Westinghouse AMPTECTOR Manual

AMPTECTOR
TESTER
INSTRUCTION
LEAFLET
3
.
Push
“
RESET
then
“
TEST
and
increase
current
steadily
but
rather
rapidly
until
relay
“
clicks
"
off
in
Test
Kit
.
(
If
current
is
preset
to
about
3
/
4
of
setting
,
using
calibrate
switch
,
the
final
setting
can
be
approached
slower
for
better
accuracy
)
.
(
See
Caution
#
3
)
.
.
4
.
Reset
—
Hold
INST
switch
in
“
READ
"
position
—
push
"
TEST
"
button
and
read
current
.
(
See
Caution
#
4
)
.
(
F
)
12
X
Discriminator
Test
(
If
the
Amptector
does
not
nave
an
instantaneous
trip
function
,
perform
this
test
)
.
(
See
Cautions
«
3
&
#
4
)
.
1
.
Do
Steps
E
.
1
.
and
E
.
2
.
2
.
With
the
Current
Adjust
set
at
0
.
push
“
RESET
"
,
then
“
TEST
"
.
.
Gradually
,
but
within
about
3
seconds
raise
the
current
to
over
about
65
amps
using
the
Current
Adjust
control
.
The
Amptector
should
not
trip
instantaneously
.
After
about
2
seconds
activate
the
Stop
switch
(
Long
Delay
would
eventually
trip
)
.
Leave
the
Current
Adjust
setting
where
it
is
.
3
.
Push
“
RESET
.
Wait
10
sec
.
Push
"
TEST
.
The
Amptector
should
trip
instantaneously
.
4
.
Using
the
Calibrate
switch
,
set
Current
Adjust
for
45
amps
.
Push
“
RESET
.
Wait
10
seconds
.
Push
“
TEST
.
The
Amptector
should
not
trip
instantaneously
.
Push
the
Stop
switch
after
about
2
seconds
.
(
G
)
To
Check
Short
Delay
Pick
-
up
(
Set
Instant
,
to
Max
.
)
.
1
.
Place
Short
Delay
switch
in
OPERATIVE
position
,
time
to
min
.
and
proceed
similar
“
to
Instantaneous
above
.
2
.
Set
Short
Delay
switch
to
“
READ
AMPS
’
*
to
read
ammeter
as
in
E
.
4
.
above
.
(
See
Caution
#
4
.
)
(
H
)
To
Check
Short
Delay
Time
NOTE
:
It
is
possible
,
under
certain
conditions
,
that
the
fixed
discriminator
or
instantaneous
function
may
trip
instan
-
taneously
during
short
delay
time
testing
.
To
avoid
this
,
merely
hold
the
Instantaneous
Operative
/
Read
Amps
Toggle
switch
in
the
“
READ
AMPS
”
position
while
performing
the
test
in
Step
H
.
4
.
1
.
Set
Short
Delay
Pick
-
up
dial
at
4
X
(
20
amperes
)
.
2
.
Set
“
CURRENT
ADJUST
at
10
X
(
50
amperes
)
with
Calibrate
switch
.
(
See
Caution
#
3
)
.
3
.
Turn
Timer
on
and
Short
Delay
switch
to
“
OPERATIVE
"
.
4
.
Push
"
RESET
and
manual
timer
reset
button
,
then
"
TEST
ana
timer
will
give
an
approximate
reading
of
the
delay
.
NOTE
:
This
is
not
accurate
enough
for
close
timing
of
short
delay
but
it
will
show
the
difference
between
the
three
band
calibrations
.
(
I
)
To
Check
Ground
Pick
-
up
1
.
Hold
Ground
Test
momentary
switch
in
down
position
during
steps
2
.
3
and
4
.
2
.
Place
“
CURRENT
ADJUST
knob
at
zero
.
3
.
Push
"
RESET
then
“
TEST
.
4
.
Turn
“
CURRENT
ADJUST
until
unit
trips
(
from
0.9
to
1.2
amps
)
.
5
.
For
Amptectors
with
