wirsbo SetPoint 150 User manual

SetPoint 150 Controller
Installation Manual

SetPoint 150 Controller
Installation Manual is published by
Uponor Wirsbo, Inc.
5925 148th Street West
Apple Valley, MN 55124
Phone: (952) 891-2000
Fax: (952) 891-1409
www.wirsbo.com
©2005 Uponor Wirsbo
All rights reserved
Second Edition
First Printing Feb. 2001

1
Table of Contents
T
able of Contents
Table of Contents Page
Introduction ................................................................................2
SetPoint 150 Controller Elements ......................................2
Installation ..................................................................................3
Inventory ..............................................................................3
Mounting the SetPoint 150 Controller ..............................3
Rough-in Wiring ..................................................................3
Connecting the Wiring ........................................................4
Electrical Connections ........................................................4
Sequence of Operation ......................................................5
Programming ..............................................................................6
Troubleshooting ..........................................................................8
Technical Data ............................................................................9
Wiring Diagrams ......................................................................11

2
Introduction
Introduction
Introduction
The Uponor Wirsbo SetPoint 150 Controller is a microprocessor-
based control that can be programmed to maintain a fixed
setpoint temperature by cycling a heating or cooling device.
This reliable and versatile controller features a wide setpoint
range and an adjustable differential and time delay for several
applications. A digital liquid crystal display (LCD) window shows
the actual setpoint and sensor temperatures as well as other
programmed settings. (See Figure 1.)
AUniversal Sensor (A3060071) is supplied with the SetPoint 150
Controller. The wire to the sensor can be extended up to 500 feet
(150m) with standard 18 AWG low-voltage wire. The display
indicates a sensor fault when the sensor is open or has a short
circuit.
SetPoint 150 Controller Elements
Refer to Figure 2 for an explanation of all the elements on the
SetPoint 150 Controller.
Wiring Chamber;
Terminals for 24VAC
Power Supply and
Control Circuit
for Heating/Cooling
Device
Item Selection
and Display
Button
Wiring Chamber;
Terminals for
Sensor
°For °C
Indicators
Cooling Mode
Indicator
Programming and
Display Buttons
Heating Mode
Indicator
Programming
Mode Indicator
Temperature,
Differential and
Delay Display
Item
Identifiers
Hole for Mounting Screw
Hole for Mounting Screw
Setpoint Differential Delay
PRGM
HEAT COOL
FC
Item
Date
S/N
No Power
56
Power Relay
12 34
Setpoint Control
A3040150
Sensor
-+
Made in Canada
Signal Wiring must be
rated at least 300V
NRTL/C
LR 58223
Figure 1: SetPoint 150 Controller
Figure 2: SetPoint 150 Controller Elements

Installation
Inventory
Check the contents of this package. If any contents listed below
are missing or damaged, please contact your Uponor Wirsbo
sales representative or distributor for assistance.
•One SetPoint 150 Controller (A3040150)
•One Universal Sensor (A3060071)
•One SetPoint 150 Controller Installation Manual
Note: Carefully read the Sequence of Operation section in this
manual to ensure you have chosen the proper controller, and you
understand its functions within the operational requirements of
your system.
Mounting the SetPoint 150 Controller
Follow the steps below to mount the controller.
1. Grasp the front cover by the fingertip grips on the top and
bottom of the enclosure and pull the front cover off.
2. Remove the wiring cover screw.
3. Use #6 screws to mount the enclosure flush onto a wall or
onto a 2x4 electrical box.
4. Wire the controller through the back or bottom of the
enclosure into the wiring chamber.
5. Reassemble the enclosure by first replacing the wiring
chamber cover and then pushing the front cover onto the
enclosure until it snaps into place.
Rough-in Wiring
All electrical wiring terminates in the two wiring chambers at the
bottom front of the controller.If the controller is mounted on an
electrical box, rough-in the wiring at the electrical box prior to
installing the controller. Uponor Wirsbo recommends standard
18 AWG solid wire for all low-voltage wiring to this controller.
Caution: Do not apply power to any of the wires during
this rough-in wiring stage.
1. Install the Universal Sensor and run the wiring back to the
controller,but do not connect it.
2. Install a 24VAC Class II transformer with a minimum 5 VA
rating close to the controller and run the wiring from the
transformer to the controller. A Class II transformer must
be used. Do not connect any of the transformer terminals
to the ground.
3. Install the wiring from the heating or cooling device control
circuit to the controller.
3
Installation
Installation
Caution: Improper
installation and operation
of the SetPoint 150
Controller could result in
damage to equipment or
possibly even personal
injury. Please ensure the
controller is installed
according to all applicable
safety codes and standards.

