Architects and Engineers Specifications
NATIONALSALESOFFICE
800-631-2148
Canada 800-397-5777
http://www.wheelockinc.com
DistributedBy:
The alarm bells shall be Wheelock Series CVX/CSX explosion-proof bells or approved equals. They shall be UL
ListedforHazardous Atomospheres,andsuitable for use in Division One applications: Class One, groups B, C
and D; and Class Two, groups F and G. They shall be CSAapproved.
Specificmodelsshallbe designed for either single stroke or vibrating mode, andoperationfor either 24 VDC or 115 VAC.
Sound output at 10 feet shall be 87 dBA for single stroke versions and 90 dBA for the vibrating version.
All versions shall be polarized for DC supervision.
Operating current shall be as follows: .220 amperes for 115 VAC vibrating, .125 amperes for 115 VAC single stroke;
.500 amperes for 24 VDC single stroke.
Outdoor versions shall incorporate a cast protective hood and guard over the bottom half of the bell shell.
Dimensions for the indoor versions shall be 10 and one-eighth inches wide, 11 inches high and 6 and one-half inches
deep. Outdoor versions shall measure 11 and one-half inches wide, 11 and one-half inches high, and 7 and one-half
inches deep.
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained
and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in
accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing
must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA),
Underwriters’ Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county,
province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all
appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
WARNING: PLEASE READ THESE SPECIFICATIONS ANDASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,
SPECIFYING ORAPPLYING THIS PRODUCT. FAILURE TO COMPLY WITHANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS
COULD RESULT IN IMPROPERAPPLICATION, INSTALLATIONAND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCYSITUATION,
WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOUAND/OR OTHERS.