adjustable
pick
-
up
.
see
chart
on
top
of
Amptector
.
(
J
)
To
Check
Ground
Time
1
.
With
Ground
Test
momentary
switch
and
calibrate
switch
in
down
position
,
turn
Current
Adjust
to
get
2.5
amperes
.
2
.
Turn
"
TIMER
”
on
.
(
If
timer
is
not
at
zero
,
push
manual
reset
button
)
.
CAUTIONS
:
1
.
DO
NOT
TEST
AMPTECTOR
WHILE
BREAKER
IS
CARRYING
CURRENT
.
2
.
IF
POSSIBLE
.
TESTING
SHOULD
BE
PERFORMED
WITH
AMPTECTOR
UNDER
TEST
CONNECTED
TO
A
DIRECT
TRIP
ACTUATOR
AS
IT
IS
ON
A
BREAKER
.
IF
A
DIREGTTRIP
ACTUATOR
IS
NOT
AVAILABLE
.
CONNECT
A
15
TO
30
OHM
RESISTOR
(
1
/
8
WATT
MINIMUM
)
ACROSS
TERMINALS
"
OP
"
AND
"
ON
"
.
IF
AMPTECTOR
IS
NOT
LOADED
IN
THIS
MANNER
^
SOME
FUNCTIONS
AND
INDICATORS
MAY
NOT
PERFORM
PROPERLY
.
3
.
TO
MINIMIZE
THERMAL
STRESS
ON
TEST
KIT
AND
AMPTECTOR
.
HOLD
"
CALIB
"
(
MOMENTARY
)
TOGGLE
SWITCH
FOR
NO
MORE
THAN
15
OR
20
SECONDS
AT
A
TIME
.
4
.
AFTER
READING
CURRENT
BY
ANY
MEANS
.
IF
CURRENT
PERSISTS
.
USE
“
STOP
"
SWITCH
TO
CUT
OFF
CURRENT
.
5
.
WHEN
CHECKING
OUT
SETTINGS
ON
AN
AMPTECTOR
FOR
USE
.
THE
GENERAL
PROCEDURE
IS
TO
START
WITH
THE
HIGH
CURRENT
SETTINGS
AND
WORK
DOWN
TO
THE
LOWEST
CURRENT
SETTING
.
THIS
AVOIDS
UNNECESSARY
DIAL
CHANGES
AFTER
CALIBRATION
.
THE
LAST
CHECK
WOULD
PROBABLY
BE
STEP
(
K
)
.
TESTING
AMPTECTOR
Times
marked
on
Amptector
dials
are
TOP
of
the
band
-
hence
,
expect
shorter
times
when
testing
.
*
(
A
)
3
Phase
The
selector
switch
permits
checking
to
see
if
all
Amptector
phase
inputs
are
operative
.
Since
all
feed
into
a
common
pick
-
up
and
timing
circuit
,
it
is
only
necessary
to
use
one
phase
to
check
out
all
the
solid
state
circuitry
functions
.
It
is
only
necessary
to
use
one
circuit
function
(
say
.
long
delay
pick
-
up
)
to
verify
that
each
phase
(
A
.
B
and
C
)
performs
similarly
(
say
,
each
phase
trips
at
about
5
amps
with
long
belay
pick
-
up
set
at
1
X
)
.
(
B
)
Pick
-
up
values
are
mid
-
band
which
has
+
10
%
tolerance
:
(
See
table
)
(
C
)
To
Check
Long
Delay
Pick
-
up
(
Switch
to
Lo
.
Turn
Timer
OFF
)
.
1
.
Push
"
RESET
"
and
then
“
TEST
*
.
2
.
Slowly
increase
current
until
Long
Delay
neon
lamp
(
clear
)
glows
steadily
indicating
Amptector
pick
-
up
.
3
Use
"
STOP
"
switch
to
cut
off
current
.
(
D
)
To
Check
Long
Delay
Time
(
Set
30
amp
.
[
6
X
]
with
"
CALIBRATE
"
switch
)
(
See
Caution
#
3
)
.
1
.
Push
"
RESET
"
and
turn
Timer
“
ON
"
.
2
.
Push
“
TEST
"
—
Test
Kit
will
stop
when
Amptector
fires
the
output
Timer
should
read
less
than
dial
setting
but
not
under
2
/
3
of
the
setting
,
i
.
e
.
if
set
at
36
it
should
be
more
than
24
seconds
.
3
.
Any
other
multiple
of
sensor
may
be
checked
,
if
desired
—
see
performance
curves
for
approximate
trip
time
to
be
expected
.
(
E
)
To
Check
Instantaneous
(
Turn
