Wormald 08451 User manual

WORMALD FirePro Aerosol System
Operation and Maintenance Manual
Model 08451
Rev 2.1

Page | 2
Contents
1 Introduction................................................................................. 3
1.1 General Information............................................................. 3
1.2 How Does it Work................................................................ 3
1.3 In Case of Fire..................................................................... 3
2 Components List .......................................................................... 4
3 Design Considerations .................................................................. 5
3.1 Power Supply Input.............................................................. 5
3.2 Agent Released Input........................................................... 5
3.3 Siren/Strobe Output............................................................. 5
3.4 Discharge Output................................................................. 5
3.5 Circuit 1 Alarm Output.......................................................... 6
3.6 Circuit 2 Alarm Output.......................................................... 6
3.7 Mounting ............................................................................ 6
3.8 Cabling Requirements .......................................................... 7
3.9 Connecting Multiple FirePro Generators.................................. 7
4 Installation .................................................................................. 8
5 Wiring Diagram.......................................................................... 13
6 Programming ............................................................................. 14
7 Operation .................................................................................. 14
7.1 LED Indicators................................................................... 14
7.2 Isolate Function................................................................. 14
7.3 Reset Function................................................................... 15
7.4 Test Function .................................................................... 15
7.5 Discharging the Fire System................................................ 15
7.6 Alarm Silence .................................................................... 15
8 Commissioning and Test Procedure.............................................. 16
9 Servicing and Maintenance.......................................................... 17
9.1 Daily Service Schedule ....................................................... 17
9.2 Semi-annual / Annual Service Schedule ............................... 18
10 Troubleshooting ......................................................................... 18
10.1 Internal Faults ................................................................... 18
10.2 External Faults................................................................... 18
11 Specifications............................................................................. 19
12 RFI Environments....................................................................... 20
13 Safety Data Sheet (SDS) - FirePro................................................ 20
14 Vehicle and Mobile Plant Installation Notes (AS5062) .................... 21

Page | 3
1Introduction
1.1 General Information
The FirePro FP-08451 Fire Control Panel is a combined detection and extinguishant system,
and is compliant for use in both marine (AMSA NSCV) and vehicle installations (AS5062).
The FIP (fire indicator panel) incorporates:
-2x Detection circuits;
-1x Extinguishing Discharge circuit;
-1x Siren/Strobe circuit;
-1x Agent Release Notification circuit;
-Programmable Activation (automatic and/or manual);
-Fault Monitoring system;
-Isolation Function.
1.2 How Does it Work
All FirePro Aerosol Generators use the latest generation FPC solid compound. Upon activation,
the solid compound is transformed into a rapidly expanding, highly efficient gas, based on
Potassium salts. It does not deplete oxygen levels. The built-in fail-safe activation system
ensures operation of the generators when required, even if everything else fails. At 300⁰C the
FPC block changes to a potassium-based gas to extinguish the fire.
Ozone Depletion Potential (O.D.P.) = 0
Atmospheric Life Time (A.L.T.) = 0
Global Warming Potential (G.W.P.) = 0
Non-corrosive & Non-toxic
1.3 In Case of Fire
If a fire occurs, equipment operators should do the following:
1. Detection will initiate an alarm condition on the FirePro System
2. The siren/strobe will operate and if shutdown relays have been installed, equipment
shutdown will be initiated.
3. Evacuate all personnel from the risk area and alert the Fire Brigade.
4. Close all hatches and openings, and shutdown engines and any extraction fans or vents.
5. Manual Activation: Press and hold both mode switches continuously for 5 seconds to
activate the system.
6. Automatic Activation: The control panel will automatically begin the activation sequence
when fire has been detected on Circuit 1 Alarm.
7. Keep the FirePro suppression gas within the risk until the fire is extinguished and not able
to re-ignite.
8. Do not start engine or fans until the fire is extinguished. Operating the exhaust fans will
enable the gas to escape the risk area and could allow the fire to re-ignite.
9. Do not enter the risk until it has been rendered safe.
10.Recommended clean up after discharge is with soapy water and a cleaning agent based on
citric acid.
11.Following a discharge, replace all installed FirePro Generators and Thermal Fuse Couplings.

