11
14) Select Temperature Display Adjustment 4 LO to 4 HI –
Allows you to adjust the room temperature display up to
4° higher or lower. Your thermostat was accurately
calibrated at the factory but you have the option to
change the display temperature to match your previous
thermostat. The current or adjusted room temperature will
be displayed on the left side of the display.
15)Select Temporary Program Override Time – The thermo-
stat can hold any temperature you set it to for the amount
of time you select on this option. Your choices are 0:00 to
8:00 hours in 15 minute increments. 0:00 means disable.
Example:
1. You have selected 3:00 hours for the Temporary Pro-
gram Override time period.
2. With the thermostat set to Heat or Cool, press HOLD
for approximately 5 seconds until "HOLD time 3:00"
(indicating 3 hours) appears as a setting reminder.
3. After releasing the button, "HOLD"on the display will
blink.
4. Use or to set the temperature to your prefer
ence. The thermostat will maintain this temperature
setting for 3 hours with "HOLD"blinking to remind you
it is in Temporary Hold. After 3 hours, the thermostat
will go back to the program temperature and "HOLD"
will no longer blink or display.
16)Select F° or C° Readout – Changes the display readout
to Celsius or Fahrenheit as required.
17)Limited Heat Range – This feature provides a maximum
setpoint temperature for heat. The default setting is 90°F. It
can be changed between 62°F and 89°F by pressing the
or key.
18)Limited Cool Range – This feature provides a minimum
setpoint temperature for cool. The default setting is 45°F. It
can be changed between 46°F and 82°F by pressing the
or key.
19)Comfort Alert – This feature is available in Passive
mode on this thermostat. If a Comfort Alert module is
connected, the thermostat will receive and flash the fault
codes from the Comfort Alert module.
20 & 21) Keypad Lockout – This menu selection will
display lock () icon. The and are used to toggle
the function and display the lock icon and OFF (keypad
not locked out, default) indicating in the time digits to the
lock icon and ON (keypad locked out). When the keypad
lockout function is enabled (ON), and the SYSTEM button
is pressed again, the display will indicate the number 000
(default, still disabled) in the time digits. The and
are used to set the combination number from 0to 999. If
a combination of 000 is selected and the SYSTEM button
is pressed, the menu will be exited and keypad will not be
locked. If 1 to 999 is selected and the SYSTEM button is
pressed again, the combination is locked into non-volatile
memory and the menu is exited. The lock icon (to
designate keypad locked with a valid combination) will
display when the menu is exited. The SYSTEM button
will operate for 10 seconds after the menu mode is exited
to allow the user to change the mode from OFF to the
desired system mode.
While the keypad is locked out, a simultaneous press of
and will enter the menu item from any mode instead of
only OFF mode. When the menu is entered with the
keypad lockout feature enabled, the first menu item
displayed is the combination code 0. The or keys
are used to set the combination unlock number from 0to
999. If the unlock number matches exactly with the
combination lock number stored in memory when the
SYSTEM button is pressed, the keypad is unlocked and
the lock icon is removed. If the unlock number does not
match when the SYSTEM button is pressed, menu is
exited and the keypad remains disabled.
To reset the combination code and unlock the keypad if the
code is forgotten, see troubleshooting section, page 20.
different channel is selected on the thermostat it must also
be changed to the same setting on the remote. This is
only used in areas where there are other wireless
devices or electronic equipment that interfere with the
default frequency of the thermostat/remote sensor
communication.
7) Programmable Periods – This control can be config-
ured for 4, 2 or 0 programmable periods. The display
indicates "PRG 4" in the display as default. The program-
mable periods can be changed to 2 or 0 by pressing the
or keys. With "PRG 0" selected for non-program-
mable, SYSTEM key selection will skip EMR (item 8) and
temporary program override (item 15).
8) Select Energy Management Recovery OFF or ON –
Energy Management Recovery (EMR) causes the
thermostat to start heating or cooling early to make the
building temperature reach the program setpoint at the
time you specify. Heating will start 5 minutes early for
every 1° of temperature required to reach setpoint.
Example: You select EMR and have your heating
programmed to 65° at night and 70° at 7 AM. If the
building temperature is 65° the difference between 65°
and 70° is 5°. Allowing 5 minutes per degree the thermo-
stat setpoint will change to 70° at 6:35 AM. Cooling allows
more time per degree because it takes longer to reach
temperature.
9) Fast or Slow Cycle Selection – The factory default
setting is fast cycle, which cycles 1st stage at approxi-
mately 1.2°F and 2nd stage 0.75°F. If you prefer slow
cycle, press the temperature key to change to SL. The 1st
stage and 2nd stage would be 1.5°F and 1.2°F respec-
tively.
10)Select Compressor Lockout CL OFF or ON – Selecting
CL ON will cause the thermostat to wait 5 minutes before
turning on the compressor if the heating and cooling
system loses power. It will also wait 5 minutes minimum
between cooling and heating cycles. This is intended to
help protect the compressor from short cycling. Some
newer compressors already have a time delay built in and
do not require this feature. Your compressor manufac-
turer can tell you if the lockout feature is already present
in their system. When the thermostat compressor time
delay occurs it will flash the setpoint for about five
minutes.
11)Select Backlight Display – The display backlight improves
display contrast in low lighting conditions. When the "C"
terminal is powered, selecting backlight CdL ON will keep
the light on continuously. Select backlight OFF will keep
the light on momentarily after any key is pressed. When the
"C" terminal is not powered, the light will be on momen-
tarily after any key is pressed no matter the backlight is
selected ON or OFF.
12)Select Fast Second Stage On or OFF – For Heat:
During normal operation if the setpoint temperature is
manually raised by 3°F or more above the actual
temperature with the button, and the fast second
stage feature is enabled, FA ON, the second stage will
energize immediately.
For Cool: During normal operation if the setpoint tem-
perature is manually lowered by 3°F or more below the
actual temperature with the button, and the fast
second stage feature is enabled, FA ON, the second
stage will energize immediately.
13)Select filter replacement run time – The thermostat will
display "FLTR"after a set time of operation. This is a
reminder to change or clean your air filter. This time can be
set from 0 to 1950 hours in 50 hour increments. A selec-
tion of 0 will cancel this feature. When "FLTR"is
displayed, you can clear it by pressing HOLD and RUN at
the same time. This resets the timer and starts counting the
hours until the next filter change. Contact your system
manufacturer for a specific replacement/maintenance
interval.