Timer
OFF
)
1
.
Set
Long
Delay
to
maximum
so
Long
Delay
will
not
trip
too
fast
.
2
.
Set
Short
Delay
switch
to
“
READ
AMPS
"
.
I
.
L
.
33
-
791
-
E
EFFECTIVE
AUGUST
.
1981
SUPERSEDES
I
.
L
.
33
-
791
D
DATED
JANUARY
.
1981
Westingtiouse
Electric
Corporation
Switchgear
Division
,
East
Pittsburgh
,
Pa
.
15112
I
i
Courtesy of NationalSwitchgear.com
AMPTECTOR
fESTER
INSTRUCTION
LEAFLET
I
.
L
.
33
-
791
-
E
For
^
balance
of
checks
on
test
kit
.
use
a
known
properly
calibrated
amptector
.
Banana
plug
assembly
connected
to
the
Amptector
.
timer
switch
off
.
short
delay
toggle
switch
in
"
READ
AMPS
"
position
.
Hi
-
Low
switch
in
Lo
.
circuit
selector
set
at
"
A
**
.
Amptector
settings
:
Set
long
delay
pickup
at
1.0
(
5
ampsi
10
%
)
.
long
delay
seconds
at
36
(
triptime
for
6
X
current
[
30
amps
]
)
;
short
delay
pick
-
up
at
10
.
seconds
at
50
.
Instantaneous
pick
-
up
at
10
:
Ground
pick
-
up
at
"
A
"
(
1
amp
)
,
seconds
at
.
50
.
Turn
power
ON
.
hold
"
CALIB
"
(
momentary
)
toggle
switch
in
Calibrate
position
andturn
Current
Adjust
knob
slowly
from
2
ero
to
maximum
.
Ammeter
should
read
from
zero
to
approximately
7
amperes
.
Turn
Current
Adjust
knob
tozero
and
put
Hi
-
Lowswitch
in
Hi
position
,
hold
“
CALIBRATE
”
switch
in
Calibrate
position
and
turn
Current
Adjust
knob
from
zero
to
maximum
,
ammeter
should
read
from
0
to
about
70
amperes
,
depending
upon
the
120
V
line
voltage
and
the
test
unit
'
s
R
1
setting
.
(
See
Caution
#
3
)
.
Long
delay
pick
-
up
.
set
Current
Adjust
to
0
.
Hi
-
Low
switch
to
Lo
.
push
“
RESET
"
button
,
push
"
TEST
"
button
.
increase
“
CURRENT
ADJUST
”
knob
slowly
until
long
delay
pick
-
up
pilot
lamp
(
clear
)
is
lit
.
This
lamp
should
light
at
5
amperes
^
10
%
.
Lamp
will
go
out
when
current
is
lowered
below
pick
-
up
.
Repeat
with
Selector
switch
on
Phase
B
and
again
with
switch
on
Phase
C
.
Long
delay
time
,
set
“
Circuit
Selector
”
to
*
'
A
”
.
Hi
-
Lowswitch
toHi
.
hold
“
CALIBRATE
”
switch
in
Calibrate
position
and
turn
“
CURRENT
ADJUST
”
knob
until
ammeter
reads
30
.
Release
"
CALIBRATE
”
switch
,
press
“
RESET
”
button
.
Amptector
long
delay
set
for
36
seconds
,
turn
timer
on
.
push
“
TEST
"
button
.
Control
the
current
to
see
that
it
stays
at
30
amperes
.
Amptector
should
turn
off
timer
and
current
(
“
TEST
”
pilot
lamp
should
go
out
)
between
24
to
36
seconds
.
Push
“
RESET
"
button
.
“
RESET
”
pilot
iamp
should
go
on
.
Push
manual
reset
button
on
timer
,
timer
should
reset
to
zero
.
*
Tester
can
be
used
on
50
Hz
but
timer
reading
must
be
multiplied
by
6
/
5
.
Dials
for
short
delay
and
inst
.
pickup
are
blocked
at
10
X
on
50
Hertz
Amptectors
)
.
3
.
Release
"
CALIBRATE
"
switch
,
continue
to
hold
Ground
Test
switch
down
.