Page | 4
2Components List
FP-08451
Fire Control Panel
Detection and extinguishant
control system
2x DP-3000
4x DP-2000
2x FP-08950
1x
1x
1x
Deutsch Plug 3 Pin M/F, c/w heatshrink
Deutsch Plug 3 Pin M/F, c/w heatshrink
End-of-line Plug 22kΩ (Detection)
End-of-line Diode 1N4004 (Siren/Strobe)
End-of-Line Resistor 3k3Ω (Discharge)
Operator’s Manual
Agent Release Circuit
Siren / Strobe Circuit
FP-08825
Thermal Fuse Coupling
FP-08940
Siren/Strobe
Discharge Circuit
FirePro Aerosol
Generator
100g –500g Unit.
Constructed from Stainless Steel.
Comes with installed Deutsch Plug
for easy install
FP-6200
Heavy Duty Bracket 316 SS.
Suits FP-100, 200, 500 FirePro
Aerosol Generators.
FirePro Aerosol
Generator
1200g –5700g Unit.
Constructed from Stainless Steel.
Comes with installed Deutsch Plug
for easy install.
FP-6100
Heavy Duty Bracket 316 SS.
Suits FP-1200, 2000, 3000 5700
FirePro Aerosol Generators.
Detection Circuit (Circuit 1 Alarm & Circuit 2 Alarm)
FP-08920
Marine Grade Thermal Detector
60°C Fixed. Other temperatures
available on request.
FP-14053
Manual Actuator
Internal OR External
FP-09510
Linear Heat Detection Cable 182° C
FP-09511
Linear Heat Detection Installation kit.
Mounting Clips, 2x Junction Boxes
with strain relief cable glands and 1x
EOL for monitoring.
Installation Components
Service Components
FP-09500
2 Hour Fire Rated Shielded Cable.
FP-08960
Signage for the System. A sheet of
different size labels.
FP-08919
Wiring loom and Splitter Cable for
installaion of multiple FirePro
generators.
FP-08800
FirePro Simulator –for Testing &
Commissioning.
Additional Modules
FP-08850
Discharge Delay Module
Allows additional FirePro generators
to be discharged
FP-08860
Shutdown Relay Module
Provides facility for equipment
shutdown
FP-08870/8871/8872
Power Control Module
Provides back up power for control
panel.

Page | 5
3Design Considerations
3.1 Power Supply Input
The FP-08451 Fire Control Panel provide a single power supply input that is compatible with
12 / 24vDC. If adequate power is not supplied, the LEDs will not be illuminated, and the
control panel will not operate. The main power supply should be connected directly to a battery
or power source, not through a distribution board. The main power must not be interrupted
if the vehicle/equipment is powered down. The FirePro Battery Lead (P/N FP-14016) may be
used to connect power to the control panel. If a secondary power supply is required for an
installation, the FP-08870/08871 Power Control Module will be required.
3.2 Agent Released Input
The Agent Released input provides an indicator to the operator to notify if the suppression
system has been activated. For the indicator to operate, the FP-08825 Thermal Fuse Coupling
must be used. Thermal Fuse Couplings are single use only. If the suppression system has
operated, the thermal fuse coupling must be replaced. If the Agent Release output is not
used, the circuit must be bridged out and sealed using the supplied deutsch plugs.
3.3 Siren/Strobe Output
The recommended siren/strobe is the Flashni Xenon Sounder Beacon. In a typical install, the
maximum number of supported sirens/strobes that can be installed is 5. When installed,
Siren/Strobes are to be clearly visible and audible at all points around the risk area.
The siren/strobe output is a monitored circuit. The supplied end-of-line diode (1N4004) must
be installed on the last siren/strobe in the circuit, otherwise the fire control panel will display
a fault. If a siren/strobe is not used, the supplied end-of-line diode (1N4004) must be
connected to the siren output using the supplied deutsch plugs.
3.4 Discharge Output
The maximum number of FirePro generators able to be discharged by the FP-08451 Fire
Control Panel is limited by the voltage of the main power supply. That is:
Voltage 12vDC Max = 2 Units
Voltage 24vDC Max = 4 Units
If a risk area requires a greater number of FirePro generators to be discharged than the
standard panel can provide, the FP-08850 Discharge Delay module can be used. The module
will discharge generators in multiples up to the maximum as above.
If the number of FirePro generators connected to each output is greater than the
maximum, the fire system will not operate.
When multiple FirePro generators are connected to a single output, they must be connected
using the FP-08919 Splitter Lead (see 3.9 Connecting Multiple FirePro Generators).
If a suppression system is not used, the supplied end-of-line resistor (3k3Ω) must be connected
to the Discharge output using the supplied deutsch plugs.

