Whittaker C173285-3 Manual

T.M. C173285-3
TECHNICAL MANUAL
OPERATION AND
MAINTENANCE INSTRUCTIONS
ELECTRIC GAS
FUEL METERING SYSTEM
PART NUMBER C173285-3
AND ASSOCIATED
MOTOR CONTROLLERS
PROPRIETARY
INFORMATION
NOTICE:
–
T
HE INFORMATION CONTAINED
HEREIN IS THE PROPERTY OF
W
HITTAKER
C
ONTROLS
,
A
U
NIT OF
W
HITTAKER
C
ORPORATION
,
AND DISCLOSURE OF THE CONTENTS TO OTHERS IS GIVEN IN CON
-
FIDENCE
.
T
HIS MATERIAL MUST NOT BE REPRODUCED OR COPIED
,
OR OTHERWISE
DISCLOSED IN WHOLE OR IN PART WITHOUT THE APPROVAL OF
W
HITTAKER
C
ON
-
TROLS
,
N
ORTH
H
OLLYWOOD
,
C
ALIFORNIA
,
U.S.A.
1 DECEMBER 1997

T.M. C173285-3
1 DECEMBER 1997
A
Reproduction of the information or illustrations contained in this publication is not permitted, without written
permissionfromthepublisher:WhittakerControls,12838 SaticoyStreet,NorthHollywood,California90605,
U.S.A.
LIST OF EFFECTIVE PAGES
Insert latest changed pages; dispose of superseded pages.
NOTE: On a changed page, the portion of text affected by the change is indicated by a vertical line or other
change symbol in the outer margin of the page. Changes to illustrations are indicated by miniature pointing
hands. Changes to wiring diagrams are indicated by shaded areas.
Dates of issue for original and changed pages are as follows:
Original 1 . . . . . . . . . . . . 1 December 1997
Total number of pages in this manual is 74 consisting of the following:
Page #Change
No. No. Page #Change
No. No. Page #Change
No. No. Page #Change
No. No.
Title ............. 0
A............... 0
i – iv ............ 0
1-1 – 1-3 ..........0
2-1 – 2-13 .........0
3-1 – 3-2 ..........0
4-1 – 4-10 ........ 0
5-1 – 5-7 ......... 06-1 – 6-3 ......... 0
7-1 – 7-30 ........ 0
#Zero in this column indicates an original page.

T.M. C173285-3
1 DECEMBER 1997
i
TABLE OF CONTENTS
Section Paragraph/Title Page Section Paragraph/Title Page
SAFETY SUMMARY ................. iii
IINTRODUCTION ...................1-1
1-1. Purpose of Manual .............1-1
1-4. Scope of Manual ..............1-1
1-7. Symbols and Abbreviations ......1-1
II SYSTEM DESCRIPTION AND
OPERATION ......................2-1
2-1. General .....................2-1
2-3. Fuel Metering Skid ............2-1
2-5. Motor Controllers .............2-1
2-7. Operation ....................2-5
2-9. DLE Engine Skid Settings ......2-5
2-11. SAC Engine Skid Settings ......2-5
2-13. System Operation .............2-5
2-17. Gas Isolation Shutoff Valves
(SOV1 and SOV2) ...........2-5
2-20. Inter-Shutoff Vent Valve
(GVV) .....................2-7
2-22. Gas Supply Temperature
Transmitter (TT1/TT2) ........2-7
2-23. SAC/DLE Manual Selector
Valve (SOV4) ...............2-9
2-27. Fuel Metering Valves (FMVB
FMVP, FMVO and FMVI) .....2-9
2-30. DLE Absolute Pressure
Transducer (GP1/GP2) ......2-11
2-32. SAC Absolute Pressure
Transducer (GP1B) .........2-12
2-34. Motor Controllers (MCB, MCI,
MCO and MCP) ............2-12
III INSTALLATION ....................3-1
3-1. General .....................3-1
3-3. Mechanical Interfaces ..........3-1
3-5. Gas Inlet Supply Flange .......3-1
3-7. DLE Engine Outlet Flanges ....3-1
3-9. SAC Engine Outlet Flange .....3-1
3-11. Seal Vent Interface Flange .....3-1
III 3-13. Electrical Interfaces ............3-1
3-14. PE Grounding Connection ......3-1
3-16. Main Junction Box
Connectors ..................3-1
IV FAULT ISOLATION ................. 4-1
4-1. General .....................4-1
4-2. Fault Isolation –Gas Isolation
Shutoff Valve (SOV1 or SOV2) ..4-1
4-3. Position Indication ...........4-1
4-4. Position Indicator Moves
Normally –Possible Position
Indicating Switch Fault ........4-1
4-5. Position Indicator Will Not
Move –Possible Solenoid
Fault ......................4-1
4-6. Gas Supply Temperature
Transmitter (TT1/TT2) .........4-2
4-8. SAC Gas Supply Absolute
Pressure Transducer (GP1B) ...4-2
4-10. DLE Gas Supply Absolute
Pressure Transducers
(GP1/GP2) ..................4-2
4-12. SAC/DLE Manual Selector
Valve (SOV4) ................4-3
4-13. Position Indication ...........4-3
4-14. Inter-Shutoff Vent Valve (GVV) ..4-3
4-15. Valve Will Not Operate .......4-3
4-16. Motor Controllers (MCB, MCI,
MCO and MCP) ..............4-3
4-19. Motor Controller Enable .......4-3
4-21. Error Code Fault Isolation ......4-7
4-22. Fuel Metering Valves (FMVB,
FMVI, FMVO and FMVP) ......4-7
4-23. Valve Position ..............4-7
4-24. LVDT Position Indication ......4-7
4-25. Actuator Motor Control or
Position Problems ...........4-9
4-27. Fuel Metering Valve Motor
Controller Enable ...........4-10

