick guide linking mode for RF-sensors
1. T2 short press to select the desired channel.
2. T2 long press to activate the learning mode
("Wait for ENO ...").
3. Activate the learning mode in the RF-sensor.
4. The sensor is now programmed
Deleting links for RF sensors
Links with RF sensors can be deleted in several ways.
With a long press on T1 the delete mode is activated
for the current channel. The sensor can now be delet-
ed from the visible channel by pressing the learn but-
ton on the RF sensor. It is also possible to delete all
assignments of the selected channel by pressing T2
("All"). It is not required to operate the RF sensors.
Fig. 5: Deleting links
By programming the application program via the ETS
all programmed sensors of all channels will be delet-
ed, when the "Delete all links after download" function
in the general parameter is enabled.
If the function of a channel has been changed, pro-
gramming the parameters with the ETS deletes the
links of the modified channel.
The link mode is terminated by a short press of the
left key T1, as well as automatically after 5 minutes
without operation.
Quick guide linking mode for RF-sensors
1.
T2 short press to select the desired channel
.
2.
T1 long press to activate the delete mode ("Wait
for ENO or del all left ...").
3.
Activate the learning mode at the desired radio
sensor to delete these.
Alternatively:
T2 long press to delete all taught-in wireless sen-
sors from the selected channel.
Linking mode for RF-actuators
The operation of the gateway during the linking of ac-
tuators is similar to the linking of sensors. First the ac-
tuator is placed in linking mode. A long press of T2 at
the visible channel activates the linking mode in the
gateway. The display shows the “select key” selection
(Fig. 6). The action point (top or bottom) of the learn
telegram can be selected with the T2 button. On some

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 4/11
actuators both action points have to be linked sepa-
rately.
Fig. 6: Selection of learning telegram
Now the button T2 is pressed for sending the learn-
telegram to the actuator in the learning mode (The
display briefly shows "RF"). If this is done, the learn-
ing mode of the actuator can be finished. The actuator
should now be programmed.
The link mode is terminated by a short press of the
left key T1, as well as automatically after 5 minutes
without operation.
The procedure for activating the learn mode of the ac-
tuator can be found in the Actuator Datasheet.
Quick guide linking mode for RF-actuators
1. Select the desired channel with T2
2. Activate the learning mode on the RF-actuator.
3. T2 Long press to activate the learning mode in
the gateway.
4. T2 short press to select the action point.
5. T2 long press for sending a learn-telegram to the
actuator. (Display: “RF”).
Deleting links for RF actuators
The links to RF-actuators are stored in the respective
actuators. This can be deleted for many types locally
on the device without operating the gateway. With
some actuators it is also possible to delete individual
links, using learn-telegrams. In this case, the delete
works in the same way as the teach-in of the actua-
tors. The actuator must be set into the erasing mode.
Each programmed link must be cleared through the
learning mode on the gateway. Details are given in
the data sheet of the respective actuator.
Normal operation
RF-sensors:
When in normal operation model, each received
EnOcean telegram will be compared to see if it has
been assigned to a Channel. If so, the channel is
shown shortly in a matrix on the LCD display.
De-
pending on the configured function there will be one
or more telegrams sent on the bus. The gateway only
sends telegrams to the KNX bus when a correspond-
ing EnOcean telegram has been received. If an
EnOcean telegram is not assigned to any channel,
only the signal strength is shown in the display with a
bar.
RF actuators:
If the gateway receives a telegram from the KNX bus,
which is assigned to an actuator channel, an RF tele-
gram will be sent for this channel.
Internal links
For some use cases it is necessary to link KNX data
points (communication objects) of different channels.
Thus, values of sensor channels can be connected
with inputs from control channels. But also wireless
sensors can be connected with RF actuators.
Datapoints can be linked in the ETS by assigning the
same group address to an output and an input object.
In this case the values will also be sent to the bus.
