.Troubleshooting
.Troubleshooting
.Troubleshooting
.Troubleshooting
Phenomenon Check the following order Causes and treatment
Stall fan
1.Check whether the battery is
full the controller
2. Check the brake controller,
manual fan switch
3. Check whether the brake
controller
4. Check the blower output line
between three-terminal
resistance .
1. If full, then the battery is full
2. If the brake, it will switch to running
3. If the brake, then the fan does not turn
4. If one or more sets of resistance in Europe is less
than 0.4, indicating that the fan cable short-circuit, the
corresponding repair
Can not be
charged
1. Check all cables and terminal
access
2. The long-term no wind, no
sun
3. Check the controller input
terminal voltage of solar
4. Check the wind controller
AC voltage between input
terminals
1. If the cable is bad there is need to overhaul
2. If so, is a normal
3. If the voltage is too low, the cable is damaged or
solar panels is damaged, repair or replace accordingly
4. If the voltage is too low, or three sets of voltage is
not equal, indicating the fan motor windings or faulty
fan output cable, and make the appropriate repair