T.M. C173285-3
1 DECEMBER 1997
ii
Section Paragraph/Title Page Section Paragraph/Title Page
VMAINTENANCE ....................5-1
5-1. General .....................5-1
5-4. Repair Tasks ................5-1
5-5. Gas Isolation Valve (SOV1 or
SOV2) ....................5-1
5-6. Closed Position Indicating
Switch Replacement .........5-1
5-7. Gas Isolation Valve
Replacement .............5-2
5-8. Fuel Metering Valve (FMVB,
FMVI, FMVO or FMVP) .......5-2
5-9. LVDT Replacement .........5-2
5-10. Fuel Metering Valve
Replacement ..............5-3
5-11. SAC Gas Supply Absolute
Pressure Transducer (GP1B) ...5-4
5-13. Pressure Transducer
Replacement ..............5-4
5-14. Gas Supply Temperature
Transmitter (TT1/TT2) ........5-4
5-16. Temperature Transmitter
Replacement ..............5-5
5-17. Inter-Shutoff Vent Valve
(GVV) .....................5-5
5-19. Vent Valve Replacement .....5-5
5-20. SAC/DLE Manual Selector
Valve (SOV4) ...............5-5
V5-21. Switch Enclosure
Replacement ..............5-5
5-22. Selector Valve Replacement ..5-6
5-23. Motor Controller (MCB, MCI,
MCO or MCP) ...............5-6
5-25. DLE Gas Supply Absolute
Pressure Transducer
(GP1/GP2) .................5-6
5-26. Pressure Transducer
Replacement ..............5-6
5-27. Circuit Board Replacement ...5-7
VI MAINTENANCE PARTS LIST .........6-1
6-1. General .....................6-1
6-3. Maintenance parts ............6-1
VII ELECTRICAL WIRING INFORMATION
AND INTERCONNECTION
DIAGRAMS .......................7-1
7-1. General .....................7-1
7-3. Installation Recommendations ...7-1
7-4. Shielding ...................7-1
7-6. Cable Entries ...............7-1
7-8. Cable Wire Sizing ............7-1
7-10. Cable Lengths ..............7-1
7-12. Special Cable Capacitance
Requirements ...............7-1
LIST OF ILLUSTRATIONS
Figure Title Page Figure Title Page
2-1. Fuel Metering Skid Major Compo-
nent Locations ...................2-2
2-2. Gas Isolation Shutoff Valve (SOV
and SOV2) ......................2-5
2-3. Fuel Metering System Flow Diagram ..2-6
2-4. Inter-Shutoff Vent Valve (GVV) .......2-8
2-5. Gas Supply Temperature Transmitter
(TT1/TT2) ......................2-8
2-6. Fuel Metering Valve (FMVB, FMVI,
FMVO and FMVP) ...............2-11
2-7. DLE Gas Supply Absolute Pressure
Transducer (GP1/GP2) Junction
Box ...........................2-12
2-8. SAC Absolute Pressure Transducer
(GP1B) ........................2-13
2-9. Motor Controller (FMVB, FMVI,
FMVO and FMVP) ...............2-10
3-1. Electrical Interface Panel Diagram ....3-2
4-1. Motor Controller/Fuel Metering Valve
Test Setup ......................4-5