Page | 6
3.5 Circuit 1 Alarm Output
The Circuit 1 Alarm Output is a zoned detection circuit capable of operating up to 30
conventional detectors, 100 metres of linear heat detection cable or 30 manual actuators.
The Circuit 1 Alarm Output can be programmed for detection and alarm, or for automatic
discharge if an alarm is detected on this circuit (see 6. Programming).
The supplied end-of-line resistor (22kΩ) must be installed on the last detector or manual
actuator in the circuit, otherwise the fire control panel will display a fault. If detection is not
used, the supplied end-of-line plugs (marked green) must be connected to the Circuit 1 Alarm
output.
3.6 Circuit 2 Alarm Output
The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30
conventional detectors, 100 metres of linear heat detection cable or 30 manual actuator.
The Circuit 2 Alarm Output is a detection and alarm circuit only. When in alarm condition the
siren/strobe will operate, however the suppression system will not discharge until manually
operated.
The supplied end-of-line resistor (22kΩ) must be installed on the last detector or manual
actuator in the circuit, otherwise the fire control panel will display a fault. If detection is not
used, the supplied end-of-line plugs (marked green) must be connected to the Circuit 2 Alarm
output.
3.7 Mounting
For correct installation, the Fire Control Panel must be mounted by four bolts or screws through
the mounting holes in the flange on both sides of the Module. No penetrations are to be
made through the casing of the panel.
The Fire Control Panel enclosure is rated IP65, so should be installed in a convenient location,
away from where it may be affected by large amounts of water.
It is necessary to complete all wiring and any programming of the detection mode prior to
mounting the panel.
Dimensions and relevant clearances for installing the FP-08451 Control Panel are below. A
Dash Mount Bracket (P/N FP-08451B) is also available and may be used if the minimum
clearances cannot be met.
08451 Control Panel
Mounting Bracket

Page | 7
3.8 Cabling Requirements
When constructing extension leads the supplied Deutsch Plugs must be used to ensure water-
proof connections are made throughout the installation.
1. Cut cable to required length and strip outer insulation to approximately 25-30mm.
2. Strip inner insulation to approximately 6mm and using a Deutsch Crimping tool, fix pins to
the exposed ends of the cable, including the earth where applicable.
3. Place heat shrink over the end of the cable.
Identify correct socket on plug by the
numbers/letter on the side of the plug and
push through the gasket at the bottom of the
plug until a click is heard and the pin is locked
in place.
4. Place the locking mechanism inside the plug to ensure pins remain secure. (Male plugs;
locking mechanism is orange. Female plugs; locking mechanism is green).
5. Using the heat shrink, seal the back of the
plug.
Cables are colour coded for easy identification.
When installing system, cables should be only
connected to the correctly coded cable. Colour
Coding for cables is as follows:
3.9 Connecting Multiple FirePro Generators
If multiple FirePro Generators are being installed on a single output, they must be connected
using the FP-08919 Splitter Lead. The Splitter Lead enables the activation current to pass
uninterrupted to all connected FirePro generators and allows for continuous monitoring.
Splitter Leads can be installed at any point on the activation circuit and do not need to be
installed adjacent to the fire control panel or the discharge delay module. For ease of install,
servicing and more efficient field wiring, Splitter Leads should be installed in areas easy to
Colour
Circuit
Red
Power Supply
Yellow 1
Activation
Yellow 2
Activation Delayed
Green 1
Detection 1
Green 2
Detection 2
Blue
Discharge Advice
Orange
Siren/Strobe
White
Relay Output