4
.
Push
“
RESET
”
and
manual
timer
reset
button
,
then
“
TEST
"
and
timer
will
give
an
approximate
reading
of
the
delay
.
(
K
)
Reset
Test
(
with
any
long
delay
pick
-
up
and
time
setting
)
.
1
.
Set
current
at
30
amps
and
find
long
delay
trip
time
as
inSection
D
.
2
.
Start
test
again
,
but
when
time
is
about
80
%
of
the
above
trip
time
,
quickly
reduce
current
to
about
80
%
of
long
delay
pick
-
up
setting
.
(
Pick
-
up
light
should
go
out
)
.
3
.
Quickly
raise
current
back
to
30
amps
and
allow
Amptector
to
trip
.
4
.
The
total
time
on
counter
should
be
between
150
and
200
%
of
trip
time
in
(
1
)
above
.
(
If
time
setting
in
[
1
]
is
very
low
,
run
test
at
15
amps
instead
of
30
amps
)
.
CHECKING
TEST
KIT
(
When
first
received
or
for
Maintenance
Check
)
(
A
more
rigorous
check
-
out
would
be
to
perform
ALL
Amptector
tests
on
a
standard
Amptector
)
.
With
the
Polarized
11
Pin
Banana
plug
assembly
not
connected
to
an
Amptector
.
Timer
switch
off
.
Short
Delay
switch
in
operative
position
.
Hi
-
Low
switch
in
Lo
,
Current
Adjust
set
to
0
.
plug
tester
into
120
volt
.
60
*
Hertz
source
.
Turn
power
switch
on
,
power
pilot
lamp
should
light
(
red
)
and
reset
pilot
lamp
should
light
(
amber
)
.
If
reset
pilot
lamp
is
not
lit
.
push
“
RESET
”
button
,
reset
pilot
lamp
(
amber
)
should
light
.
Turn
timer
switch
on
,
timer
should
not
run
.
Push
“
TEST
”
button
,
test
pilot
lamp
(
red
)
should
light
,
timershould
operate
counting
seconds
,
and
reset
pilot
lamp
should
go
out
.
Operate
“
STOP
”
toggle
switch
(
momentary
)
,
timer
should
stop
and
test
pilot
.
'
amp
should
go
out
.
Push
manual
reset
button
on
timer
,
timer
should
reset
to
zero
.
If
any
of
the
above
checks
do
not
work
,
operate
Stop
switch
and
Reset
switch
and
repeat
check
.
REPAIR
PARTS
The
following
parts
are
available
at
Westinghouse
East
Pittsburgh
.
Pa
.
(
a
)
Handle
Plug
and
Cord
Assembly
(
b
)
Timer
(
fori
40
D
481
G
02
only
)
(
c
)
Relay
*
(
d
)
Relay
*
.
(
e
)
Details
for
replacing
prong
in
handle
and
cord
assembly
.
(
11
ea
per
test
kit
)
Connecting
Stud
Banana
Plug
Style
Number
682
C
898
G
01
Style
Number
3707
A
11
H
01
Style
Number
784
A
301
H
01
Style
Number
784
A
302
H
01
Style
Number
794
A
477
H
01
Style
Number
794
A
478
H
01
TABLE
OF
LIMITS
FOR
STEP
B
PICK
-
UP
LIMITS
(
AMPS
)
SHORT
DELAY
PICK
-
UP
LIMITS
(
AMPS
)
LONG
DELAY
&
INSTANTANEOUS
18
to
22
4
X
=
20
AMP
.
5
X
=
2.5
AMP
2.25
to
2.75
22.5
to
27.5
5
X
=
25
6
X
=
3.0
2.7
to
3.3
27
to
33
.
7
X
=
3.5
3.15
to
3.85
6
X
=
30
31.5
to
38.5
.
8
X
=
4.0
7
X
=
35
3.6
to
4.4
36
to
44
.
9
X
*
4.5
4.05
to
4.95
8
X
*
-
40
45
to
55
1
.
OX
=
5.0
10
X
=
50
4.5
to
5.5
54
to
66
1.25
X
=
6.25
5.6
to
6.9
12
X
=
60
Westinghouse
Electric
Corporation
z
!
*
i