Installation
Installation
Connecting the Wiring
Caution: Only properly trained and experienced
technicians should perform these tests using standard
testing practices and procedures. A good quality
multimeter, capable of reading from at least 0 to
200VAC, and at least 0 to 2,000,000 Ohms, is essential
to properly test this controller. Ensure voltages in
excess of 28VAC are not present in any of the wires
connected to this controller.
Testing the Sensor
1. Measure the temperature using a thermometer, and then
measure the resistance of the sensor at the controller.
Note: Do not connect the wires from the sensor to the
controller while performing the test.
2. Using Table 4 below, estimate the temperature measured
by the sensor. The sensor and thermometer readings
should be close. If the multimeter reads a very high
resistance, this may indicate a broken wire, a poor wiring
connection or a defective sensor. If the resistance is very
low, this may indicate a wiring short, moisture in the
sensor or a defective sensor. To test for a defective sensor,
measure the resistance directly at the sensor location.
Testing the Power Supply
1. Ensure the wires from the power supply transformer are
not touching each other, any other wires or the ground.
2. Turn on the power and use an AC voltmeter to measure
between 20 and 28VAC at the secondary side of the
transformer.
3. Turn off the power and complete the electrical connections
to the terminal strip of the controller.
Electrical Connections
Power and Output Connections (See Figure 5.)
Caution: Maximum 24VAC
1. Connect the transformer to terminals 1 and 2 (C- and R+).
2. Connect the heating and cooling device circuit to the
appropriate terminals:
- Terminals 3 and 4 are normally open (N/O) and close
when the relay turns on.
Table 4: Temperature and Resistance
No Power
56
Power Relay
12 34
Sensor
-+
MadeinCanada
Signal Wiring must be
rated at least 300V
Figure 5: Electrical Connections
4

Installation
Installation
Sensor Connection
Caution: Never apply voltage to these terminals.
1. Connect the Universal Sensor to Terminals 5 and 6.
Sequence of Operation
On/Off + Differential
Guidelines for programming the On/Off + Differential are stated
below. (See Figure 6.)
Differential: Setting the differential on any controller depends
entirely on the actual operating characteristics of the heating or
cooling equipment in each specific application. Set the differential
settings as small as possible for greatest accuracy, but take care
to avoid short cycling of the equipment. Experience, plus trial and
error during actual operating conditions, is typically the way most
installers determine the correct differential setting.
Delay: Setting the time delay also depends on the actual
operating characteristics of the heating or cooling equipment in a
specific application. With some equipment, time delays are
unnecessary and the delay setting can be set to zero. Other types
of equipment depend on a fixed off delay to prevent damage to
equipment components, particularly in the case of certain types
of refrigeration equipment. Consult the manufacturer's operating
and installation instructions for advice on recommended time
delays.
Sequence of Operation — On/Off Mode
When the controller is programmed for heat in this mode, the
relay is turned on and HEAT appears on the display when the
sensor temperature is half the differential setting below the
setpoint and the delay has timed out. When the sensor
temperature rises half the differential setting above the setpoint,
the relay turns off. HEATdisappears from the display,and the
delay starts to time out. During the time-out period, the Delay
pointer flashes if heating is needed. (See Figure 7.)
When the controller is programmed for cooling in this mode, the
relay is turned on and COOL appears on the display when the
sensor temperature is half the differential setting above the
setpoint and the delay has timed out. When the sensor
temperature drops half the differential setting below the setpoint,
the relay turns off. COOL disappears from the display, and the
delay starts to time out. During the time-out period, the Delay
pointer flashes if cooling is needed. (See Figure 8.)
Setpoint Differential Delay
P
HEAT COOL
F
Item
No Power
56
Power Relay
12 34
Setpoint Control
A3040150
Sensor
-+
Made in Canada
Signal Wiring must be
rated at least 300V
NRTL/C
LR 58223
Figure 6
Figure 7
Figure 8
5

