Wise P535 User manual

INSTRUCTION MANUAL
MODEL : P535, P536
ITEM : PRESSURE INDICATING SWITCH

Please read instructions carefully prior to using the instrument for proper and safe operations.
Mishandling could cause device malfunctions and result in disastrous injuries or accidents.
1. Do not exceed the pressure range allowed.
2. Do not use it to measure the pressure of corrosive fluid.
Damage or rupture of pressure gauge may cause release of fluid which could
lead to bodily injury or destroy surrounding area.
3. Do not apply excessive load, vibration or impact.
4. Please use within the specified temperature ranges.
Exceeding the temperature range may cause disruption in nearby area due to damage
to the temperature indicator.
5. Please use this within the rated input and output specification range stipulated in
the specification, or it may cause equipment trouble.
6. Please use a compression terminal with insulation sheath at the end of wire.
7. Please use a cable gland of the same class or upper class.
8. Please construct wiring in accordance with consumers' electrical installation guide
and electrical facilities technical standards.
9. Make sure to turn off the valve to prevent the measuring fluid leak when dismounting
the gauge.
10. Use a pressure gauge with no oil in an environment with hydrocarbon or oxygen.
Oil contained in the gauge may react with oxygen which may be flammable or explosive.
11. Please always follow the mounting instructions in the manual in cases of field installation.
12. Do not make any modifications to the product or to add more functions.
Please consult with us for any repair.
13. Please be sure to close a valve and cut off pressure in advance in opening the case
of this product.
Please be sure to cut off power because there is a risk of electric shock if wiring
14. Work is carried out while electricity is applied.
This product cannot be used in explosion proof area.
Please use PN990( explosion proof type electric contact pressure indicator )
that is the product of our company, if necessary.
Instructions for proper and safe operation
WARNING

1. INTRODUCTION
2. APPLICATIONS
3. FEATURES
4. SPECIFICATION AND STANDARDS
5. STRUCTURE AND FUNCTION
6. OPERATING PRINCIPLE
7. CONTACT POINT WORKING TYPE AND CONNECTION
8. HOW TO SET
9. MAINTENANCE AND OPERATION
10. USE
11. INSTALLATION
12. WIRING
CONTENTS

1. Introduction
This is a contact switch pressure indicating with built-in indicator and micro switch.
Please read the user manual carefully and thoroughly before using the product
for proper and safe operations.
2. Applications
The product can be used as an indicator to process control, error alarm or warning,
in accordance with on or off signal if pressure reaches the predetermined setting.
3. Features
1) A contact switch pressure indicating is desirable when a pressure indication is
needed.
2) There are independent measuring probes for the indicator and contact switch,
so that the indications are very accurate even after the switch is mounted.
3) The micro switch performs stable on or off operations with snap actions.
4) A contact switch pressure indicating has separate indicator and setting scales
for easier setting.
4. Specification and Standards
1) Norminal diameter : 100 and 150mm
2) Accuracy
Indication range : ±1.0% of Full Scale
Alarm setting : ±3.0% of Full Scale
Repeatability : ±1.0% of Full Scale
3) Materials of wetted part : Stainless Steel
4) Connection type : 3/8", 1/2" PT, NPT & PF
5) Number of contacts : 1X SPDT or 2X SPDT
6) Working temperature : -10~60℃

7) Electrical properties
8) Measuring Pressure Range and Dead Band
-1~4 -100~400
-1~5 -100~500
-1~9 -100~900
-1~6 -100~600
-1~2 -100~200
-1~2.5 -100~250
-1~3 -100~300
400 -
-1~1 -100~100
-1~1.6 -100~160
160 -
250 -
350 -
70 -
100 -
150 -
-1~25 -100~2.5MPa
-1~10 -100~1000
-1~15 -100~1.5MPa
-1~20 -100~2MPa
40 -
50 -
60 -
Range
SET POINT
mmH20(bar)
Within 150% of
10% of Adjustable
Adjustable Range
( Between each
terminal
and case )
100MΩ 이상
( Between each
terminal and case )
125V DC 0.5A 125V DC 0.05A
ADJUSTABLE SETTING RANGE
DEAD BAND OVER RANGE
TWO SPDT
PROOF RANGE
ONE SPDT
30V DC 2A 30V DC 1A
125V DC 0.5A 125V DC 0.05A
30V DC 2A 30V DC 1A
Rated voltage Withstand
voltage
Insulation
resistance
Resistance load Inductive load
125V AC 15A 125V AC 15A 1500V AC, 50/60Hz
one minute
( Between each
terminal and case )
100MΩ or more on
500VDC
( Between each
terminal and case )
250V AC 15A
16 -
6 600
Within
SET POINT
bar
1.6 160
5% of
250V AC 15A
kPa
3 300
4 400
-1 -100
1 100
2 200
15 -
2.5 250
Adjustable
35 -
20 -
Range
25 -
10 1000