T.M. C173285-3
1 DECEMBER 1997
iii
Figure Title Page Figure Title Page
7-1. DLE Gas Supply Absolute Pressure
Transducer (Outer GP1/GP2) .......7-2
7-2. DLE Gas Supply Absolute Pressure
Transducer (Inner GP1/GP2) .......7-3
7-3. DLE Gas Supply Absolute Pressure
Transducer (Pilot GP1/GP2) ........7-4
7-4. Fuel Metering Valve (FMVB, FMVI
FMVO and FMVP) ................7-8
7-5. Motor Controller (MCB, MCI, MCO
and MCP) .....................7-17
7-6. Inter-Shutoff Vent Valve (GVV) ......7-26
7-7. Gas Supply Temperature Transmitter
(TT1/TT2) .....................7-27
7-8. Gas Isolation Shutoff Valve (SOV
and SOV2) .....................7-28
7-9. SAC/DLE Manual Selector Valve
(SOV4) ........................7-29
7-10. SAC Gas Supply Absolute Pressure
Transducer (GP1B) ..............7-30
LIST OF TABLES
Table Title Page Table Title Page
1-1. Fuel Metering System Specifications/
Specifications/Major Components ...1-2
2-1. Gas Isolation Valve (SOV1 and
SOV2) Specifications/
Characteristics ...................2-7
2-2. Inter-Shutoff Vent Valve (GVV)
Specifications/Characteristics .......2-8
2-3. Gas Supply Temperature Transmitter
(TT1/TT2) Specifications/
Characteristics ...................2-8
2-4. SAC/DLE Manual Selector Valve
(SOV4) Specifications/
Characteristics ...................2-9
2-5 Fuel Metering Valve (FMVB, FMVI,
FMVO and FMVP) Specifications/
Characteristics ..................2-10
2-6. DLE Gas Supply Absolute Pressure
Transducer (GP1/GP2) Specifica-
tions/ Characteristics .............2-11
2-7. SAC Absolute Pressure Transducer
(GP1B) Specifications/
Characteristics ..................2-13
2-8. Motor Controller (FMVB, FMVI,
FMVO and FMVP) Specifications/
Characteristics ..................2-13
3-1. Main Junction Box Interface
Connectors .....................3-2
4-1. Motor Controller Enable Test
Parameters .....................4-6
6-1. Recommended Spare Parts .........6-1

T.M. C173285-3
1 DECEMBER 1997
iv
SAFETY SUMMARY
GENERAL
The following are general safety precautions that
are not related to specific procedures and therefore
do not appear elsewhere in this publication. These
are recommended precautions that personnel must
understand and apply during many phases of main-
tenance.
WEAR PROTECTIVE CLOTHING
Wear protective clothing (gloves, apron, etc.) ap-
proved for the materials and tools being used.
USE APPROVED SAFETY EQUIPMENT
When cleaners and primers are being applied,
approved explosion-proof lights, blowers, and other
equipment shall be used. Make sure that fire fight-
ing equipment is readily available and in working
order.
GIVE CLEANERS SPECIAL CARE
Keep cleaners in special polyethylene bottles or
in safety cans and in minimum quantities. Discard
soiled cleaning rags into safety cans.
ELECTRICAL SYSTEM PRECAUTIONS
Theequipmentcontainsahighvoltage115(±25)
VDC electrical system. Prior to performing electrical
system repairs after testing, make sure that the 115
VDC power source is disconnected prior to
attempting removal or disassembly of any electrical
components. This will protect personnel from
possible electric shock as well as protecting the
equipment from possible damage.

T.M. C173285-3
1 DECEMBER 1997
1-1
SECTION I
INTRODUCTION
1-1. PURPOSE OF MANUAL.
1-2. This technical manual contains instructionsfor
operation and maintenance of Electric Gas Fuel
Metering System and the associated Motor Con-
trollers, hereinafter referred to as the fuel metering
system.
1-3. The fuel metering system operates in con-
junctionwiththeGeneralElectricMarkVLM Engine
Control System to controlthe deliveryof natural gas
to the individual combustor manifolds of the SAC
(Single Annular Combustor) and DLE (Dry Low
Emissions) Gas Turbine Engines. Refer to Table 1-
1 for specifications/characteristics, component
designations/tag numbers and hazardous area
ratings.
1-4. SCOPE OF MANUAL.
1-5. This manual is intended to provide information
in sufficient detail to permit proper startup, oper-
ation, and shutdown of the equipment and, to
prescribe proper daily and periodic inspection and
procedures.
1-6. The technical manual is divided into seven
sections:
Section I –Introduction –Describes the purpose
and scope of this manual.
Section II –System Description and Principles
of Operation –Contains a physical descrip-
tion of the equipment together with explana-
tions of its operating modes and component
functions and characteristics.
Section III –Installation –Provides information for
installing, connecting, and preparing the
equipment for use.
Section IV –Fault Isolation –Contains proce-
dures for finding the cause of a malfunction.
Section V –Maintenance –Provides instructions
for adjustment of system components and re-
placement of defective components.
Section VI –Maintenance Parts List –Contains a
list of spare parts recommended for on-site
support of the equipment.
Section VII –Diagrams –Contains the necessary
wiring and flow schematic diagrams.
1-7. SYMBOLS AND ABBREVIATIONS.
1-8. Symbols and abbreviations used in this
technical manual are as follows:
AWG American Wire Gage
CCentigrade (Celsius)
DC Direct current
DLE Dry Low Emissions
FFahrenheit
Hz Hertz
kg Kilogram
kg/s Kilograms/second
kPa KiloPascal
LVDT Linear variable differential transformer
mm Millimeter
NPT National Pipe Thread
P/N Part Number
PE Primary Earth (electrical ground)