Page | 8
access and should be used to minimise the required extension leads, and to bypass obstacles.
4Installation
FirePro generators must remain disconnected until system is completed and fire control panel
is no longer in a fault or alarm condition. The FirePro Test Module (P/N FP-08800) can be used
to take the panel out of a fault condition.
Note: Any required extension leads must be constructed as per the instructions in 3.8 Cabling
Requirements.
Note: It is recommended that one circuit is installed and connected at a time to isolate the
cause of any faults that may occur during installation. The supplied End-of-line plugs and Test
Module may be used to keep the control panel out of a fault condition.
1. Power: When panel has been mounted in a suitable location, connect main supply power
using a FP-14016 Battery Lead to the power input (marked red).
Where a Power Control Module (FP-08870 / 08871) is used,
the battery lead should be connected to the “Primary Power
Supply” Input and the “Battery Backup” output to the control
panel. The internal battery connection will need to be
connected for the control panel to operate.
See FP-08870 / 08871 product manual for further
details.

Page | 9
2. Agent Released Circuit: The Thermal Fuse Coupling (P/N FP-08825) should be screwed
into the thermal port on one of the installed FirePro generators and connected to the control
panel.
3. Siren/Strobe Circuit: Mount the siren/strobe (P/N FP-08940) in a location where it is
visible and audible in all points with the risk area and connect to the “Siren” output on the
module (marked orange). If more than one siren/strobe is being installed, they are to be
connected using the secondary positive/negative terminals in the sounder.
The supplied end-of-line diode should be installed in the secondary positive/negative
terminals of the last siren/strobe in the circuit. The diode is polarised, so the positive lead
of the diode (marked with a grey band) should be terminated in the positive terminal of
the siren/strobe, otherwise a fault will occur on the fire control panel.
Where a Siren & Shutdown Module (FP-08860) is used, the module should be connected
to the “Siren/Strobe” output on the control panel. The siren/strobe should be connected
to the “Siren” output on the module (marked orange) and the relay connected using the
“Shutdown Relay” output (marked white). See FP-08860 product manual for
further details.

Page | 10
The Siren & Shutdown Module allows for programming of the delay prior to shutting down
equipment and for the relay to be set to either normally open or normally closed Note:
The Siren/Strobe or end-of-line diode must be connected for the relay to operate.
Delay Timer Switch
Mode
Relay State Switch
Mode
Switch 1 –ON
Switch 2 –ON
DELAY Set to
1 second
Switch - ON
Relay set to
NORMALLY OPEN
Switch 1 –OFF
Switch 2 –ON
DELAY Set to
5 seconds
Switch 1 –ON
Switch 2 –OFF
DELAY Set to
10 seconds
Switch - OFF
Relay set to
NORMALLY CLOSED
Switch 1 –OFF
Switch 2 –OFF
DELAY Set to
15 seconds
4. Circuit 1 Alarm Circuit: This circuit can be programmed for ALARM ONLY (operate
siren/strobe) or AUTOMATIC DISCHARGE (discharges suppression system and operates
siren/strobe). If detection is not used, the supplied end-of-line plugs (marked green) must
be connected to the Circuit 1 Alarm output.
-Manual Actuator: (P/N FP-14053) can be connected together in quantities up to 30.
If a manual actuator is being used for remote activation, it must be installed on Circuit
1 Alarm. The supplied end-of-line plugs (marked green) must be connected to the last
manual actuator in the circuit.
-Linear Heat Detection: Linear Heat Detection can be installed in lengths up to 100m.
Any terminations of cable must be enclosed using sealed, metal enclosures from the
LHD Install Kit (P/N FP-09511). P-Clips must be installed at intervals of 50cm maximum
to support the cable. The supplied End-of-line junction box must be installed on the
end of the cable.
-Detection Not Used: If detection is not used, the supplied end-of-line plugs (marked
green) must be connected to the Circuit 1 Alarm output.

Page | 11
5. Circuit 2 Alarm Circuit: This circuit is ALARM ONLY and will only operate the
siren/strobe. Connections for detection and manual actuator are the same as Circuit 1
Alarm. If detection is not used, the supplied end-of-line plugs (marked green) must be
connected to the Circuit 2 Alarm output.