5. Structure and Function
1) Indicating type pressure switch( 100mm )
2) Indicating type pressure switch( 150mm )
브르돈관
마이크로스위치
내기
지시침
설정침
하우징
터미널 단자
(MICRO SWITCH)
(MOVEMENT)
(POINTER)
(BOURDON TUBE)
(HOUSING)
(TERMINAL BLOCK)
(SET POINTER)

6. Operating Principle
As shown in diagram below, the bourdon tube transmits the position change
according to pressure change through a lever to open or close the micro switch.
7. Contact Point Working Type and Connection
1) Upper limit contact type (HIGH ALARM)
There is one contact point to turn the circuit ON if the pressure is above the setting
or OFF if it is below the setting.
2) Lower limit contact type (LOW ALARM)
There is one contact point to turn the circuit ON if the pressure is below the setting
or OFF if it is above the setting.
설정치0 최대압력
41
52
63
(CONNECTION BOX) (MICRO SWITCH)
연결단자
,
(SET POINT) (MAX.PRESSURE)
단자대 마이크로 스위치
(CONNECTION TERMINAL)
2 3
내기
마이크로스위치
로드
(MICRO SWITCH)
(BOURDON TUBE)
(MOVEMENT)
(ROD)
브르돈관
로드
(ROD)
내기
(MOVEMENT)
(
BOURDON TUBE)
브르돈관
마이크로스위치
(MICRO SWITCH)
설정치0 최대압력
41
52
63
(CONNECTION BOX) (MICRO SWITCH)
연결단자
1,2
(SET POINT) (MAX.PRESSURE)
단자대 마이크로 스위치
(CONNECTION TERMINAL)

3) Upper and lower limits contacts type (HIGH & LOW ALARM)
There are two contacts in combination of two previously mentioned types.
They operate independently of each other.
4) Two upper limit contacts (HIGH & HIHIGH ALARM)
There are two contacts combining two upper limit contact types that operate
independently.
5) Two lower limit contacts (LOW & LOLOW ALARM)
There are two contacts in combination of two lower limit contact types that operate
independently.
8. How to Set
Use a screw driver to turn the adjustment shaft installed inside.
Settings are shown below according to contact types.
0
41
52
63
하한접점 (검정색침), 연결단자
2,3
하한접점 (적색침), 연결단자
65 ,
설정치 최대압력
(SET POINT) (MAX.PRESSURE)
(CONNECTION BOX)
단자대
(MICRO SWITCH)
마이크로 스위치
(LOW CONTACT (BLACK POINTER),
(LOLOW CONTACT (RED POINTER),
CONNECTION TERMINAL)
CONNECTION TERMINAL)
0
41
52
63
상한접점 (검정색침), 연결단자
1,2
하한접점 (적색침), 연결단자
65 ,
설정치 최대압력
(SET POINT) (MAX.PRESSURE)
(CONNECTION BOX)
단자대
(MICRO SWITCH)
마이크로 스위치
(HIGH CONTACT (BLACK POINTER),
(LOW CONTACT (RED POINTER),
CONNECTION TERMINAL)
CONNECTION TERMINAL)
상한접점 (검정색침), 연결단자
1,2
상한접점 (적색침), 연결단자
54 ,
설정치 최대압력
(SET POINT) (MAX.PRESSURE)
(CONNECTION BOX)
단자대
(MICRO SWITCH)
마이크로 스위치
(HIHIGH CONTACT (BLACK POINTER),
(HIGH CONTACT (RED POINTER),
CONNECTION TERMINAL)
CONNECTION TERMINAL)
0
41
52
63