T.M. C173285-3
1 DECEMBER 1997
1-2
psi Pounds per square inch
psia Pounds per square inch, absolute
psid Pounds per square inch, differential
psig Pounds per square inch, gage
SAC Single Annular Combustor
SPDT Single-pole, double-throw
VDC Volts direct current
Table 1-1. Fuel Metering System Specifications/Specifications/Major Components
Applications ...........................................General Electric LM1600, LM2500, LM2500+
and LM6000 Gas Turbine Engines
Service Fluid ....................................................Natural Gas (per MID-TD-0000-1)
Electrical Power ............................................................... 115 (±25) VDC
Temperatures
Normal Ambient ................................................. –54 to 104°C (–65 to 220°F)
High Ambient (one hour) ..................................................... 177°C (350°F)
Natural Gas ....................................................... 0 to 149°C (32 to 300°F)
Weight (approximate) ...................................................... 615 kg (1350 pounds)
MAJOR COMPONENTS
DESCRIPTION WHITTAKER
PART NUMBER WHITTAKER
DESIGNATION HAZARDOUS AREA RATING
Gas Isolation Shutoff Valve 1 C329305 SOV1 EEx d IIB T4 Ta 120°C, Demko Cer-
tification 95D119.660
Gas Isolation Shutoff Valve 2 SOV2
SAC/DLE Manual Selector Valve C326961 SOV4 Explosion Proof Class 1, Divisions 1
and 2, Groups C and D, FM/CSA
DLE Engine Inner “C”Fuel Metering
Valve C329635-D5 FMVI Actuator: EEx d IIB T4 Ta 105°C,
LCIE Certification 97D6070
LVDT: EEx d IIB T4 Ta 120°C,
Demko Certification 97D112.635
DLE Engine Pilot “B”Fuel Metering
Valve FMVP
DLE Engine Outer “A”Fuel Metering
Valve FMVO
SAC Engine Fuel Metering Valve C329635-D3 FMVB
Inter-Shutoff Vent Valve C327048 GVV EEx d IIB T4, PTB Certification Ex
88.B.1049

T.M. C173285-3
1 DECEMBER 1997
1-3
Table 1-1. Fuel Metering System Specifications/Specifications/Major Components (continued)
DESCRIPTION WHITTAKER
PART NUMBER WHITTAKER
DESIGNATION HAZARDOUS AREA RATING
Gas Supply Temperature Trans-
mitter C173265 TT1 EEx d IIB T4 Ta 120°C, Demko Cer-
tification 95D119.657
TT2
DLE Gas Supply Absolute Pressure
Transducer C173255-1 Inner GP1A EEx d IIB T4 Ta 120°C, Demko Cer-
tification 95D119.658
Inner GP1B
Pilot GP1A
Pilot GP1B
Outer GP1A
Outer GP1B
Inner GP2A
Inner GP2B
Pilot GP2A
Pilot GP2B
Outer GP2A
Outer GP2B
SAC Gas Supply Absolute Pressure
Transducer C327049 GP1B Ex ds IIC T5, BASEEFA Certification
Ex 81252X
DLE Engine Inner Motor Controller C173455 MCI –
DLE Engine Pilot Motor Controller MCP
DLE Engine Outer Motor Controller MCO
SAC Engine Motor Controller MCB