Page | 12
6. Discharge Circuit: This circuit should remain disconnected until all other circuits are
connected. The control panel must not be in an alarm/fault condition when the FirePro
generators are connected, as this may cause an accidental discharge. A Test Module (P/N
FP-08800) should be connected to take the control panel out of fault condition and for any
commissioning.
-Mounting FirePro Generators: FirePro Generators must be installed using only
approved brackets with observation of the relevant stream lengths and thermal
clearances noted in the design calculation and risk assessment. Generators should be
mounted near the top of the risk area, with care taken to aim generators away from
openings or obstacles that may impede dispersion of the suppression agent. Egress
routes for personnel must be kept clear, and not be obstructed by any installed
components or by agent dispersion.
-Connecting FirePro Generators: If a single FirePro Generator is being installed, it
can be connected directly to the Discharge output on the control panel.
If multiple FirePro Generators are being installed on a single output, they must be
connected using the FP-08919 Splitter Lead. See 3.4 Discharge Output, for design
considerations when connecting multiple FirePro generators. The maximum number of
FirePro Generators that can be connected will depend on the main power supply.
-Discharge Not Used: If the discharge circuit is not used, the supplied end-of-line
resistor (3k3Ω) must be connected to the Discharge output using the supplied deutsch
plugs.

Page | 13
5Wiring Diagram

Page | 14
6Programming
The FP-08451 Control Panel provides several programming options,
allowing it to be adapted to site conditions. The 2-way DIP switches
inside the panel next to the terminal block allow one of 4 modes to
be selected. To access the DIP switches, open the panel enclosure.
Note: All programmed settings should be recorded in the logbook.
Note: If a Discharge Delay Module (P/N FP-08850) is installed, panel must be programmed for
extended discharge.
7Operation
7.1 LED Indicators
The FP-08451 Control Panel uses LED indicators to notify the
operator of the condition of the control panel and each of the
monitored circuits. If an LED is illuminated, it indicates the following:
Circuit
LED
Condition
Power
Power supply is available
Circuit 1 Alarm
System is in alarm condition
Circuit 2 Alarm
System is in alarm condition
Fault
System is in fault condition and needs servcing
Isolated
System has been isolated using buttons on panel
Discharging
System has initiated activation sequence
Agent Released
Agent has been released and needs servcing
7.2 Isolate Function
To isolate the control panel, press and hold Mode Switch 1 until a 1
beep is heard and the “Isolated” LED is illuminated.
To restore the control panel to normal operation, press Mode Switch 1 and ensure the
“Isolated” LED turns off.
Isolating disables automatic activation. Manual Activation will remain operational.
When isolated, the control panel continues to monitor for alarm and fault, and show the alarm
and fault indications, but will not operate the siren and the automatic discharge. When
isolated, any change in the detector status, will cause the panel sounder to operate for 1
second as an alert of the status change, but the panel will remain isolated.
The isolate function will also silence the siren/strobe and the internal sounder but will not
cancel the alarm or fault indication.
Switch 1
Mode
Switch 2
Mode
OFF
Standard Discharge
Power Applied for 2
seconds
DEFAULT
OFF
Manual Discharge
Detectors operate
siren/strobe only
ON
Extended Discharge
Power applied for 240
seconds
ON
Automatic Discharge
Detection on Circuit 1
Alarm will discharge
system
DEFAULT

Page | 15
7.3 Reset Function
To reset the control panel, press and hold Mode Switch 1 until 2 beeps are heard. Following
a reset, the control panel will automatically isolate. To restore the control panel to normal
operation, press Mode Switch 1 and ensure the “Isolated” LED turns off. Note: The control
panel cannot be reset if the activation sequence has been initiated. When the “Discharging”
LED is no longer illuminated, the reset function will become available again.
7.4 Test Function
The control panel includes a test function, enabling the operator to ensure that the control
panel is functioning correctly. To operate the test function, press and hold Mode Switch 1 until
3 beeps are heard. The test function will illuminate all LEDS on the control panel and operate
the internal sounder and any external siren/strobes for 2 seconds, and then return the control
panel to normal operation. The test function does not activate the suppression system. Note:
If any LEDS or siren/strobes do not operate, contact your supplier.
7.5 Discharging the Fire System
To manually discharge the fire system, press and hold both Mode Switch 1 and Mode Switch
2 continuously for 5 seconds. This will immediately operate any installed siren/strobes and
any shutdown relays, to warn any occupants. Manually discharging the fire system should only
performed during commissioning/servicing when the system has been appropriately isolated,
or in case of fire.
7.6 Alarm Silence
To silence the internal sounder and any installed siren/strobes that have operated due to an
alarm condition, press and hold Mode Switch 1 until a 1 beep is heard and the “Isolated” LED
is illuminated. This will also override any installed shutdown relays and allow for operation of
the equipment. Note: Equipment should not be operated until it has been rendered safe by
the appropriate authority. The control panel will remain in an alarm/fault condition until
serviced and reset.

