Rev. Date Editor Changes
D 2013-09-12 GG New device features & updates with software version 1.2005
nThe easYgen provides LogicsManager equations to release frequency control LM 00.96
and/or voltage control LM 00.97. The operator can now from outside determine when
which control is executed.
For details refer to:
–Release f-control parameter ID 12909 Ä p. 308
–Release V-control parameter ID 12938 Ä p. 327
nThe easYgen provides a third active power setpoint, which can be switched like setpoint 1
and 2 from outside. Refer to Setp. 3load parameter ID 12998 Ä p. 315 for details. (Benefi‐
cial, when demanded VDE-AR-N 4105).
nThe reactive power controller additionally provides the reactive power regulation at the
interchange point. Refer to
Ä Chapter 4.5.12.6.1 “Control The Power Factor / Reactive
Power At The Mains Interchange Point” on page 328
for details.
nLoad sharing: The ramping of an engine onto others will be interrupted if not enough nom‐
inal power on the busbar is available. Refer to
Ä Chapter 4.5.12.7 “Load Share Control”
on page 336
for details.
nThe easYgen provides a voltage restraint Time Over Current Relay (ANSI 51 V). Refer to
Ä Chapter 4.4.1.17 “Generator Voltage Restrained Overcurrent Monitoring - ANSI #51”
on page 137
nThe easYgen provides an external mains kvar sensing (via analog input). Refer to
Ä Chapter 4.2.3 “External Mains Reactive Power” on page 103
for details.
nThe df/dt monitoring (ROCOF-Relay) is additionally applicable with Phase Shift Monitoring.
Refer to
Ä “Phase shift” on page 159
for details.
nThe QV monitoring function according the German grid code VDE-AR-N 4105 depends on
the parameter "phase-phase/ phase-neutral monitoring" (Even if the grid code requires
only phase/phase). Refer to
Ä Chapter 4.4.2.9 “QV Monitoring” on page 157
for details.
nA dedicated LogicsManager is installed to disable all mains monitoring and the decoupling
function. The mains decoupling function can be released or blocked from outside now.
Refer to
Ä Chapter 4.4.2.16 “Blocking of Mains Protection” on page 170
for details.
nThe easYgen allows, under given circumstances, the external closure of GCB and MCB in
synchronization mode “Off” being in AUTOMATIC. Refer to
Ä Chapter 4.5.1.10 “Synchro‐
nization” on page 232
for details.
nThe easYgen synchronizer allows a negative slipping frequency at the interchange point
for synchronization the MCB. This avoids in critical application exporting of power short
after synchronization the MCB. Refer to
Ä Chapter 4.5.1.9 “Breakers MCB” on page 229
for details.
nThe Neutral Interlocking feature controls a Neutral Contactor (NC) of each generator. The
rule is that only one neutral contactor of all running generators are closed. The Logic must
ensure that with changing of generators the neutral link is passed over to another running
generator. Refer to
Ä Chapter 4.5.1.11 “Neutral Interlocking” on page 234
for details.
nThe Generator monitoring can be blocked with a LogicsManager equation. This supports
application, where the engine/generator monitoring shall be released or blocked from out‐
side.
nThe easYgen provides 4 configurable alarms with all related settings and free editable
alarm texts. Refer to
Ä Chapter 4.4.6.2 “Free Configurable Alarms” on page 200
for
details.
nThe setting range for number of teeth of the Magnetic Pickup Unit is expanded. Refer to
Ä Chapter 4.5.9.3 “Magnetic Pickup Unit” on page 273
for details.
nThe easYgen provides 8 dedicated thresholds out of the 40 flexible thresholds with an
additionally configurable delay-off time. The flexible thresholds no. 25 through 32 are used.
This feature ensures other functionalities, like for example load shedding. The individual
fall-back times can be taken to generate 8 steps with individual priorities. Refer to
Ä Chapter 4.4.5 “Flexible Limits” on page 194
for details.
nThe easYgen can automatically check, whether I/O expansion boards are connected. If not
the easYgen disables accordingly functionalities, which are not needed and improves
thereby the performance of HMI, Toolkit and Modbus.
General Information
About This Manual > Revision History
37532G easYgen-3100/3200 P1/P2 | Genset Control 19