Universal Input Indicator
DP70
Optional Analog Output

Page II WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]

WISCO DP70 Manual V2.0 Page III
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
สารบัญ
Universal Input Indicator ............................................................... 1
I. Example of application ................................................................... 2
II. Wiring diagram .............................................................................. 2
III. setting ............................................................................................ 3
1. Menu Input Type ............................................................................ 5
2. Menu Scale ..................................................................................... 7
3. Menu Analog Output ....................................................................... 8
4. Menu Alarm ................................................................................... 10
5. Menu Calibrate .............................................................................. 12

Page IV WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]

WISCO DP70 Manual V2.0 Page 1 of 13
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
Universal Input Indicator
DP70
-5 Digits Display
-Programmable Input type
-2 Alarm Relay
-1 Analog output or RS485
(Option)
Universal Input Indicator is panel meter with programmable input. It has
5 digit and 2 set of alarm (Hi/Low). Moreover there is optional for analog output
Specifications
Serial Interface (Optional)
Serial Standards: RS485 (Isolated)
2 Pin Terminal Block
Loading: RS485 Max 32 Unit
Distance: RS485 Length 1 Km.
Protocol: MODBUS ASCII/RTU
Supply Software: Citect, Wonderware, LAB
View etc.
Monitor
Display: 5 digits, 14.2 mm. (7-Segment)
Display Color: Red (std)
Analog Input
Number of channel: 1 Channel
Input type: Programmable
Input range:
Thermocouple (R, S, K, E, J, T, B)
RTD (Cu10, PT100, PT1000)
Resistance (0 to 600 Ω, 0 to 1200 Ω,
0 to 4000 Ω)
Voltage mVDC (0 to 80, 0 to 150 mVDC)
Voltage (0 to 1, 0 to 5, 0 to 10, 0 to 30 VDC)
Current (4 to 20, 0 to 20, 0 to 40 mA)
ADC Resolution: 16 bits
Accuracy: ± 1 least significant digit
Analog Output (Optional)
Number of channel: 1 Channel
Output type: Current, Voltage
Output range:
Current (0 to 20, 4 to 20 mA)
Voltage (0 to 1, 0 to 5, 0 to 10 VDC)
Output Impedance:
Current Max Load 800 Ω
Voltage Min Load 1000 Ω
Relay Output
Number of Channel: 2 Channels (Alarm)
Relay Type: N.O. or N.C.
Contact Rating: 6A@250VAC, 6A@30VDC
Power Requirements
Power Supply: 85 to 230 VAC
(12 to 35 VDC Optional)
Environmental Limits
Operating Temperature: 0 to 55 °C
Operating Humidity: 5 to 95% RH
Storage Temperature: 0 to 70 °C
Physical Characteristics
Dimension: W96 x H48 x D120 mm.
Panel Cutout: W90 x H40 mm.
Mounting: Panel Flush Mounting
Wiring: Screw terminals
Warranty
Warranty Period: 5 Year

Page 2 of 13 WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]
I. Example of application
Pressure
Transmitter
Input Alarm Output
Analog Output
Data Logger
II. Wiring diagram
15
A/D
24 Bit
SUPPLY
220 VAC
MCU
Display
AL1
AMP
RS485
L(+)
N(-)
16
17
VI
13
12
14+24X
+
-
2 Wire Transmitter
Jump for mA
1
2
3
4
8
6
7
5
11
10
AL2
9
+
-
Current
Voltage
+
-
+
15
16
17
V
POT
RTD
A
B
B
TC mV/Volt
15
16
17
15
16
17
15
16
17
mA

WISCO DP70 Manual V2.0 Page 3 of 13
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
III. Setting Menu
Mode 3
Input Type TC
RTD
R(Ohm)
mV
V
mA
R,S,K,E,J,T,B
Cu10,Pt100,Pt1,000
600,1200,4000
0-80,0-150
0-1,0-5,0-10,0-30
4-20,0-20,0-40
Mode
Exit
ExitMode
Exit
ExitMode
ExitMode
Exit
Exit
Mode Exit
Exit
Mode Exit
Exit
Mode Exit
1 2
Mode
Scale 0,1,2,3,4,
Max Rang
Min Rang
Mode Exit
High Value
Mode Exit
Low Value
Exit
Exit
Exit
Mode
Mode
Display

