
3
Returns require written authorization from The Whalen Company. Unauthorized returns will be
refused. All material returned will be inspected. Any damage, missing parts, rework or
repackaging resulting from prior installation, abuses or neglect will constitute just cause for The
Whalen Company to issue partial credit.
Installation
Prior to installation check to make sure unit is as ordered and that the fan rotates freely. This
unit must be installed in a manner which will allow the blower access panel to be removed in
order to clean the coil surface, blower, or motor. When installed in a concealed building space
acting as return-air plenum, the installation must conform to the requirements of NFPA Standard
90B. It must be installed level and condensate drain lines must be trapped with proper slope for
rapid drainage. Water and drain connections must be made to the unit in accordance with local
codes.
Normal Piping Practice
The bottom coil connection, on the leaving-air-side, is the water-supply inlet. All piping must be
supported independently from the coil to prevent damage to the soldered joints. Chilled water
and condensate drain lines must be insulated for efficient operation and to prevent condensate
formation. Pipe insulation must be closed-cell or have a vapor barrier. All joints must be
properly sealed against air leaks to the piping. Control valves, shut-off valves, and un-insulated
water piping must be installed over the drain pan or utilize an accessory drain pan extension.
Condensate lines, one primary and one secondary, must be properly pitched to the building
drain. The Whalen Company will not assume any liability for damage caused as a result of the
condensate drain line not being properly pitched or trapped. The use of a secondary drain pan
under the entire unit, with a separate drain line, is advised in areas where water damage is very
critical. See the Fan Coil Piping Instructions on Page 5.
CAUTION
It is the sole responsibility of the customer to provide the necessary protection to prevent vandalism
and weather protection of the equipment. Under no circumstance should the fan coil be left exposed to
the elements. Protect the units from dirt, plaster and other debris during the entire construction phase.
Prior to start-up, the entire interior of the unit should be inspected for debris and dirt. Clean, if
necessary. Any failure of the unit or damage to the building as a result of improperly protecting and
cleaning the unit is not covered by the warranty.
WARNING
These units weigh 140-307 lbs., a minimum of two people are recommended for handling and
installation.
WARNING
If the unit is installed during the winter months, care must be taken so that the unit is not subject to
freezing temperatures while filled with water during construction. Coils damaged due to freezing are not
covered by the warranty. The Whalen Company fan coil units are suitable for zero clearance to
combustible material. All air must be bled out of the water system. Any air trapped in the hot- or
chilled-water coil can be released from the system by using the manual air vent on the coil.
For hot and humid areas: Do not operate during construction or renovation with windows and doors
open causing outside air to enter the building. When the outside air enters the building, it imposes high
cooling and dehumidifying loads on the units.