•
r
Courtesy of NationalSwitchgear.com
/
-
/
-
/
O
•
i
w
.
•
ijfr
n
£
*
#
>
/
fltH
-
J
/
f
_
:
t
'
iwZvt
A
*
"
jg
&
sfit
>
^
y Z
“
’
'
7
_
.
’
Y
”
IAST
/
AZ
*
'
o
/
’
-
F
0
XCAV
.
5
ip
_
.
.
.
7
~
oI
/
lXML
.
A
)
-
#
/
A
&
s
/
*
/
rro
(
<
L
&
)
.
71
?
.
^
)
L
)
js
ZPPJ
^
.
^
AT
^
PTPK
-
6
PfAA
£
E
.
.
.
.
.
.
•
^
)
i g
>
^
<
flti
.
4
y
S
/
cAAp
TO
.
/
0
£
)
_
.
A
^
S
~
.
/
/
Z
^
y
.
.
.
„
.
5
ZPr
.
PE
.
PE
.
-
jr
-
jQ
_
J
CJ
_
_
c
.
)
jr
#
-
oXT
'
/
)
i
j
/
&
y
P
/
b
&
vP
t
'
Vft
^
ALO
/
vr
/
)
Z
£
#
*
z
'
~
ro
v
i
~
5
>
V
O
’
/
<
5
A
-
>
•
l
•
•
'
.
V
.
7
•
•
•
—
•
r
’
-
.
»
.
.
'
•
-
<
r
-
r
1
:
-
V
:
„
7
7
)
"
"
/
ob
'
ZK
.
&
s
>
Y
)
Moj
.
.
/
?
s
'
/
?
*
^
y
fj
PlPPA
/
AZrrosr
AMQ
£
„
.
SA
0
WlY
.
0
-
-
/
)
*
?
/
htrcz
.
A
/
PA
.
A
A
A
7
J
~
£
p
oyzAA
.
_
oJ
_
~
/
9
r
.
r
P
/
LQ
^
TAZAE
y
*
?
-
A
*
rt
)
S
3
~
&
r
°
z
&
sr
t
/
.
A
«
6
~
ro
•
\
•
.
o
W
-
/
,
<
2
*
Z
>
7
<
A
/
-
/
?
/
yVAA
jjs
*
s
/
r
£
/
f
r
~
e
/
A
/
/
A
/
nf
A
/
O
.
.
.
_
.
w
.
_
P
)
S
zZ
1
A
PAAI
.
PJ
*
.
.
P
~
P
3
°
PA
A
-
/
tcpZ
)
c
7
^
Z
/
S
.
v
rc
'
/
tjj
gwr
/
Mwr
j
3
A
?
*
#
Ezs
jr
/
.
v
)
TV
£
r
/
/
n
IE
0
/
0
{
y
A
^
s
/
t
ris
7
~
7
~
/
/
»
.
£
>
*
L
5
V
/
Cst
-
0
EO
/
O
/
*
oft
.
Z
T
/
ZZAJ
APS
sc
.
Tp
*
P
'
_
P
CPC
.
ALA
'
A
*
*
$
*
*
..
7
S
£
T
77
A
\
r
j
~
o
S
/
tltT
_
_
•
:
»
s
5
trnv
^
fi
/
ek
-
cyf
*
S
/
po
^
T
jQLc
/
^
y
iTr
^
E
^
r
oP
/
r
^
J
#
Art
'
ET
~
.
!
,
,
tfhA
—
fry
:
c
i
—
i
7
vv
2
/
^
.
szss
^
pp
;
j
?
/
=
_
/
V
/
~
SZ
/
oft
-
T
/
7
^
^
3
Zzsz
'
r
py
zs
*
~
sp
S
%
T
4
«
c
^
y
<
OpArfy
A
~
r
J
.
Z
3
~
c
)
/
/
}
Ao
ro
E
/
i
)
P
<
/
3
?
i
to
;
rr
?
j
7
^
5
-
7
"
"
I
OKfi
/
M
-
l
'
l
/
l
ys
/
T
/
Crt
•
!
<
g
/
/
-
7
APPpAzZL
.
•
’
•
<
/
;
^
/
-
^
Q
74
Z
)
r
^
/
/
1
7
~
JAAPALZ
PPA
&
y
sA
<
2
/
'
Eb
T
/
Z
-
PP
v
\
ri
/
t
-
o
*
—
/
<
77
0
£
'
7
~
os
OsJ
_
/
?
£
r
/
9
-
AZK
t
/
/
i
£
?
Aj
r
/
9
-
£
>
pu
±
i
J
;
Oq
•
/
:
Courtesy of NationalSwitchgear.com
/
?
oftr
DisAy
Pic
/
c
:
(
yP
c
G
/
JJ
,
i
)
d
/
jzcK
s
/
t
.
o
/
eLTj
)
xifry
/
9
~
T
4
$
Vy
S
/
&
&
#
*
-
£
>
7
-
S
-
/
P
AT
'
A
)
6
x
ffc
/
Ps
OU
)
/
£
"
OL
^
:
/
jiM
P
£
7
-
5
3
fry
'
f
3
c
-
yy
4
*
/
•
•
9.0
.
A
’
2
0
A
A
#
A
/
•
/
/
/
/
u
'
7
/
/
yOAPA
-
V
7
~
/
sht
.
/
J
SPT
-
SAo
/
zr
J
&
T
y
X
)
SOT
/
f
~
)
/
PO
y
~
o
/
/
f
3
)
.
S
o
s
'
S
#
-
O
#
-
T
oz
^
-
A
-
y
TO
off
A
AT
P
y
)
sor
~
c
-
&
KA
.
tMr
A
/
xrosT
-
7
:
0
y
~
o
/
h
^
P
tv
/
rpf
cp
-
^
/
s
.
si
1
/
T
)
TPAX
TO
/
?
-
yS
:
JPX
^
£
S
ZT
-
T
&
t P
>
/
J
£
(
LCAfcOC
_
.
.
.
.
C
-
)
Pc
'
SA
-
A
.
TSST
_
V
*
7
)
A
PS
A
7
~
S
7
~
F
)
SfrotfuD
7
~
/
\
?
Ot
/
T
/
9
~
T
/
S
~
C
5
ic
.
S
ST
~
s
^
oA
.
r
-
'
OSz
-
'
f
-
y
.
A
-
T
~
•
33
-
/
0
)
As
pcsc
STOPS
X
-
7
—
^
,
33
SZ
-
C
*
/
<
»
«
.
•
*
<
•
-
•
*
.
••
•
1
1
“
•
i
Courtesy of NationalSwitchgear.com