In contrast, the internal links are foreseen to link
communication objects directly without sending tele-
grams via the KNX bus. For this purpose no group
addresses have to be assigned in the ETS. Internal
links can be created in the parameter dialog of the
ETS. In the receiving channel, the communication ob-
ject number of the output channel can be selected.
The value of the selected object is copied internally in-
to the receiving object and implements the associated
function.
Gateway functions
For each channel, one of the following functions can
be chosen. The selection is made in the parameter
dialog of the ETS.
Link from EnOcean sensor to KNX bus
The following functions are available in the sensor pa-
rameters:
- RPS switch

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 5/11
Fig. 7: RPS switch (sensor)
There are types of switches from one, two and four
rockers. To the Rocker (A…D), the following modes of
operation can be assigned:
Switch – On/Off
On/Off (rocker up/down)
A short or long key press on the upper switch will
send an off-telegram. A short or long key press on the
lower switch will send an on-telegram.
On/Off (rocker up/down)
Function as before, but rocker swapped top and bot-
tom.
Comm.-Object Type KNX size
Channel…: switch 1.001 1 Bit
Dimming
On/Off – brighter/darker (rocker up/down)
Short pressing on the top button switches the dimmer
on and short pressing on the bottom switches it off. A
long press on the top button dims the light brighter
and a long press on the bottom button dims darker.
Dimming stops by releasing the button.
Off/On – darker/brighter (rocker up/down)
Function as before, but rocker swapped top and bot-
tom.
Comm.-Object Type KNX Size
Channel…: switch 1.001 1 Bit
Channel…: dimming 3.007 4 Bit
Shutter – Up/Down
Slats – shutter up/down (Rocker up/down)
After a long press on, the run command is sent for the
shutter. With a short press the shutter trip stops.
When the shutter is not moving, the slats are rotated
by a short press on the switch. The direction of the
command is up by pressing the top button. By press-
ing the lower key the run command is “down”.
Slats – shutter down/up (Rocker up/down)
Function as before, but rocker swapped top and bot-
tom.
Comm.-Object Type KNX Size
Channel…: Slats 1.009 1 Bit
Channel…: Shutter 1.008 1 Bit
Scene – a/b
Two scenes can be switched. Depending on the set-
ting, a scene can be saved for a long push if the actu-
ator supports this.
Comm.-Object Type KNX Size
Channel…: Scene 18.001 1 Biyte
- Other switches and contacts
Fig.8: Other switches and contacts
In the submenu “Other switches and contacts” window
contacts, window handles, key card switches and
pressure switches can be integrated.
For window handle sensors, three states can be de-
tected. (Window is open, tilted or closed). When turn-
ing the handle in a position the corresponding state
will be mapped to two communication objects and
transmitted. Up to four handles can be taught to a
channel.
The gateway calculates a common status of all han-
dles assigned to the channels. Following some exam-
ples from the state table:
Window 1 Window 2 Window 3 Window 4 Common
status
Open Open Open Open Open
Open Tilted Open Open Open
Open Closed Tilted Closed Open
Closed Closed Closed Tilted Tilted
Closed Closed Closed Closed Closed
For window handles are available the following com-
munication objects:
Comm.-Object Type KNX Size
Channel…: Status 1 1.001 1 Bit
Channel…: Status 2 1.001 1 Bit
Handle Closed Tilted Open
Status 1 Off On On
status 2 Off Off On
The position of the handle is dependent on the instal-
lation condition. This is described in the datasheet of
the window handle. The handle is mounted correctly if
two Off-telegrams via both datapoints are sent when
the window is closed.
Up to four window contacts can be linked with one
channel. The gateway calculates a common status of
all contacts assigned to the channel and sends the
value “closed only, if all contacts are closed.
For window contacts the following datapoint is availa-
ble:
Comm.-Object Type KNX Size
Channel…:Window group open 1.019 1 Bit
For pressure switches the following datapoint is avail-
able:
Comm.-Object Type KNX Size
Channel…:Pressed 1.002 1 Bit
For key card switches the following datapoint is avail-

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 6/11
able:
Comm.-Object Type KNX Size
Channel…:Key card inserted 1.002 1 Bit
- Temperature sensors
Fig. 9: Temperature sensors
Temperature sensors with various value ranges are
supported. The temperature value is mapped to a
2-byte floating-point value.