Page 4 of 13 WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]
Alarm 1 High, Low
Parameter
Parameter
Analog Output
Min Rang
Max Rang
1 2
High Value
Low Value
Mode Exit
Exit
Exit
Mode
Mode
Level
Mode Exit
Exit
Set point
Mode Exit
Exit
Hysteresis
Mode
Exit
Mode
Alarm 2 Level High, Low Exit
Mode Exit
Parameter
Parameter
Set point
Hysteresis
Exit
Mode Exit
Mode
Exit
Mode
Exit the menu by hold Exit button for 3 second

WISCO DP70 Manual V2.0 Page 5 of 13
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
Setting Menu for DP70
1. Menu Input Type
Input Type
Mode Mode Mode Mode
Thermocouple RTD R (Ohm) Voltage Current
Mode
mV
Menu Input Type is for setting type of input. DP70 has 6 type of input which
isThermocouple, RTD, R (Ohm), mV, Voltage andCurrent as detail below
Thermocouple Input
Thermocouple
Type R Type S Type K Type E Type J Type T Type B
Set upThermocouple Input push Mode button for3 secondthen choose
usingto choose for thermocouplethen using to
select thermocouple type R, S, K, E, J, T, and B. click on Exit button to go the
next step.
RTD Input
RTD
CU 10 PT 100 PT 1000
Set upRTD Input push Mode for 3 second then choose clickMode
then select then using button to select type of RTD which is Cu10,
PT100, PT1000 then click Exit button to go to the next step.
R (Ohm) Input
R (Ohm)
600 Ω1200 Ω4000 Ω
Setting R (Ohm) Input by clickMode button and hold for 3 second then
setting menu will appear click on mode button to select for
input then click to select type of desire input which areType 600 Ω, 1200
Ω, 4000 Ω then click on Exit button to go to the next step.

Page 6 of 13 WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]
mV Input
mV
0-80 mV 0-150 mV
SettingmV Input by click Mode button and hold for3 second to go setting
menuthen select to choose input type. Click onMode button to select
for mV input. Use button to choose mV type which is 0-80 mV,
0-150 mV then click on Exit button to go to the next step.
Voltage Input
Voltage
0-1 VDC 0-5 VDC 0-10 VDC 0-30 VDC
Set upVoltage Input clickMode button and hold for 3 second to go to
setting menu then select to choose input type. Click on mode button
to select for Voltage input. Use button to choose Voltage input
type which is 0-1, 0-5, 0-10, 0-30 VDC then click on Exit button to go to the
next step
Current Input
Current
4-20 mA 0-20 mA 0-40 mA
Set upCurrent Input click Mode button and hold for 3 second to getting in
to setting menu then select to choose input type. Click on mode
button to select for Current input. Use to select type of Current
input which is 4-20, 0-20, 0-40 mA then click on Exit button to go to the next
step.

WISCO DP70 Manual V2.0 Page 7 of 13
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
2. Menu Scale
Display
Scale
Mode
Hi Value
Mode
Low Value
Menu Scale is use for calibrate display scale and set up display digit.
Display
Display
0 0.0 0.00 0.000 0.0000
Display menu is for set up display digit by click Mode button and hold for 3
second to go to setting menu and the select use Mode button to
select and useto select digit type. Clcik Exit button to go to the
next step.
Hi Value
Hi Value is for set maximum value of the scale.
Click Mode button and hold for 3 second and then
select use choose then use
to select maximum desire value. Click Exit to go to
the next step
Function of each button inHi Value mode:
to increase
Mode
to decrease
changing position
Hi Value

Page 8 of 13 WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]
Low Value
Low Value is for minimum scale setting. Click Mode
button and hold for 3 second to get in to setting menu
then select on use Mode button to select
then set minimum desired value by click
Click Exit button to go to the next step
Function for each button in low value mode:
increase value
Mode
decrease value
change position
ExampleDP70
Input type 4-20 mA and display on panel as 0-100. So, Hi =100 and Low
= 0
Input= 4 mA Show0
Input= 20 mA show 100
3. Menu Analog Output
Hi Value Low Value
Com Port
Mode
Menu Analog Output set up value of analogOutput (Optional Analog Output)
Hi Value
Hi Value is for setting maximum value ofOutput. Click
Mode button and hold for 3 second. Select and
usebutton to select click on button to set
maximum desired value. Click Exit to go to next step
Function of each button on Hi Value mode:
Increase
Mode
Decrease
change position
Low Value
Hi Value