Page | 16
8Commissioning and Test Procedure
Commissioning should be performed when the fire control panel is not in an alarm/fault
condition. Note: No personnel should be in the risk area until the fire system is fully isolated.
Six Monthly Test Procedure:
1. Isolate the control panel (see 7.2 Isolate Function) and disconnect the
any installed FirePro aerosol generators. This will generate a fault on the
fire control panel.
2. Connect a FP-08800 Test Module to the “Discharge” output to the panel
(marked yellow). Turn off the Isolate function.
3. Control Panel and components
-Clean and remove dirt, grease or foreign material. Replace any parts
that appear damaged or are painted.
-Check all indicators are in normal position.
4. FirePro Aerosol Generators
-Inspect FirePro generators to ensure they are in good condition.
-Check mounting brackets are in good condition and secure.
-Check Dust Covers are in good condition –replace as necessary.
-Check FirePro Units are pointing at predetermined aiming points.
5. Electrical Actuation system –
-Check Manual Actuators are secure, clean, undamaged.
-Check that anti-tamper seals/pull pins are in place and secure.
-Check Detection system: wiring, connection and supports are in intact, not damaged
and in correct position.
6. Labels Check manual release, system warning and instruction labels are securely in place,
visible and legible.
7. Test the fault monitoring system by disconnecting and reconnecting all connected detection
devices and the siren strobe circuit one at a time. Ensure the “Fault” LED indicator
illuminates and the internal sounder is heard each time a circuit is disconnected.
8. Discharge Testing from Control Panel
-Perform a manual discharge test by pressing and holding both mode switches on the
panel continuously for 5 seconds.
-Following activation, ensure the Test Module has operated.
-Isolate the panel to silence alarm. Panel should now display a fault.
-Reset Test Module. Panel should no longer be in fault condition.
-Turn off the Isolate function.

Page | 17
9. Discharge Testing from External Devices : Each detection and manual actuator device
connected to must be tested individually.
-Perform an automatic discharge test by activating the detectors or manual actuators.
-Following the activation sequence ensure the Test Module has operated.
-Isolate the panel to silence the alarm. The control panel should now display a fault.
-Reset the Test Module.
-Reset the control panel by pressing and holding a single mode switch until 2 beeps are
heard. The control panel should no longer be in alarm/fault condition.
10. System control and indicating equipment.
-During discharge test, ensure operation of all installed siren/strobe(s).
-During discharge test, ensure operation of all installed shutdown relays. This must
shutdown any equipment specified in the risk assessment.
-Test backup battery capacity. Replace every backup battery every 2 years.
11. Disconnect the FP-08800 Test Module and reconnect all FirePro aerosol generators.
12. Turn off the Isolation function. System is now operational.
Additional requirements for Commissioning of a System after Install or Discharge
13. Design Survey - check against the baseline data, for alterations, changes in use or
operating environment, or other factors that could affect the performance of the fire
protection system.(Annual)
14. Risk Assessment –required to be prepared and reviewed every 5 years or after any
incident. Review document to ensure system compliance. Check if document is current.
9Servicing and Maintenance
Inspection and servicing of the installed fire system should occur in accordance with the
relevant Australian Standards (i.e. AS1851 or AS5062).
Any alterations to the risk area should be recorded and where necessary the risk assessment,
design calculation and installed components must be revised to reflect the new operating
conditions.
A logbook must be kept, recording all the relevant information from the installation and
servicing. The logbook must contain the following:
Content of logbook:
Appendices of Logbook:
General details
Devices used
Date and outcome each inspection
Risk Assessment
Schematic diagrams
Photos of the original Installation
Programming of the control panel
Inspection reports
9.1 Daily Service Schedule
A daily inspection should be performed by the operator prior to operation of the equipment.
If anything does not appear normal, the equipment should not be operated and the fire service
provider alerted. The Daily Inspection should include:
-Visual inspection of the control panel and installed components. These should be accessible