6
Programming
Programming
Programming
Digital Display
The digital display on the SetPoint 150 Controller has the
following features.
• Displays the actual sensor temperature.
• Allows the user to view and program the various
controller settings.
• Displays HEAT when the relay closes to operate a heat
source and displays COOL when the relay closes to
operate a cooling device.
• Displays Err when the sensor is open or has a short
circuit.
Power On
When the controller is powered up, the digital display shows all
the display elements. (See Figure 9.)
Operating Mode
After approximately five seconds, the controller automatically
goes into operating mode. The controller monitors the
temperature at the sensor and displays it in the digital display.
(See Figure 10.)
Note: The control automatically goes back to operating mode
when the buttons are left untouched for 20 seconds.
Display Mode
Use the keypad buttons to view the current settings on the
controller.Adjustments to the controller's settings cannot be
made in the display mode. Refer to the Programming Mode for
instructions on changing the control's settings. Toview the
current settings, do the following.
1. Push and hold the ITEM Button. The programmed heating
or cooling setpoint displays. (See Figure 11.)
2. Push and hold the UP Arrow Button. The programmed
Differential displays. (See Figure 12.)
3. Push and hold the DOWN Arrow Button. The programmed
Delay length displays. (See Figure 13.)
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13

7
Programming
Programming
Programming Mode
Push all three buttons at the same time and PRGM appears in the
display. The controller is now in the programming mode. The
pointer will flash to Setpoint. Push the UP or DOWN arrow
buttons to increase or decrease the setpoint temperature.
(See Figure 14.)
Setpoint Range: -40 to 239°F (-40 to 115°C)
Note: Programming settings have a 10-year memory backup.
Pushing the ITEM button again changes the flashing pointer to
Differential. Push the UP or DOWN arrow buttons to increase or
decrease the differential temperature. (See Figure 15.)
Differential Range: 1 to 40°F (1 to 22°C)
Pushing the ITEM button again changes the flashing pointer to
Delay. Push the UP or DOWN arrow buttons to increase or
decrease the Delay time. (See Figure 16.)
Time Delay Range: 0 to 19 min. 50 sec.
(10 second increments)
Pushing the ITEM button again selects the operating mode. Push
the UP or DOWN arrow buttons to select between heating or
cooling operations. (See Figure 17.)
Operating Mode: Heating or Cooling
Pushing the ITEM button again selects the temperature scale.
Push the UP or DOWN arrow buttons to select either Fahrenheit
or Celsius. (See Figure 18.)
Temperature Scale: Fahrenheit or Celsius
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18

8
Troubleshooting
Troubleshooting
Troubleshooting
Follow the Testing the Wiring procedure on page 4 ofthis manual
to troubleshoot the controller.
1. If Err displays, the sensor is open, has a short circuit or the
sensor temperature is outside the temperature range of the
controller. When this fault occurs, the controller turns off its
relay.
2. If the controller appears to be operating incorrectly, check
that the settings are correct and that the problem is not due
to external causes.
3. Ensure all wiring connections are connected properly and
the sensor is in the correct location.
Before Leaving
1. Install the wiring cover over the wiring chamber and secure
it with the screw provided.
2. Place the front cover on the controller to conceal the setting
dials and snap the cover into place.
3. Leave this manual in a conspicuous location near the
controller for future reference.
4. Explain the operation of this controller to the end user or
anyone else who will operate the system.