T.M. C173285-3
1 DECEMBER 1997
2-1
SECTION II
SYSTEM DESCRIPTION AND
OPERATION
2-1. GENERAL.
2-2. The fuel metering system (see Figure 2-1)
consists of two major components, the Electric Gas
Fuel Metering Skid (P/N C173285-3), and the four
individual Motor Controllers (P/N C173455).
2-3. FUEL METERING SKID.
2-4. The Fuel Metering Skid is comprised the fol-
lowing components and the associated piping net-
work, all of which are mounted on a steel chassis
with casters which allows easy movement of the
system. The fuel metering skid is designed specifi-
cally for test cell usage, and customer connections
have been optimized for easy installation and re-
moval via the use of quick-connectstyleconnectors
for all electrical interfaces.
C
Gas Isolation Shutoff Valves (SOV1 and
SOV2)
C
Inter-Shutoff Vent Valve (GVV)
C
Gas Supply Temperature Transmitter
(TT1/TT2)
C
SAC/DLE Manual Selector Valve (SOV4)
C
SAC Engine Fuel Metering Valve (FMVB)
C
DLE Engine Fuel Metering Valves (Inner
“C”, Pilot “B”and Outer “C”) (FMVI, FMVO
and FMVP)
C
Absolute Pressure Transducers (GP1 and
GP2) (each consisting of four absolute
transducers with their associated electrical
interface cards)
C
SAC Gas Supply Absolute Pressure Trans-
ducer (GP1B)
2-5. MOTOR CONTROLLERS.
2-6. The four Motor Controllers (MCP,MCO,MCI,
MCB) are installed remotely from the Fuel Metering
Skid, but must be located within 200 feet wire run
length from the Fuel Metering Skid. Each motor
controller consists of a servo amplifier, an inlet and
outlet signal noise filter and a capacitor/resistor ar-
rangement, all of which are packaged in a compact
assembly with readily accessible customer wiring
terminations.
NOTE
If the motor controllers must be instal-
led in a hazardous area, Part Number
C173465 Motor Controllers should be
used. These function the same as Part
Number C173455, but the explosion
proof enclosure provides an extra
degree of protection for the electronic
components.

T.M. C173285-3
1 DECEMBER 1997
2-2
Figure 2-1. Fuel Metering Skid Major Component Locations (Sheet 1 of 3)

T.M. C173285-3
1 DECEMBER 1997
2-3
Figure 2-1. Fuel Metering Skid Major Component Locations (Sheet 2 of 3)

T.M. C173285-3
1 DECEMBER 1997
2-4
Figure 2-1. Fuel Metering Skid Major Component Locations (Sheet 3 of 3)

T.M. C173285-3
1 DECEMBER 1997
2-5
SOLENOID
VENT
PORT
OUTLET
PORT
FLOW
BODY
INLET
PORT
ACTUATOR
ELECTRICAL
ACCESS
PORT
Figure 2-2. Gas Isolation Valve (SOV1
and SOV2)
2-7. OPERATION. (Refer to Figure 2-2.)
2-8. The fuel metering system is designed to pro-
vide the controlled flow of natural gas fuel to both
DLE and SAC engine configurations. Depending on
the model of engine being operated, specific set-
tings must be selectedon the fuelmetering skidand
specific modes of operations must be followed.
These specific settings are discussed in the follow-
ing paragraphs. The gas inlet connections and the
electricalconnectionsareidenticalfor bothDLEand
SAC engine operations.
2-9. DLE ENGINE SKID SETTINGS.
2-10. When operating DLE engines, the SAC/DLE
manual selector valve (SOV4) must be set to open
position and the outlet pipe from the SAC Engine
Fuel Metering Valve (FMVB) must be capped with
a blanking flange and gasket.
2-11. SAC ENGINE SKID SETTINGS.
2-12. When operating SAC engines, the SAC/DLE
Manual Selector Valve (SOV4) must be set to the
closed position and the outlet pipes of the DLE fuel
metering valves (FMVO, FMVP and FMVI) must be
capped with blanking flanges and gaskets.
2-13. SYSTEM OPERATION.
2-14. After the natural gas inlet supply line and the
fuel metering valve outlet lines are connected, and
the electrical connections (see Section VII) are
made, natural gas is applied to the fuel metering
skid gas inlet from the facility gas supply system.
Fuel flow through the fuel metering system is ini-
tiated byelectricallycommanding thepneumatically
actuated gas isolation valves (SOV1 and SOV2) to
open and the inter-shutoff vent valve (GVV) to
close.
2-15. The fuel metering valves (FMVP, FMVO and
FMVI or FMVB) are then opened to control the flow
of natural gas fuel to the individual engine combus-
tor manifolds by modulating in response to position
commands received through the motor controllers
from the Mark V LM Control System.
2-16. The position commands from the Mark V LM
Control System are derived from many parameters
suchasengineoperatingconditions,gasproperties,
gas pressuresand gastemperatures. The use of an
extensive valve characteristics map and accurate
position feedback, accurately provides the desired
mass flow rates of the natural gas into the individual
combustor manifolds.
2-17. GAS ISOLATION SHUTOFF VALVES
(SOV1 and SOV2). (Refer to Figure 2-2.)
2-18. In preparation for engine startup and opera-
tion, gas at a minimum supply pressure of 200 psia
is supplied to the inlet of valve SOV2. Both valves
SOV1 and SOV2 are electrically commanded to
their open positions by energizing their solenoids
with 115 VDC electrical power. Energizing the sole-
noids allows inlet gas pressure to enter the actu-
ators of the valves, which actuates the valves to
their fully open positions. For gas isolation valve
characteristics and specifications, refer to Table
2-1.