Page | 18
and free from debris, rust, or electrical faults.
-Visual inspection of the control panel to ensure normal functioning. When functioning
normally the only indicator illuminated should be the “Power” indicator (green).
-Visual inspection of anti-tamper seals and travel pins, to ensure they are in place.
9.2 Semi-annual / Annual Service Schedule
Semi-annual and Annual servicing and maintenance are to be undertaken only by
accredited service technicians. Any misuse of the FIP may result in an accidental discharge
of the suppression system and is not covered by warranty.
Servicing should include a visual inspection of all the installed components to ensure they are
in good condition, and that the relevant stream lengths and thermal clearances are observed
as per the original design calculation and risk assessment.
Operation of the fire system should be tested as outlined in 8. Commissioning and Test
Procedure.
10 Troubleshooting
The FP-08451 Control Panel provides a comprehensive fault monitoring system that will detect
any open-circuit in the Circuit 1 Alarm Output, Circuit 2 Alarm Output, Siren/Strobe Output,
Discharge Output and Agent Released Input and any malfunctions of the control panel’s
internal components.
When in a fault condition, the control panel will operate the “Fault” LED indicator and operate
the internal sounder. The control panel uses a coded sequence to indicate the type circuit to
the operator. Note: to diagnose if a fault is internal or external, attempt to isolate the panel.
If the control panel can be isolated, the fault is external. (see 7.2 Isolating the Control Panel)
10.1 Internal Faults
An internal fault cannot be isolated and will display as:
Internal Sounder
Fault LED
Fault
Continuous, steady beep
On
Internal 5vDC Supply OR Watch Dog Circuit
Continuous, pulsing beep
On
Internal Microprocessor
Internal faults can be rectified by powering down the panel and powering up again. This will
reset the system to normal conditions. If the fault persists, contact your supplier.
10.2 External Faults
An external fault can be isolated and will display as:
Internal Sounder
Fault LED
Fault
1 beep
On
Circuit 1 Alarm
2 beeps
On
Circuit 2 Alarm
3 beeps
On
Discharge Circuit OR Siren/Strobe Circuit
External faults will require inspection and testing of connections and installed components.
End-of-line plugs should be plugged directly into the panel, to return it normal condition, and
then used to systematically check along the effected circuit(s). If the fault persists, contact
your supplier.

Page | 19
11 Specifications
General
Dimensions
148L x 84W x 35D mm
Material
Diecast Aluminium, UV Tolerant
Ingress Protection
IP65
Operating Temperature
-40 to 85 degrees Celsius
Fault Monitoring –External
Circuit 1 Alarm –Open/Closed
Circuit 2 Alarm –Open/Closed
Siren/Strobe –Open/Closed
Discharge –Open/Closed
Fault Monitoring –Internal
Poly-switch fuse operated
Loss of internal 5V supply
Internal microprocessor malfunction
Power Supply Input
Mains Operating Voltage
12-30VDC
Mains Operating Current
20mA on 12V
23mA on 24V
Backup Power
See FP-08870 / 08871 / 08872 manual
Detection Output
Circuit 1 Alarm &
Circuit 2 Alarm
No. of Detection Zones
2
Operating Voltage
12-30VDC (same as main supply voltage)
Detection End-of-line
22kΩ Resistor
Maximum Detectors per Zone
30 Conventional Detectors
100m Linear Heat Detection
30 Manual Actuators
Alarm Threshold
3.6V Fault sensing threshold: 0.53V
Compatible Detectors
Hochiki SLV-AS Smoke Detector
Hochiki DCD-AE3M Thermal Detector
14053 Manual Actuator
09510 180˚C Linear Heat Detection
Discharge Output
Discharge Output Current
2A at 12VDC
4A at 24VDC
Discharge End-of-line
3K3Ω Resistor
Maximum FirePro Generators
2 in series at 12VDC
4 in series at 24VDC
Standard Discharge Delay
5 seconds from automatic/manual activation
Siren/Strobe Output
Siren/Strobe Output Current
Max 0.5A
Siren/Strobe Output Protection
0.5A poly-switch resettable fuse
Siren/Strobe End-of-line
1N4004 Diode
Maximum Siren/Strobes
5
Compatible Siren/Strobes
Flashni Xenon Sounder Beacon
Agent Released Input
Input Type
Thermal Switch, NC, Latching, Non-resettable
Operation
Thermal Event >80˚C