For all temperature sensors the following communica-
tion object is available:
Comm.-Object Type KNX Size
Channel…: Temperature 9.001 2 Byte
- Temperature and humidity sensors
Fig. 10: Temperature and humidity sensors
Two different combined sensors can be selected. The
measured values are stored in two different communi-
cation objects.
Comm.-Object Type KNX Size
Channel…: rel. humidity 9.007 2 Byte
Channel…: Temperature 9.001 2 Byte
- light sensors
Fig. 11: light sensors
The measuring of light intensity is done in lux (lx). The
measured value is available as a 2-byte float value.
Comm.-Object Type KNX Size
Channel…: Lux 9.004 2 Byte
- Presence sensors
Fig. 12: Occupancy sensors
In this section presence sensors and motion detectors
can be integrated.
Comm.-Object Type KNX Size
Channel…: presence 1.018 1 Bit
- Light-/Temperature- und occupancy sen-
sors
Fig. 13: Light-/Temperature- und occupancy sensors
Light intensity and temperature are each mapped to a
communication object with a 2 bytes float value.
Presence and motion detectors send 1-bit values.
Comm.-Object Type KNX Size
Channel…: Lux 9.004 2 Byte
Channel…: Temperature 9.001 2 Byte
Channel…: Presence 1.018 1 Bit
Channel…: Occupancy 1.001 1 Bit
- Gas sensors
Fig. 14: Gas sensors
Sensors for CO and CO2 can be connected. The CO
sensor can measure the gas concentration and the
temperature (2 bytes each values).
The CO2 sensor can measure gas concentration,
temperature and relative humidity (each 2 byte val-
ues).
Comm.-Object Type KNX Size
Channel…: Gas 9.008 2 Byte
Channel…: Temperature 9.001 2 Byte
Channel…: Humidity 9.007 2 Byte
- Room operation panel

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 7/11
Fig. 15: Room operation panel
Various room controls with temperature, presence,
and day / night switches can be a linked. Depending
on the type, setpoint values, temperature limits and
multiple fan speeds can be set.
Comm.-Object Type KNX Size
Channel…: Fan speed 5.001 1 Byte
Channel…: Temp. setpoint 9.001 2 Byte
Channel…: Humidity 9.007 2 Byte
Channel…: Temperature 9.001 2 Byte
Channel…: Occupancy 1.018 1 Bit
Channel…: Night 1.001 1 Bit
Channel…: Automatic Fan 1.001 1 Bit
- Automated meter reading
Abb. 16: Automated meter reading
Each channel can read up to three meters. For each
counter, there are two communication objects of 4
bytes available: One value for the current consump-
tion and one value for the total consumption.
Comm.-Object Type KNX Size
Channel…: Count 12.001 4 Byte
Channel…: Count rate [1/s] 12.001 4 Byte
Channel…: Total energy [kWh] 13.013 4 Byte
Channel…: Current Energy [W] 9.024 2 Byte
Channel…: Total gas [m³] 14.076 4 Byte
Channel…: Current Gas [l/h] 9.025 2 Byte
Channel…: Total water [m³] 14.076 4 Byte
Channel…: Current water [l/h] 9.025 2 Byte
- Environmental and weather sensors
Fig.17: Environmental sensors
The following environmental sensor types can be pro-
grammed: Weather station, sunlight (northern hemi-
sphere), date, time and day, direction and geographic
position. Depending on the setting, there are different
communication objects for each sensor type.