T.M. C173285-3
1 DECEMBER 1997
2-6
Figure 2-3. Fuel Metering System Flow Diagram

T.M. C173285-3
1 DECEMBER 1997
2-7
2-19. When the valves begin to open, the closed
position indicating switches of the valves open, sig-
naling a loss of continuity to the Mark V LM control-
ler.
2-20. INTER-SHUTOFF VENT VALVE (GVV).
(Refer to Figure 2-4.)
2-21. The Inter-Shutoff Vent Valve is a normally
open, energize to close, direct operated solenoid
shutoff valve. When valves SOV1 and SOV2 are
de-energized to the closed position, the gas volume
trapped between the two valves is vented to a safe
area through the inter-shutoff vent valve. When
valves SOV1 and SOV2 are energized open, valve
GVV is energized closed, preventing gas from vent-
ing. For inter-shutoff vent valve characteristics and
specifications, refer to Table 2-2.
2-22. GAS SUPPLY TEMPERATURE
TRANSMITTER (TT1/TT2).
(Refer to Figure 2-5.)
2-23. The Gas Supply Temperature Transmitter is
a dual element platinum RTD that monitors the fuel
gas supply temperature downstream of the gas iso-
lation valves. The temperature is converted to an
electrical signal by the transmitter for use by the
Mark V LM Controller for fuel flow factor correction
to compensate for temperature variations. For gas
supply temperature transmitter characteristics and
specifications, refer to Table 2-3.
Valve Type ................... Gas Flow Shutoff, Solenoid Pilot Operated, Gas Actuated, Fail Safe Closed
Service Fluid ................................................... Natural Gas (per MID-TD-0000-1)
Pipe Size .................................................................. 51 mm (2 inches)
Pressures
Normal ................................................... 1 380 to 4 830 kPa (200 to 700 psig)
Proof .................................................................9 930 kPa (1440 psig)
Flow .....................................................0 to 2.77 kg/s (0 to 6.1 pounds/second)
Pressure Drop (fully open) (maximum) .............. Cv = 55 (124 kPa at 3 140 kPa, 2,77 kg/s, and 149°C)
(18 psid at 450 psig, 6.1 pounds/second, and 300°F)
Internal Leakage ............................................................. per ANSI Class V
Electrical Data
Solenoid Voltage
Normal .......................................................................115 VDC
Range ................................................................... 90 to 140 VDC
Current (maximum) .................................0.43 ampere at 140 VDC and –54°C (–65°F)
Coil Resistance (at 20°C [68°F]) .............................................403 to 447 ohms
Coil Resistance (at –40°C [–40°F]) ...........................................308 to 341 ohms
Closed Position Indicating Switch
Type ..................................................................... 3-wire, SPDT
Rated Voltage .................................................................. 115 VDC
Electrical Connection ........................................................... ½-14 NPT port
Fluid Connections ...................................................... Flanges per ANSI B16.5,
2-inch pipe, Class 600RF
Seal Vent .................................................................... ½-14 NPT port
Temperatures
Normal Ambient ...................................................–54 to 104°C (–65 to 220°F)
High Ambient (one hour) .......................................................177°C (350°F)
Fluid ...............................................................0 to 149°C (32 to 300°F)
Weight (dry) (maximum) .......................................................39 kg (85 pounds)
Table 2-1. Gas Isolation Valve (SOV1 and SOV2) Specifications/Characteristics

T.M. C173285-3
1 DECEMBER 1997
2-8
ELECTRIC
CONDUIT
PORT
TEMPERATURE
SENSING PROBE
ELECTRICAL
ACCESS
COVER
ELECTRIC
CONDUIT
PORT
Figure 2-5. Gas Supply Temperature Transmitter
(TT1/TT2)
Figure 2-4. Inter-Shutoff Vent Valve (GVV)
RTD Type .............. Dual element platinum
with thermowell
and enclosure
Pressure Capability ........30 000 kPa at 400
/
C
(4400 psig at 750°F)
Temperatures
Fluid ....................... –20 to +400
/
C
(4 to 750°F)
Ambient (maximum) ........... 120
/
C (248°F)
Electrical Data
Voltage ........................... 5 VDC
Current ..................... 0.001 ampere
Electrical Connection ........... Terminal Block
(¾-inch NPT conduit entry)
Dry Weight ................1,8 kg (4.0 pounds)
Table 2-3. Gas Supply Temperature Transmitter
(TT1/TT2) Specifications/Characteristics
Valve Type ...........Direct Solenoid Operated,
Shutoff, Fail Open
Service Fluid .....................Natural Gas
(per MID-TD-0000-1)
Line Size ......................... G¼British
Standard Female Pipe
Orifice Size ...............1 millimeter diameter
Pressures
Normal ................. 1 380 to 4 830 kPa
(200 to 700 psig)
Proof .................9 930 kPa (1440 psig)
Temperatures
Fluid ............... –20 to 90
/
C (4 to 194°F)
Ambient (maximum) ............ 40
/
C (104°F)
Duty Cycle ...................... Continuous
Electrical Data
Voltages
Normal ....................... 115 VDC
Range ....................90 to 140 VDC
Power Consumption ..................10 watts
Electrical Connections ......3-conductor 18 AWG
cable with molded
tension relieving
cable gland
Dry Weight ................0,9 kg (2.0 pounds)
Table 2-2. Inter-Shutoff Vent Valve (GVV)
Specifications/Characteristics