Popular Test Equipment manuals by other brands

Artesis AMT Toolkit user manual

Artesis

Artesis AMT Toolkit user manual

AlcoSense Verity user manual

AlcoSense

AlcoSense Verity user manual

Hach HQ Series user manual

Hach

Hach HQ Series user manual

VOLTCRAFT KBM-110 operating manual

VOLTCRAFT

VOLTCRAFT KBM-110 operating manual

WIKA PASCAL 100 operating instructions

WIKA

WIKA PASCAL 100 operating instructions

Bacharach PCA 2 24-9448 Operating & maintenance instructions

Bacharach

Bacharach PCA 2 24-9448 Operating & maintenance instructions

STEP SYSTEMS ECO pH manual

STEP SYSTEMS

STEP SYSTEMS ECO pH manual

Bosch 0 986 618 001 manual

Bosch

Bosch 0 986 618 001 manual

MESSKO MZT1650S operating instructions

MESSKO

MESSKO MZT1650S operating instructions

SW-Stahl 32255L instruction manual

SW-Stahl

SW-Stahl 32255L instruction manual

Powerfix Profi PAWSB 12 A1 operating instructions

Powerfix Profi

Powerfix Profi PAWSB 12 A1 operating instructions

TESTO 570 instruction manual

TESTO

TESTO 570 instruction manual

Rohde & Schwarz RT-ZF7 manual

Rohde & Schwarz

Rohde & Schwarz RT-ZF7 manual

Philips PM 3256U Service manual

Philips

Philips PM 3256U Service manual

Chicago Electric 90636 operating instructions

Chicago Electric

Chicago Electric 90636 operating instructions

VOH III SAV user manual

VOH

VOH III SAV user manual

Krohn-Hite 3103 Operating and maintenance manual

Krohn-Hite

Krohn-Hite 3103 Operating and maintenance manual

Bacharach FYRITE Gas Analyzer CO2 and O2 Indicators operating & maintenance manual

Bacharach

Bacharach FYRITE Gas Analyzer CO2 and O2 Indicators operating & maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.