Weather station:
Comm.-Object Type KNX Size
Channel…: Dawn 9.004 2 Byte
Channel…: Temperature 9.001 2 Byte
Channel…: Wind speed 9.005 2 Byte
Channel…: Night 1.001 1 Bit
Channel…: Rain 1.001 1 Bit
Sun intensity, northern hemisphere:
Comm.-Object Type KNX Size
Channel…: Sun west 9.004 2 Byte
Channel…: Sun south 9.004 2 Byte
Channel…: Sun east 9.004 2 Byte
Date:
Comm.-Object Type KNX Size
Channel…: Date 11.001 3 Byte
Time and Day:
Comm.-Object Type KNX Size
Channel…: Time 10.001 3 Byte
Direction:
Comm.-Object Type KNX Size
Channel…: Elevation 8.011 2 Byte
Channel…: Azimuth 8.011 2 Byte
Geographic position:
Comm.-Object Type KNX Size
Channel…: degree of longitude 14.007 4 Byte
Channel…: degree of latitude 14.007 4 Byte
- Digital input
Fig. 18: Digital input
It supports digital inputs with and without battery
monitor. The digital inputs with battery monitor send
an additional telegram when the battery is weak.

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 8/11
Comm.-Object Type KNX Size
Channel…: Contact 1.019 1 Bit
Channel…: Low battery 1.020 1 Bit
Link to actuators
To control EnOcean actuators the gateway emulates
the corresponding sensor profiles. This means the
device sends the same radio telegrams as an
EnOcean push button for example. Here, each chan-
nel uses its own sender ID.
The following functions are available in the actuator
parameters:
- RPS switch
Fig. 19: RPS switch (actuator)
Various KNX functions are selected, similar to the
sensors (Dimming, blinds, scene und switching). De-
pending on the type of actuator, the correct KNX func-
tion has to be chosen.
Comm.-Object Type KNX Size
Channel…: Switching 1.001 1 Bit
Channel…: Dimming 3.007 4 Bit
Channel…: Blinds 1.008 1 Bit
Channel…: Slats 1.009 1 Bit
Channel…: Scene 18.001 1 Byte
Absolute dimming is not available because it is not
provided in the EEPs.
- 1BS Contact input
Fig. 20: 1BS Contact input
It can simulate a simple contact input. On or off will be
sent.
Comm.-Object Type KNX Size
Channel…: Window open 1.019 1 Byte
- HVAC Actuator for valve drive
Fig. 21: HVAC actuator
In this configuration, battery-operated heating and air
actuators can be controlled. The temperature values
sent by the actuator will be sent to the bus. A tele-
gram is sent when the EnOcean device signals a low
battery.
Battery-operated heating and ventilating actuators can
be controlled. The included temperature readings are
transmitted to the bus. The device sends a value
when a "low battery" signal by the EnOcean-unit is re-
ceived.
Comm.-Object Type KNX Size
Channel…: Valve 5.001 1 Byte
Channel…: Temperature 9.001 2 Byte
Channel…: Low battery 1.020 1 Bit
Control/Logic
Control / logic functions can be selected. They include
time, control, logic, encoder, trigger and watchdog
functions.
- Timer
Fig. 22: Timer
It is possible to realize a switch-on and switch-off de-
lays. The time is set in seconds.
Comm.-Object Type KNX Size
Channel…: Switch-on delayed
input 1.001 1 Bit
Channel…: Switch-on delayed
output 1.001 1 Bit
Comm.-Object Type KNX Size
Channel…: Switch-off delayed
input 1.001 1 Bit
Channel…: Switch-off delayed
output 1.001 1 Bit

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 9/11
- Controller
Fig. 23: Controller
Two-point float
Comm.-Object Type KNX Size
Channel…: Controller On/Off 1.001 1 Bit
Channel…: Setpoint (absolute) 9.001 2 Byte
Channel…: Setpoint (relative) 9.002 2 Byte
Channel…: Value actual 9.001 2 Byte
Channel…: Switch 1.001 1 Bit
Continuously float
It is a continuous temperature controller with night-,
presence and window-/door-function.
