
____________________________________________________________________________________
Westell
4
universal for 19” and 23” rack mount spacing
(see figure 4.2.1) and can be mounted so the
panel can be installed for a flush mounting or
5” offset. Adjust the position and orientation of
the correct mounting brackets on the fuse
panel, such that it will fit the rack you wish to
mount the panel in. Please see drawing 1105-
16 on page 8 for mounting bracket
configuration.
19" Mounting Position
23" Mounting Position
Figure 4.2.1
4.3. Mount the fuse panel in the required
position on the rack using the thread forming
rack screws and tooth lock washers provided.
WARNING:For safety reasons, all wiring
should be performed with the power source
removed, and performed by a trained Installer
experienced with DC power systems.
Note: A readily accessible disconnect device
shall be incorporated in the building
installation wiring.
4.4. Remove the distribution fuse feeding the
input cables that are to be connected to the
new panel. Attach the input cables to the
input terminal block in accordance to the
National Electrical Code, ANSI/NFPA, and
Canadian Electrical code. Hook up the input
cables to the input terminal block on the fuse
panel (“BAT” & “RTN” for each bus). Each
high current input terminal uses a two hole
compression lug (1/4” on 5/8”, torque to 5.5 ft-
lbs). A two hole lug must be used for proper
operation
4.5. The fused battery outputs (BAT) and
ground returns (RTN) are also located on the
back of the panel. Each fuse holder and
terminal position is individually numbered.
Connect your load side equipment to the fuse
panel, and record which equipment is
connected to which input on the designation
card (supplied).
4.6. Alarms; There are three connections for
each of the alarm relays; common (C),
normally open (NO), and normally closed
(NC). Connect the alarm extension wires as
per your alarming scheme (22 or 24awg
typical). Example; Connect the signal that you
want extended in an alarm condition to the “C”
pin. When there’s an alarm, “C” will become
shorted to “NO”. Typically a ground is
connected to the “C”, and the “N.O.” signal is
extended to the alarm monitoring system,
providing a “Ground Alarm”. A “Bus Alarm” is
caused by a fuse failure or an input power
failure on that bus. “Normal” indicates the
state when the panel is powered up with no
blown fuses. The three relay contacts are dry,
so you can parallel the contacts, etc. Please
limit the current thru the relays to 1Amp or less
(Alarm Battery Supply fuse should be 1 Amp
max). Alarm extensions discussed above, are
optional; only use them if you wish (see 3.4 for
details).
4.7. Chassis Ground; for safety reasons, the
chassis should be electrically connected to the
rack ground. From step 4.3, the panel should
already be bonded to the rack via the #12-24
thread forming rack screws and outside tooth
lock washers. In addition to grounding via the
mounting brackets, an appropriate cable size
as outlined in section 5 (typically 10awg or
larger) and the ¼” bolt and locks on rear of
chassis (1/4” bolt torque;5.5ft-lbs or 7.5Nm)
should also be used. Consult the National
Electric Code, ANSI/NFPA, and Canadian
Electrical code for AWG sizes.
4.8. The input wiring feeding this panel should
be protected by a Listed fuse/breaker rated for