WISCO DP70 Manual V2.0 Page 9 of 13
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
Low Value
Low Value is for setting maximum value ofOutput.
Click Mode button and hold for 3 second. Select
and use Mode button to choose then set
minimum desired value by click button. Click Exit to
go to the next step
Function of each button on Low Value mode:
Increase value
Mode
Decrease value
changing position
Example DP70 Input Type is RTD (PT100) set upInput range as0-200. Hi
= 200 andLow = 0
Input= 0 °C Output = 4 mA
Input= 200 °C Output = 20 mA
Low Value

Page 10 of 13 WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]
4. Menu Alarm
Alarm Mode
Alarm 1
Mode
Set Point Hysteresis
Mode
Alarm Mode
Mode
Set Point Hysteresis
Mode
Menu Alarm is for set up alarm mode
Alarm Mode
Alarm Mode is setup by click on Mode button for
3 secondand click or to in order
to set alarm1 or alarm1 click then choose
and then set mode by click on Click on
the Exit button to go to the next step
Set Point
Set Point is setting alarm value. Click on Mode button
for 3 second then choose orand then
click mode button and choose and set value by
click . Click on Exit button to go to the next step
Function of set point mode
Increase value
Mode
Decrease value
Position Change
High
Alarm Mode
Low
Set Point

WISCO DP70 Manual V2.0 Page 11 of 13
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
Hysteresis
Hysteresis would be setup by Click on Mode button
and hold for 3 second then select or
click on Mode button and choose
then set up desire value by click . Click on Exit
button to go to the next step
Function of Hysteresis mode
Increase value
Mode
Decrease value
Position Change
Example:Input Type is4-20 mA and display value0-100
Alarm 1 set asHigh, Set Point = 80 andHysteresis = 2
Alarm 1 is on when value is more than 80 and alarm 1 is off when value is
(80-2) = 78
Alarm 2set as low Set Point = 30 andHysteresis = 1
Alarm 2 is on when value is lower than 30 and alarm 2 is off when value is
(30+1) = 31
Hysteresis

Page 12 of 13 WISCO DP70 Manual V2.0
-
(02)591-1916, (02)954-3280-1, (02)580-4427, www.wisco.co.th, [email protected]
5. Menu Calibrate
Calibrate Input Zero Span Bias
Mode Mode Mode
Exit Exit
ExitMode
Output Zero Span Mode
Exit
ExitMode
Click on and hold for 3 second to login to calibration mode
Bias Revise Offset value onY Axis, Shift graph up and down
Span Set upMax scale of Input/Output
Zero Set up min scale of Input/Output
Calibrate of Input
Input Zero Span Bias
Mode Mode
Exit Exit
Click onand hold for 3 second to login to calibration mode then choose
and Click
Calibrate Zero turns on the minimum power. Minimum input will
show on display and setup by click until get desire value an
then click Exit for save and go to the next step
Calibrate Span turns on the maximum power. Display will show the
maximum input then adjust by click then click Exit for save
and go to the next step
Calibrate Bias is for set offset value for all input. Turn on the power
and clickto adjust offset value then click Exit value to save
and go to the next step.

WISCO DP70 Manual V2.0 Page 13 of 13
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
Calibrate of Output
Output Zero Span
Exit
Measurement equipment will be needed for calibrate output such as multi
meter etc.
In order to calibrate output, Clickbutton and hold for 3 second to login
to calibration mode then choose and click to select revise function
Calibrate Zero turns on the minimum power. Minimum input will
show on display and reading output by multi meter then setup by
click until get desire value for output an then click Exit for
save and go to the next step
Calibrate Span turns on the maximum power. Display will show the
maximum input and multi meter will show maximum output then
adjust by click until got desired output then click Exit for
save and go to the next step
P.S. Display panel show only value of input. In order to display analog
output, multi meter would be needed.
Edit: 08/04/2020