POWERPATH™
NAC POWER SUPPLIES
Description
POWERPATH™ Series PS-12/24-8CP and PS-12/24-8MP are
power limited 8 amp power supply/chargers used to expand
the supervised power capability of a fire alarm control panel
(FACP) for notification appliance circuits (NAC).
The PS-12/24-8CP provides up to 200 milliamps of continuous
auxiliary output that can be used for control functions during
alarm (or up to 60 milliamps for 60 hour battery requirements).
The PS-12/24-8MP provides up to 3.5 amps of auxiliary output
that is available only during nonalarm condition for such
applications as door holder systems.
Both models provide regulated and filtered 12 or 24 VDC output
to four (4) Class “B” or two (2) Class “A” circuits. Each Class “B”
circuit has a rating of three (3) amps with a total output of up to
eight (8) amps. Each Class “A” circuit is rated at three (3) amps.
Two (2) Class “A” or Class “B” inputs from an FACP and two (2)
dry contact inputs are provided to trigger the outputs. The units
accept either 12 or 24 VDC inputs and provide 12 or 24 VDC
outputs. Both units support a full 8 amps of notification power
even if the battery is in a degraded mode and only AC power is
connected.
POWERPATH™ Series PS-12/24-8CP and PS-12/24-8MP are
compatiblewithallWheelock12or24VDCLifeSafetyNotification
Appliances and with their Patented BUILT-IN SYNCHRONIZED
MODE feature, they can control and operate all of Wheelock’s
Synchronized Notification Appliances, including silencing
audibles while maintaining strobe activation.
Series PS-12/24-8CP
Series PS-12/24-8MP
(Batteries Not Included)
Features
Approvals
•Approvals Include: UL Standard 864, California State Fire
Marshal (CSFM), (New York City (MEA), Factory Mutual
(FM), Chicago (BFP) See Approvals by model in
Specification and Ordering Information
• Compliant with NFPA 72
Inputs
•Compatible with 12 or 24 VDC FACP
•115 VAC @ 50/60 Hz or 240 VAC @ 50/60 Hz
• Two 12 or 24VDC NAC Initiating Circuits from host panel
• Two “Dry” contact input circuits
• Accepts 2 Class “A” or 2 Class “B” NAC circuit inputs
• Additional activation options are: NC contacts or open
collector of a transistor
Outputs
• 8 amperes rated supply current @ 12 or 24 VDC
• Filtered and regulated power supply outputs
• Class 2 rated power limited outputs
• Dip switch selectable options
•Field selectable 12 or 24 VDC outputs
•4 Class “B” or 2 Class “A” or 1 Class “A” and 2 Class
“B” Notification Appliance Circuits)
•Each Class “B” output has a maximum rating of three
(3) amperes
• Each Class “A” output has a maximum rating of
three (3) amperes
•Code 3 (Temporal) option
• Steady output option
Copyright 2004 Wheelock, Inc. All rights reserved.
Outputs Cont.
• Built-In Wheelock Synchronization Protocol
• Input and output synchronization (including pass
through)
Supervision
• FACP NAC supervision steered to either input #1 or #2
• Common input and output trouble circuit
• Input and output LED indicators
• AC fail supervision (Form “C” contacts rated @ 1 amp
@ 24 VDC or 115 VAC)
• Battery presence and low battery supervision (Form
“C” contacts rated @ 1 amp @ 24 VDC or 115 VAC)
• Ground fault detection
• 4 latching LED’s for NAC trouble annunciation
Power
•Not Battery Dependent - Full 8A even if battery is
degraded
• Automatic switch over to standby batteries when AC
fails
•Supports sealed lead acid or gel type batteries
• Fused battery protection
• Thermal and short circuit protection with auto reset
•Supports both 7AH or 12AH batteries in the same
cabinet (Cabinet Size: 16" H x 12.25" W x 5" D)
Auxiliary Power
• Up to 200 mA continuous with PS-12/24-8CP
• Up to 3.5 amps nonalarm with PS-12/24-8MP
ACTION MESSAGES
COMMUNICATIONS
SYSTEMS
ADA
THE CITY OF
NEW YORK
DEPARTME NT OF BUILDINGS
U
L
®
INC.
Helping People Take Action
SM
POWERPATH
1
2
3
4
ON
OUT1-4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUT4
OUT2
OUT3
+
-
-
+
OUT1
-
+
+
IN1
-
TO NEXT APPLIANCE
OR EOLR
RET1
+
-
F
C
P
A
OR RETURN
TO FACP
(CLASS "A")
-
+
1234
ON
SW9
POWERPATH
1234
ON
OUT1-4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OR EOLR
+
-
IN1
RET1
-
+
OUT1
+
-
A
P
C
F
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OUT2
-
+
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
+
-
OUT3
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OUT4
-
+
1234
ON
SW9
Normal Mode (Class B)
Normal Mode (ClassA)
POWERPATH™ OperatingModes(refertoInstallationManual):
Normal Mode: Provides constant 12 VDC or 24 VDC output upon initiation by a
voltagetoinputIN1orIN2orbyacontactopening on DRY1 or DRY2. Theunitreturns
tostandbymode when theinputis deactivated.
Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock
