Wise P680 User manual

#1201, 122, Jomaru-ro 385beon-gil, Bucheon-si, Gyeonggi-do, Republic of Korea
Tel. +82-32-351-5751~53, Fax, +82-32-351-5754
http. Www.wisecontrol.com
USER MANUAL
WISE Control Inc.
MODEL : P680
PRODUCT NAME : DIFFERENTIAL PRESSURE INDICATION SWITCH

Please read instructions carefully prior to using the instrument for proper and safe operations.
Mishandling could cause device malfunctions and result in disastrous injuries or accidents.
1. Do not exceed the pressure range allowed.
2. Do not use it to measure the pressure of corrosive fluid.
Damage or rupture of pressure gauge may cause release of fluid which could
lead to bodily injury or destroy surrounding area.
3. Do not apply excessive load, vibration or impact.
4. Please use within the specified temperature ranges.
Exceeding the temperature range may cause disruption in nearby area due to damage
to the temperature indicator.
5. Please use this within the rated input and output specification range stipulated in
the specification, or it may cause equipment trouble.
6. Please use a compression terminal with insulation sheath at the end of wire.
7. Please use a cable gland of the same class or upper class.
8. Please construct wiring in accordance with consumers' electrical installation guide
and electrical facilities technical standards.
9. Make sure to turn off the valve to prevent the measuring fluid leak when dismounting
the gauge.
10. Use a pressure gauge with no oil in an environment with hydrocarbon or oxygen.
Oil contained in the gauge may react with oxygen which may be flammable or explosive.
11. Please always follow the mounting instructions in the manual in cases of field installation.
12. Do not make any modifications to the product or to add more functions.
Please consult with us for any repair.
13. Please be sure to close a valve and cut off pressure in advance in opening the case
of this product.
Please be sure to cut off power because there is a risk of electric shock if wiring
14. Work is carried out while electricity is applied.
This product cannot be used in explosion proof area.
Please use P970, P990( explosion proof type electric contact pressure indicator )
that is the product of our company, if necessary.
Instructions for proper and safe operation
WARNING

1. INTRODUCTION
2. FEATURES
3. SPECIFICATION AND STANDARDS
4. STRUCTURE AND FUNCTION
5. OPERATING PRINCIPLE
6. TRANSPORTATION, STORAGE AND OPENING
7. CONTACT POINT WORKING TYPE AND CONNECTION
8. INSTALLATION
9. WIRING
10. MAINTENANCE AND OPERATION
CONTENTS

1. Introduction
P640, P680 Series is a differential pressure indication switch product with a built-in
micro switch, and is so designed that it can be used for corrosive fluid or high pressure process.
The switch is divided into a sensor part under pressure, a control part that regulates
the set value and inflow pressure, and a micro switch that gives contact output.
Micro switch is a high-precision product designed so that it can be operated by
minute pressure change, and has various rated current values. Please correctly use
this product after having thorough knowledge of this instruction manual that states
how to use it respectively in case of intending to use this product.
2. Features
This product can be used for turning on an abnormality alarm or warning light, or
process control according to ON-OFF signal in case of reaching the set differential
pressure. And it cannot be used in explosion proof area.
3. Specification and standards
1) Nominal diameter : 160mm
2) Accuracy : ±1.0%, ±1.5% of Full Scale
3) Repeatability : ± 1.0%, ±1.5% of adjustable range
4) Static pressure : Max. 100 bar
5) Number of contacts : 1 X SPDT or 2 X SPDT
6) Notes in accordance with Pressure Equipment Directive 97/23/EC
- The pressure gauges are "Pressure accessories" in accordance with Article 1, Paragraph 2.1.4
- The pressure gauges carry CE marking for Fluid Group 1G in accordance with Annex 2,
Table 1.
- Pressure gauges that do not carry the CE marking are manufactured in accordance with
Article 3, Paragraph 3 "Sound engineering practice".