T.M. C173285-3
1 DECEMBER 1997
2-9
2-23. SAC/DLE MANUAL SELECTOR VALVE
(SOV4).
2-24. The SAC/DLE Manual Selector Valve is a
manually operated ball-type shutoff valve with inte-
gral open and closed position indicating switches.
For SAC/DLE manual selector valve characteristics
and specifications, refer to Table 2-4.
2-25. For DLE engine operation, the manual selec-
tor valve is set to the fully open position, allowing
gas to flow to the pilot fuel metering valve (FMVP),
the outer fuel metering valve (FMVO) and the inner
fuel metering valve (FMVI). In the fully open posi-
tion, there will be continuity through the open posi-
tion indicating switch (SW4) and no continuity
throughtheclosedpositionindicating switch(SW3).
2-26. For SAC engine operation, it is necessary to
isolate the volume of the DLE inlet manifold circuit
due to system volume dynamics. For SAC engine
operations, the manual selector valve is set to the
fullyclosedposition, restrictinggasflow onlytoSAC
fuel metering valve (FMVB). In the closed position,
there will be continuity through the closed position
indicating switch (SW3), and no continuity through
the open position indicating switch (SW4).
2-27. FUEL METERING VALVES (FMVB, FMVI,
FMVO and FMVP). (Refer to Figure 2-6.)
2-28. The Fuel Metering Valves are normally
closed, failclosed,DC servomotoroperated sleeve-
type metering valves. The DLE fuel metering valves
(FMVI, FMVO and FMVP) are identical in design,
but are individually mapped, and must be used in
conjunction with their corresponding calibration
map. The SAC fuel metering valve is identical to the
DLE fuel metering valves, except for a lower
restrictor valve element and the use of a universal
calibration map which is used for all SAC fuel
metering valves. For fuel metering valve character-
istics and specifications, refer to Table 2-5.
2-29. Integral to the back side of each DC servo-
motor is a precision 12-bit resolver which provides
for motor commutation and position feedback tothe
Mark V LM control system through the motor con-
troller. Attached to the motor output shaft is a preci-
sion ballscrew assembly which translates the rotary
motion of the motor shaft to linear motion for the
valvepoppetarrangement.Combiningthis2,54mm
(0.1 inch) pitch ballscrew with the resolver provides
0,000635 mm (0.000025 inch) linear position
resolution at thevalve poppet, and an overall stroke
capability of 38.10 mm (1.500 inches). Redundant
position feedback is providedon each fuel metering
valve through an LVDT (linear variable
displacement transducer) which is attached to the
valve coupling. The LVDT supplies a linear stroke
position signal to the Mark V LM control system.
Upon loss of the electrical command signal, the in-
ternalreturnspringwillmove the valve to theclosed
position.
Valve Type ......... Manually Operated, Shutoff
(with two SPDT position
indicating switches in
explosion proof housing)
Service Fluid .....................Natural Gas
(per MID-TD-0000-1)
Line Size ..............51 mm (2-inch) diameter
Pressures:
Working ..............6 900 kPa (1000 psig)
Hydrostatic ...........10 300 kPa (1500 psig)
Temperatures
Fluid ....................... –20 to +150
/
C
(4 to 194°F)
Ambient (switch) ............... –40 to +71
/
C
(–40 to 160°F)
Electrical Data
Switch Rating
Voltage .................. 115 (±25) VDC
Current ............ 0.5 amperes (resistive)
Electrical Connection ........... Terminal Block
(½-inch NPT conduit entry)
Dry Weight (approximate) .....15 kg (33 pounds)
Table 2-4. SAC/DLE Manual Selector Valve
(SOV4) Specifications/Characteristics