audibleandstrobenotification appliances. Audibles canalsobesilencedin this mode
whilethestrobescontinuetoflash.
In>Out Sync Mode: Acceptsacodedsignalorsynchronizationsignal on theinputto
provide a coded output or synchronized output. This signal may come from a FACP,
anotherPOWERPATHora Wheelock SMor DSM synchronizationmodule. Caution:
Donot use strobeson coded outputcircuits.
TemporalMode: Codestheoutputvoltageinacode-3temporalpatterntodriveaudible
appliances such as horns, bells or chimes. Caution: Do not use strobes on coded
outputcircuits.
Notification Appliance Circuit
Layout and Design
Subject
Project
No.
By Date
The power supplies shall be Wheelock POWERPATH™ Series PS-12/24-8CP or PS-12/24-8MP, or equivalent. The units shall
be stand alone power supplies intended for powering fire alarm notification appliances via their own NotificationAppliance Circuit(s)
(NAC). The units shall be UL 864 Listed for power limited operation of their outputs and comply with NFPA 70 (NEC), article
760.
The power supplies shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power
is connected.
The power supplies shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP)
or a “Dry contact” closure. The units shall be 8 ampere, 12 or 24 VDC, regulated and filtered, supervised remote power supply/
chargers. The power supplies shall provide a full 8 amperes of current and shall not be battery dependent. They shall operate
over the voltage range of 8 to 33 VDC or FWR. The primary application of the units shall be to expand fire alarm system
capabilities for additional NAC circuits to supportADArequirements and to provide auxiliary power to support system accessories
or functions. The power supplies shall provide four Class “B”, two Class “A”, or two Class “B” and one Class “A” NAC circuit(s).
The PS-12/24-8CP units shall also supply up to 200 mA of auxiliary power that is available during both nonalarm and alarm.
The PS-12/24-8MP units shall also supply auxiliary power of not less than 3.5A at 24 VDC during nonalarm. The power
supplies shall be capable of charging batteries of up to 12 ampere hours per NFPA 72 (1999). Input activation options shall be
from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of being directed to any
combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class “B” applications or
3 amperes each for Class “A”. The outputs shall be programmable to generate a steady or Temporal (Code 3) output and or
a synchronized strobe or horn output. The power supplies shall provide independent loop supervision for either Class “A” or
Class “B” FACP NAC circuits and shall have the capability to “steer” all alarm or trouble conditions to either incoming NAC
circuit. The units shall have common output terminals. The power supplies shall be powered from a 120 VAC or 240 VAC
source with a current consumption of 5 amperes max. The unit shall incorporate short circuit protection with auto reset. The
power supply shall incorporate a built in battery charger for lead acid or gel type batteries with automatic switchover to battery back
up in the event ofAC power failure. The charger shall incorporate fused protection for the batteries and have the ability to report
low battery and/or no battery condition(s). Standby current for battery back up shall be 100 mA max. The cabinet dimensions
shall be 16" H x 12.25" W x 5" D.
Architects and Engineers Specifications
Specifications and Ordering Information
S9000 11/04
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA Distributed By:
National Sales Office
800-631-2148
Canada800-397-5777
E-Mail: [email protected]
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice
in accordance with Wheelock Inc. standard terms and conditions.
273 BranchportAvenue • Long Branch, NJ 07740 • TEL: 732-222-6880 • FAX: 732-222-2588
rebmuNledoMedoCredrOtnerruC/egatloVtupnI slavorppA
LUAEMMFSCMF
PC8-42/21-SP7403.xamspma0.5;zH06/05@CAV022/021X*X*
PM
8-42/21-SP6403.xamspma0.5;zH06/05@CAV022/021XXXX
stiucriCCANtuptuO tnerruC/egatloVtuptuO
”B“ssalC)4(ruoF tiucri
Crepspma3@CDV42/21
ro”A“ssalC)2(owT tiucriCrepspma3@CDV42/21
"B"ssalC)2(owTdna"A"ssalC)1(enO )"A"ssalC(ti
ucriCrepspma3@CDV42/21 )"B"ssalC(tiucriCrepspma3@CDV42/21
tnerruCybdnatS spmA060.0
tnerruCmralA spmA001.0
t
nerruCCANlatoT .xaMspmA8
seirettaBybdnatS ybdnatS emiT tuptuOmralA setuniM/spmAlatoT tuptuOxuA PM8-42/21-SP tu
ptuOxuA PC8-42/21-SP
HA21/CDV42 )seiresniseirettabCDV21)2(owtsesu( sruoH42setuniM51/spmA8
gnirudA5.3 mralanon
Am002
sruoH06setuniM51/spmA8Am06
HA21/CDV21 sruoH42setuniM51/spmA8Am0
02
sruoH06setuniM51/spmA8Am06
WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING
THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
X=Approved
*= Pending