7) Electrical properties
■ P680 Series

4. Structure and Function
⑤
⑥
①
⑦
②
⑧
③
⑨
④
NO.
①
②
③
⑥
⑦
⑨
Terminal Box Box to which a terminal is mounted.
U- bolt A device that fastens the mounting bracket to 2-inch pipe
⑤Air vent A device that releases air from the piping to the outside in
pressure transducing.
⑧Mounting bracket A device used in case of intending to mount a differential
pressure gauge on measurement position
Differential pressure
gauge body
Pressure measurement equipment to which a
measurement device is mounted.
④3-WAY MANIFOLD
A device that enables valve to be opened in consecutive
order in pressure transducing, in order to prevent a
differential pressure gauge from being damaged.
Zero adjustment screw Adjust zero point according to the mounting position.
Impulse pipe Connection tube for the differential pressure gauge body
and 3-way manifold
NAME FUNCTION REMARKS
Differential pressure
scale plate
Indicate pressure difference between two
points, and flow rate. 160mm
LOW
PRESSURE
HIGH
PRESSURE

5. Operating Principle
④
③
②
①
1) If pressure comes in the pressure transducing part of high pressure side and the pressure
transducing part of low pressure side, ①bellows will shrink by differential pressure between
two points. Then, ②ROD connected to the bellows moves in the right and left direction.
And ③SHAFT and ④POST, which is connected to the indicating part of differential
pressure gauge, rotates by this moving distance, and indicates differential pressure.
2) In case of bellows, high pressure side and low pressure side is made to be separated.
And a uniform moving distance is made to occur by combination with spring according
to the differential pressure range.
6. Transport, storage, and opening
1) Attention in case of transportation
Please pay sufficient attention to transportation because damage can be caused
in terms of performance, in case of being impacted by a fall.
2) Attention in case of storage
Please store it at the place with little humidity and the place where there is no
vibration and dust.
In case of multi-level stacking, the weight should be to a degree where packing
box isn't deformed. And always store the product so that it cannot fall.
LOW
PRESSURE
HIGH
PRESSURE

3) Attention in case of opening a package
Please carefully handle the object in case of opening a package.
Please take out the product at the sufficiently wide place in order not to drop the
object by mistake in taking out it.
7. Contact Point Working Type and Connection
1) P680

8. Installation
1) Store this product free of moisture, vibration, dust or corrosive gas.
2) Avoid higher temperature than specified in this manual.
3) Be prepared for lightning or vapor.
4) Avoid direct sunlight.
5) Use M5 bolts when fixing the product to the panel or wall through fixing holes.
When you use fittings, fix them firmly.
6) Use a flexible tube for the impulse line to prevent excessive force on the pressure gauge.
7) For pipe connection, do not grab and turn the product case, rather use a designated
spanner.
9. Wiring
1) Please be careful not to overstrain the body.
2) Please use vinyl sheathed wire, cabtyre cable, etc. suitable for load.
3) Please firmly wire a terminal block by using a compression terminal for M3.
4) Please carry out wiring after checking the contact type in the mark of wiring diagram.
5) Please use waterproof sealing fitting in case of conduit type.
6) Please use waterproof cable gland in case of cable gland type.
7) You should use a ground wire with a thickness of 0.7sq or over.
10. Maintenance and Operation
1) The commercial pressure shall be below 75% of the max graduation.
2) Do not impose a pressure beyond the allowable limit.
3) Avoid sudden pressure surge or drop.
4) If there is a risk of pulsation or impact pressure, install overpressure protection device
like dampener or gauge protector.
5) Do not grease the operation parts in the pressure gauge.
6) The regular inspection shall be made once or twice in 6 months to check contact operation.
7) If the indication instrument makes a big error, remove it from the product for inspection.
It may have been caused by wear, corrosion, external shock, vibration, or shock of a part.
In this case, you must remove, adjust, or exchange the part.
8) Standard rated current is based on 3.6). However, it may be different in case of having

a MICRO S/W built-in. Therefore, please use it with a tolerance in consideration of
inrush current etc. within the rated current marked on this product.
9) The contact resistance of micro switch increases little by little, as time passes.
Especially, in case of small load, contact resistance increases in a short period of time
because "SiO2" accompanied with contact operation is accumulated at the contact part
in the environment where "Si" is contained. Therefore, please carry out ventilation or
use it in the clean environment. In particular, in case of using it for inputting sequence
for control, a contact fault may occur for this reason. Therefore, please use bufferrelay
for AC 110/220V between contact and sequence.
10) Please open and close the cover surely after cutting off power, in case of carrying out
work in order to repair or check the pressure gauge.
This manual suits for next models
2
Table of contents
Other Wise Switch manuals
Popular Switch manuals by other brands

Intelligent network solutions
Intelligent network solutions 561112 user manual

SilverStone
SilverStone CPL02-E quick start guide

Ruijie Networks
Ruijie Networks RG-S7800C Series Quick installation guide

Avaya
Avaya P333R user guide

SEKURYX
SEKURYX CK4-P102 user manual

Allied Telesis
Allied Telesis C613-02013-00 user guide