9
Technical Data
T
echnical Data
Technical Data
SetPoint 150 Controller (A3040150)
Literature SetPoint 150 Controller Installation
Manual
Control Microprocessor P control; This is not a
safety (limit) control.
Package Weight 1lb. (450 g)
Dimensions 4³⁄₄"Hx2⁷⁄₈" W x ⁷⁄₈"D(120 x 74 x 22mm)
Approvals Meets DOC and FCC regulations for
EMI/RFI
Ambient Conditions Indoor use only, -20 to 122°F
(-30 to 50°C), < 90% RH non-condensing
Power Supply Class II, 24VAC ±10% 1 VA or
32 VDC ±20% 0.02 A
Relay Rating 120VAC 5AΩ¹⁄₄ hp
Pilot duty 240VA2A
Sensor NTC thermistor,10 kΩ@77°F
(25°C ±0.2°C) ß=3892
Temperature -85 to 302°F (-65 to 150°C)
Display (150m) of 18 AWG wire to sensors
Programmed 10-year memory backup
Settings
Temperature -85 to 302°F(-65 to 150°C)
Display
Setpoint -40 to 239°F (-40 to 115°C)
Operation
Differential 1to 40°F(1 to 22°C)
Time Delay 0to 19 min., 50 sec.
Operating Heating or Cooling
Mode
T
emperature Fahrenheit or Celsius
Display

10
Page 10 is blank

11
Wiring Diagrams
SetPoint 150 Controller Wired to pro Series Controls
This electrical drawing shows the connections between the
SetPoint 150 Controller and respective pro Series controls.
Wiring Diagrams

12
Wiring Diagrams
Wiring Diagrams
SetPoint 150 Controller Wired to Zone Control Module
As shown, the SetPoint 150 Controller provides input to the Zone
Control Module (ZCM) and operates the associated Motorized
Valve Actuators (MVAs) on the corresponding terminal
connections. The sensor (S1) can be placed within a concrete slab
or strapped to supply or return piping in order to operate a pump
(P1) and boiler based on a drop in temperature.

13
Wiring Diagrams
Wiring Diagrams
SetPoint 150 Controller Wired to Single-zone Pump Relay
As shown, the SetPoint 150 Controller operates a Single-zone Pump
Relay (A3010100). Place the sensor (S1) within a concrete slab or
strapped to piping to operate the pump (P1) based on a drop in
temperature.

SetPoint 150 Controller Wired to a Three-zone
Multi-pump Relay
As shown, the SetPoint 150 Controller operates a single pump
using a Three-zone Multi-pump Relay (A3080301). The sensors
(S1) can be placed within a concrete slab or strapped to piping in
order to operate a pump (P1) based on a drop in temperature.
14
Wiring Diagrams
Wiring Diagrams

15
Notes

16
Notes


www.wirsbo.com
Uponor Wirsbo, Inc.
5925 148th Street West
Apple Valley,MN 55124
Tel: (800) 321-4739
Fax: (952) 891-1409
www.wirsbo.com
Copyright © 2005 Uponor Wirsbo, Printed in the United States_SP150MAN_05
Table of contents
Popular Controllers manuals by other brands

Siemens
Siemens SIRIUS 3RW44 manual

Johnson Controls
Johnson Controls ZFR1810 installation instructions

TVC
TVC Ethos Two user guide

Power Gear
Power Gear M2 Sync Room Slideout System Installation & service manual

Becker
Becker Centronic SunWindControl SWC545-II Assembly and operating instructions

Vaillant
Vaillant VRT 350 operating instructions