T.M. C173285-3
1 DECEMBER 1997
2-10
Valve Type ......................Gas Fuel Metering, DC Servomotor Operated, Sleeve-Type, Fail Closed
Service Fluid .................................................... Natural Gas per MID-TD-0000-1
Pipe Size .................................................................... 51 mm (2-inch)
Pressures
Normal Range ............................................. 1 380 to 4 830 kPa (200 to 700 psia)
Proof ..................................................................6 200 kPa (900 psia)
Flow
FMVB .............................................0,02 to 2,77 kg/s (150 to 22,000 pounds/hour)
FMVI, FMVO and FMVP ...............................0,01 to 1,89 kg/s (60 to 15,000 pounds/hour)
Pressure Drop Characteristics
FMVB ........................................................................... Cv = 64
FMVI, FMVO and FMVP ............................................................ Cv = 36
Electrical Data
Motor
Voltage .................................................................. 90 to 140 VDC
Current (maximum) ................................ 0.3 amperes steady state; 7.0 amperes peak
Thermostat ....................................... Normally closed, rated for 4 amperes, 120 VAC,
Opening Temperature ...............................................170 (±5°C) (338 [±9°F]),
Closing Temperature .............................................. 127 (±5°C) (260.5 [±9°F]),
Resolver
Input Voltage .................................................................... 4 VAC
Input Current ........................................................ 25 to 60 milliamperes
Output Voltage ............................................................ 1.9 to 2.0 VDC
Sensitivity ........................................................ 33 to 35 millivolts/degree
LVDT
Excitation Voltage ....................................... 7.07 (±0.14) volts rms, 3000 (±300) Hz
Input Current (maximum) ....................................................25 milliamperes
Electrical Connections
Motor and Thermostat ............................ Terminal Block, 6-32 screws, 22 to 16 AWG wires
LVDT ......................................... Terminal Block, 2-56 screws, 20 to 18 AWG wires
Control Performance (full stroke opening or closing) ..........................Less than 400 milliseconds
Seal Vent ................................................................... 1/8-27 NPT port
Temperatures
Ambient .........................................................–54 to 104°C (–65 to 220°F)
Ambient (maximum transient) ...................................................177°C (350°F)
Fluid ............................................................–40 to 149°C (–40 to 300°F)
Weight (maximum) ...........................................................34 kg (75 pounds)
Table 2-5. Fuel Metering Valve (FMVB, FMVI, FMVO and FMVP) Specifications/Characteristics

T.M. C173285-3
1 DECEMBER 1997
2-11
Figure 2-6. Fuel Metering Valve (FMVB, FMVI,
FMVO and FMVP)
2-30. DLE ABSOLUTE PRESSURE
TRANSDUCER (GP1/GP2).
(Refer to Figure 2-7.)
2-31. When operating DLE engines, gas pressure
at the inlet and outlet of each fuel metering valve is
monitored by the DLE Absolute Pressure Trans-
ducer. Each fuel metering valve has its own dedica-
ted pressure transducer assembly, each of which
incorporatesfour“smart”temperaturecompensated
digital absolute pressure transducers and their
corresponding electronic interface circuit cards in
oneexplosionproofenclosure.Two transducersare
provided in this assembly for redundant upstream
pressure measurement (GP1) and two transducers
are provided for redundant downstream pressures
(GP2). For DLE absolute pressure transducer char-
acteristics and specifications, refer to Table 2-6.
Type ..............Digital pressure transducers
and interface electronics
in explosion proof enclosure
Service Fluid .....................Natural Gas
(per MIL-TD-0000-1)
Pressure Ports .......... 3/8-inch tube, 4 places
(compression fitting)
Pressures
Calibrated ...................0 to 5 170 kPa
(0 to 750 psia)
Overpressure .........13 800 kPa (2000 psia)
Accuracy ..................±0.02% of full scale
Temperatures
Fluid ....................... –54 to +121
/
C
(–65 to 250°F)
Ambient (maximum) ............ 82
/
C (180°F)
Electrical Data
Voltage (normal) ................... 12 VDC
Voltage Range .................9 to 16 VDC
Current ....................10 milliamperes
Electrical Connections .......... Terminal Block
(¾-inch NPT conduit entry)
Dry Weight ..............17.5 kg (38.5 pounds)
Table 2-6. DLE Absolute Pressure Transducer
(GP1/GP2) Specifications/Characteristics
Table of contents
Popular Industrial Equipment manuals by other brands

Siemens
Siemens 3VA9132-0WA00 operating instructions

Vicon
Vicon V8650H-18 Instructions for installation and operation

Meyer
Meyer Diamond Edge 41770 Assembly instructions

Beijing ART Tech
Beijing ART Tech PCI8302 user manual

Thomas
Thomas 8218 user guide

ipf electronic
ipf electronic BY98A091 operating instructions