Other manuals for POWERPATH series PS-12-24-8CP

1

This manual suits for next models

1

Other Wheelock Power Supply manuals

Wheelock POWERPATH series PS-12-24-8MP User manual

Wheelock

Wheelock POWERPATH series PS-12-24-8MP User manual

Wheelock POWERPATH PS-12-24-8 User manual

Wheelock

Wheelock POWERPATH PS-12-24-8 User manual

Wheelock A55BM-K User manual

Wheelock

Wheelock A55BM-K User manual

Wheelock ET80-24MCW-FW User manual

Wheelock

Wheelock ET80-24MCW-FW User manual

Wheelock 43T-G6-24 User manual

Wheelock

Wheelock 43T-G6-24 User manual

Wheelock RPS-2406-I User manual

Wheelock

Wheelock RPS-2406-I User manual

Wheelock RPS-2440-A User manual

Wheelock

Wheelock RPS-2440-A User manual

Wheelock PSC-2420-B User manual

Wheelock

Wheelock PSC-2420-B User manual

Wheelock POWERPATH PS-12/24-6 User manual

Wheelock

Wheelock POWERPATH PS-12/24-6 User manual

Wheelock EPS-1205 User manual

Wheelock

Wheelock EPS-1205 User manual

Wheelock POWERPATH series PS-12-24-8CP User manual

Wheelock

Wheelock POWERPATH series PS-12-24-8CP User manual

Popular Power Supply manuals by other brands

Elektro-Automatik 09 230130 instruction manual

Elektro-Automatik

Elektro-Automatik 09 230130 instruction manual

RTZ PS410 owner's manual

RTZ

RTZ PS410 owner's manual

HEIDENHAIN UV 130D Replacing Instructions

HEIDENHAIN

HEIDENHAIN UV 130D Replacing Instructions

Rohde & Schwarz HM8143 user manual

Rohde & Schwarz

Rohde & Schwarz HM8143 user manual

Stanley PLUGBANK 6 manual

Stanley

Stanley PLUGBANK 6 manual

Caswell SPC-9250 user manual

Caswell

Caswell SPC-9250 user manual

Whelen Engineering Company CS240S installation guide

Whelen Engineering Company

Whelen Engineering Company CS240S installation guide

Altronix AL125220 Series installation guide

Altronix

Altronix AL125220 Series installation guide

Capetti Elettronica Winecap BOX-PPS user manual

Capetti Elettronica

Capetti Elettronica Winecap BOX-PPS user manual

Bass Habit PP600.1 owner's manual

Bass Habit

Bass Habit PP600.1 owner's manual

M2TECH EVO SUPPLY user manual

M2TECH

M2TECH EVO SUPPLY user manual

American DJ MidiPak User instructions

American DJ

American DJ MidiPak User instructions

AAT Novus NVE-SV100 installation manual

AAT

AAT Novus NVE-SV100 installation manual

Raybend RAI-1500 Installation and service manual

Raybend

Raybend RAI-1500 Installation and service manual

Vacon NX series Applications manual

Vacon

Vacon NX series Applications manual

Altronix TROVE T2MK34 installation guide

Altronix

Altronix TROVE T2MK34 installation guide

KEPCO BOP 10-100GL quick start guide

KEPCO

KEPCO BOP 10-100GL quick start guide

Data Video PD-6A instruction manual

Data Video

Data Video PD-6A instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.