Comm.-Object Type KNX Size
Channel…: Controller On/Off 1.001 1 Bit
Channel…: Setpoint (absolute) 9.001 2 Byte
Channel…: Setpoint (relative) 9.002 2 Byte
Channel… Temperature actual
value 9.001 2 Byte
Channel…: Night 1.001 1 Bit
Channel…: Presence 1.018 1 Bit
Channel…: Window open 1.019 1 Bit
Channel…: Control variable 5.001 1 Byte
Heat demand requirements
The maximum value of the control inputs from1 to 6 is
transmitted to the output. Only the highest value is
passed. The value of the datapoint “Demand” will be
set to “1”, when the maximal value is greater than ze-
ro.
Comm.-Object Type KNX Size
Channel…: Control value 1 5.001 1 Byte
Channel…: Control value 2 5.001 1 Byte
Channel…: Control value 3 5.001 1 Byte
Channel…: Control value 4 5.001 1 Byte
Channel…: Control value 5 5.001 1 Byte
Channel…: Control value 6 5.001 1 Byte
Channel…: Demand 1.001 1 Bit
Channel…: Max value 5.001 1 Byte
Lighting control
Several functions can be realized:
- Full-automatic control
A typical application for the fully automatic control is
the lighting of a corridor.
The light is turned on in presence when the current
brightness value is below the threshold. By manual
operation, the light can be switched on or off for a
specific time.
- Semi-automatic control
The semiautomatic mode allows the user or residents
to turn the lights on and off manually. The semi-
automatic only intervenes when the light was ‘forgot-
ten’. A typical application is an office room with sever-
al desks.
The light will not be switched on automatically. The
semi-automatic switches the light off when the current
brightness value is above the threshold or when for a
defined time presence is no longer detected.
- Simple control
The simple control only evaluates the brightness and
can be used, for example, for a store window.
The light turns on if it is too dark, and automatically
turns off when the brightness limit is reached.
Comm.-Object Type KNX Size
Channel…: Controller on/off 1.001 1 Bit
Channel…: Light on/off 1.001 1 Bit
Channel…: Presence 1.019 1 Bit
Channel…: Light actual value 9.004 2 Byte
Channel…: Switch 1.001 1 Bit
Channel…: Dimm value 5.001 1 Byte
- Logic element
Fig. 24: Logic element
AND-, OR-, XOR-, NAND-, NOR-, XNOR-Gate
Two different logic functions can be selected inde-
pendently for Type A or Type B.
Comm.-Object Type KNX Size
Channel…: Gate input A1 1.001 1 Bit
Channel…: Gate input A2 1.001 1 Bit
Channel…: Gate output A 1.001 1 Bit
Channel…: Gate input B1 1.001 1 Bit
Channel…: Gate input B2 1.001 1 Bit
Channel…: Gate output B 1.001 1 Bit

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 10/11
Inverter
Four signals can be inverted. (Input and output A-D)
Comm.-Object Type KNX Size
Channel…: Inverter input A-D 1.001 1 Bit
Channel…: Inverter output A-D 1.001 1 Bit
Toggle flip-flop
Per channel, up to 4 flip-flops can be used. If the input
receives "1", the output changes its value ("0" to "1" or
"1" to "0").
Comm.-Object Type KNX Size
Channel…: Toggle flip-flop
input A-D 1.001 1 Bit
Channel…: Toggle flip-flop
output A-D 1.001 1 Bit
- Special
Fig. 25: Special
Valuator (byte)
Up to 4 byte-valuators can be implemented on one
channel. If the values "0" or "1" are received on the
input datapoint , the configured value will be sent via
the output datapoint.
Comm.-Object Type KNX Size
Channel…: Valuator binary-in
A-D 1.001 1 Bit
Channel…: Valuator value out
A-D 5.000 1 Byte
Valuator (float)
Up to 2 float-valuators can be implemented on one
channel. If the values "0" or "1" are received on the
input datapoint, then the configured value will be sent
via the output datapoint.
Comm.-Object Type KNX Size
Channel…: Valuator binary-in
A-B 1.001 1 Bit
Channel…: Valuator value out
A-B 9.000 2 Byte
Trigger (byte)
Up to 4 byte-triggers can be implemented on one
channel. The trigger compares input value with the
configured trigger level corresponding to the config-
ured condition. Is this condition is fulfilled, the value
“1” will be sent via the output datapoint.