1) Upper limit type (H)
It will be turned ON if the pressure on the rise reaches the set value of the indicator hand.
Adjust with the indicator hand to a new setting by moving it from the upper limit to
lower limit.
2) Lower limit type (L)
It will be turned ON if the decreasing pressure reaches the set value of the indicator hand.
Adjust with the indicator hand to a new setting by moving it from the lower limit to
upper limit.
9. Maintenance and Operation
1) The commercial pressure shall be below 75% of the max graduation.
2) Do not impose a pressure beyond the allowable limit.
3) Avoid sudden pressure surge or drop.
4) If there is a risk of pulsation or impact pressure, install overpressure protection device
like dampener or gauge protector.
5) Do not grease the operation parts in the pressure gauge.
6) The regular inspection shall be made once or twice in 6 months to check contact operation.
접단차
0최고압력
(Differential Gap)
설정치
설정눈금
설정침
설정조정축
설정치
(MAX.PRESSURE)
(SET POINT)
감압(DECREASING PRESSURE)
승압(RISING PRESSURE)
(SET POINT)
(SETTING SCALE)
(SETTING POINTER)
(SETTING SCREW)
접단차
0최고압력
(Differential Gap) 설정조정축
설정침
설정눈금
설정치
감압(DECREASING PRESSURE)
승압(RISING PRESSURE)
설정치
(SET POINT)
(MAX.PRESSURE)
(SET POINT)
(SETTING SCALE)
(SETTING POINTER)
(SETTING SCREW)

7) If the indication instrument makes a big error, remove it from the product for inspection.
It may have been caused by wear, corrosion, external shock, vibration, or shock of a part.
In this case, you must remove, adjust, or exchange the part.
8) The standard rated current shall follow 4. 7) but it may be different when the product is
equipped with a special micro software. Please, add some allowance to the rated current
written in this product, considering the inrush current.
9) The micro switch contact resistance is destined to increase gradually as per the elapsed time.
Under minute load in Si environment, in particular, SiO2 which is accompanied by contact
operation may deposit on the contact to increase the contact resistance abruptly, so you
must ventilate or move to a clean environment. When you use the product for control
sequence input, there is more possibility of contact disorder, so please use an AC 110/220V
buffer relay between the contact and the sequence.
10) Before you open or close the cover for pressure gauge repair or inspection, be sure to shut
off the power.
Malfunctioning of the switch may ignite the explosive gas in the gauge.
10. Use
1) When installing a gauge for the first time, it is recommended to use the valve so it can be
removed or controlled easlily.
2) It is required to find out followings before using the gauge.
- Pulsation exist? If yes, then use Dampner.
- Vibration exist? If yes, then filled the gauge with oil or use oil filled gauge.
- Is ambient temperature high? If yes, then use capillary type gauge.
3) Before using the gauge, make sure zero point is properly adjusted.
4) On the connection screw, use teflon tape or gasket to install the gauge firmly.
5) When installation is finished, slowly open the valve to find out the pointer is correctly
indicating current pressure.

11. Installation
1) Install in a place devoid of moisture, vibration, dust or corrosive gas.
2) Avoid areas that might exceed the temperature ranges specified in this manual.
3) Make sure to protect from lightning or steam.
4) Avoid areas with direct sun light.
5) Use M5 nuts and bolts to mount on a panel or wall using the mounting holes.
If mounting brackets are used, make sure it is installed securely.
6) Inlet tube should be flexible not to strain the pressure indicating switch.
7) Please use specified wrench.
12. Wiring
1) Do not stress the main body.
2) Please use proper PVC insulated wire or captire cable.
3) Use M4 crimps to connect terminals for solid contacts.
4) Please confirm contact types in the diagrams before connecting terminals.
5) In case of conduit type, use waterproof sealing fittings.
6) In case of cable gland type, use waterproof cable glands.
This manual suits for next models
1
Table of contents
Other Wise Switch manuals
Popular Switch manuals by other brands

Intelligent network solutions
Intelligent network solutions 561112 user manual

SilverStone
SilverStone CPL02-E quick start guide

Ruijie Networks
Ruijie Networks RG-S7800C Series Quick installation guide

Avaya
Avaya P333R user guide

SEKURYX
SEKURYX CK4-P102 user manual

Allied Telesis
Allied Telesis C613-02013-00 user guide