Page | 20
12 RFI Environments
The control panel’s circuit arrangement provides a number of layers of electronic protection
designed to minimise the effects of electromagnetic emissions and prevent accidental
discharges of the suppression system.
Shielded, fire rated cable (FP-09500) is required to be used throughout every installation to
protect the fire system from electromagnetic emissions. Cables should be installed with
appropriate clearances from any cables or equipment that may produce high levels of RF
interference.
13 Safety Data Sheet (SDS) - FirePro
This is an EXTRACT ONLY from the full SDS. To view the full SDS go to www.chemwatch.com.au.
PRODUCT NAME CELANOVA FIREPRO
PRODUCT USE Fire extinguishing agent.
HAZARDOUS SUBSTANCE. DANGEROUS GOODS.
According to NOHSC Criteria, and ADG Code.
POISONS SCHEDULE - None
RISK
SAFETY
•Contact with combustible material may cause fire.
•Harmful if swallowed
•Irritating to eyes and skin.
•May cause SENSITISATION by skin contact.
•Harmful to aquatic organisms may cause long- adverse
effects in the aquatic environment.
•Cumulative effects may result following exposure
•May produce discomfort of the respiratory. system*
•Possible respiratory sensitiser*.
•May possibly affect fertility* (limited evidence).
•Keep away from combustible material
•Avoid exposure - obtain special instructions before use.
•To clean the floor and all objects contaminated by this material
use water and detergent.
•Keep away from food drink and animal feeding stuffs.
•In case of contact with eyes rinse with plenty term of water and
contact Doctor or Poisons Information Centre.
•If swallowed IMMEDIATELY contact Doctor or. Poisons
Information Centre (show this container or label).
•This material and its container must be disposed of as hazardous
waste.
FIRST AID MEASURES
SWALLOWED
•If swallowed do NOT induce vomiting.
•If vomiting occurs, lean patient forward or place on left side (head-down position, if possible) to maintain
open airway and prevent aspiration. Observe the patient carefully.
•Never give liquid to a person showing signs of being sleepy or with reduced awareness.
•Give water to rinse out mouth, then provide liquid slowly and as much as casualty can comfortably drink.
•Seek medical advice.
EYE
•If this product comes in contact with the eyes:
•Wash out immediately with fresh running water.
•Ensure complete irrigation of the eye.
•Seek medical attention without delay; if pain persists or recurs seek medical attention.
•Removal of contact lenses after an eye injury should only be undertaken by skilled personnel.
SKIN
•If skin contact occurs:
•Immediately remove all contaminated clothing, including footwear.
•Flush skin and hair with running water (and soap if available).
•Seek medical attention in event of irritation.
INHALED
•If dust is inhaled, remove from contaminated area.
•Encourage patient to blow nose to ensure clear passage of breathing.
•If irritation or discomfort persists, seek medical attention.
Table of contents
Popular Control Panel manuals by other brands

Calira
Calira Check-Panel 210 operating instructions

RHINO
RHINO SMS8 instructions

Autronica
Autronica AutroSafe BS-60 Commissioning Handbook

Simplex
Simplex SafeLINC 4020 Specification sheet

Beckhoff
Beckhoff CP60 Series Installation and operating instructions

G-Force
G-Force UNDER CONTROL CP-34 PILOT user manual

Siemens
Siemens Sinamics G130 Basic Operator Panel 20 operating instructions

mr. steam
mr. steam TEMPO/PLUS owner's manual

mundoclima
mundoclima WDC-120GWK Owners and installation manual

Goldline
Goldline AQL-SPASIDE-RF Installation and operation manual

Spraying Systems
Spraying Systems AutoJet 2850+ owner's manual

Scantronic
Scantronic 808 user guide