Comm.-Object Type KNX Size
Channel…: Trigger value in A-
D 5.000 1 Byte
Channel…: Trigger binary out
A-D 1.001 1 Bit
Trigger (float)
Up to 2 float-triggers can be implemented on one
channel. The trigger compares the input value with
the configured trigger level corresponding to the con-
figured condition. Is this condition is fulfilled, the value
“1” will be sent via the output datapoint.
Comm.-Object Type KNX Size
Channel…: Trigger value in A-
B 9.000 2 Byte
Channel…: Trigger binary out
A-B 1.001 1 Bit
Watchdog
Up to 4 group objects can be monitored on one chan-
nel. If the associated group object (GO) does not send
a value within the configured time, then the value “1”
will be sent via the output (alarm) datapoint. For the
connecting of the group objects only the internal links
can be used.
Comm.-Object Type KNX Size
Channel…: Watchdog A-D
alarm 1.001 1 Bit
Repeater function
The repeater function is used for extend distances be-
tween sensors and actuators. The KNX ENO 634 is a
level-1 radio repeater. This means, that only tele-
grams that come directly from a transmitter will be re-
peated. Telegrams sent by other repeaters are not re-
peated again.
The repeater function of the KNX ENO 634 is activat-
ed by the general parameters in the ETS. If the func-
tion is enabled it will be displayed in the main menu of
the display (Fig. 26).

KNX ENO 634
WEINZIERL ENGINEERING GmbH EN
2013-08-14 Page 11/11
Fig. 26: Active repeater function
Bus monitor function
The integrated bus monitor function is used for sys-
tem diagnostics directly on the device. The device can
display both EnOcean and KNX telegrams.
A short press of T1 in menu activates the dual
EnOcean and KNX bus monitor ("E+K BUSMON").
The last five incoming and outgoing messages are
displayed at the bus monitor. With a long press of T2
can be switched between the EnOcean bus monitor
("ENO BUSMON"), the KNX bus monitor ("KNX
BUSMON") and the dual E+K bus monitor.
To return to the main menu of the gateway, the T1
button is used. The bus monitor is automatically
closed after 5 minutes of inactivity.
EnOcean bus monitor
If a telegram is received from an EnOcean device, the
signal strength (RSSI) value is shown in the first posi-
tion of the line. The RSSI (Received Signal Strength
Indication) is represented by a value between 1 and 4
(1 = min., 4 = best). The first 8 digits of numeric value
is the hexadecimal ID of the sending device. The
transmitted data is displayed also in hexadecimal cod-
ing in the second numeric part.
If a message is sent by the gateway, it is displayed in
the first position of the line with an "S". The ID used
by the gateway and the transferred data are also
shown.
Fig. 27: EnOcean bus monitor
KNX bus monitor
The KNX bus monitor displays the messages at the
object level. Therefore, only group telegrams are visi-
ble which address the gateway or which are sent by it.
If a telegram is received from KNX bus, it will be
shown in the KNX bus monitor with an "I". Behind it
the decimal group object number and the data packet
will be shown with up to 4 hexadecimal bytes.
If a KNX group address is associated with several
group objects in the gateway, then one line will be
shown for each link.
When sending a message to the KNX bus, an "O" is
displayed with the decimal object number and the da-
ta packet in hexadecimal coding.
Fig. 28: KNX bus monitor
Representation of the messages on the display:
Receiving of EnOcean-telegram
(1-4) Device ID Data packet
Sending of EnOcean-telegram
S Device D Data packet
Receiving of KNX-telegram
I GO-No. Data packet
Sending of KNX-telegram
O GO-No. Data packet
Weinzierl Engineering GmbH
DE-84508 Burgkirchen
E-Mail: [email protected]
Web: www.weinzierl.de
Table of contents
Other Weinzierl Gateway manuals