XEMEX DINgate TM User manual

USER MANUAL
DINgate TM
Transparent Modem
Copyright ©XEMEX
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by
any means, electronic, mechanical, photocopying, recording or otherwise, without prior written permission of the publisher.

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 2 of 20
DOCUMENT INFO
Version: 1.1
Status: Reviewed
Version date: 26/10/2021
Filename: User Manual - DINgate TM.docx
Author: Luc Olieslagers
Number of pages: 20
HISTORY CHANGES
VERSION
DATE
DESCRIPTION
1.0
01/10/2021
Draft
1.1
13/10/2021
Added configuration

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 3 of 20
TABLE OF CONTENTS
1INTRODUCTION...................................................................................................................................... 5
1.1 Scope .............................................................................................................................................................. 5
1.2 Target group................................................................................................................................................... 5
1.3 Disclaimer....................................................................................................................................................... 5
1.4 Applicable product versions ........................................................................................................................... 5
1.5 Intended usage............................................................................................................................................... 5
1.6 Technical assistance ....................................................................................................................................... 5
1.7 Used symbols.................................................................................................................................................. 5
1.8 Safety precautions.......................................................................................................................................... 6
2TECHNICAL DESCRIPTION................................................................................................................... 7
3TECHNICAL SPECIFICATIONS ............................................................................................................. 8
3.1 Mains power connection................................................................................................................................ 8
3.2 RS485 Interface .............................................................................................................................................. 8
3.2.1 Physical Interface ....................................................................................................................................... 8
3.2.2 Protocol Description................................................................................................................................... 8
3.3 IR Interface ..................................................................................................................................................... 8
3.4 User Interface - LEDs ...................................................................................................................................... 9
3.5 SIM card slot................................................................................................................................................... 9
3.6 LTE antenna connection ................................................................................................................................. 9
3.6.1 DINgate TM 1.0 .......................................................................................................................................... 9
3.6.2 DINgate TM 1.1 .......................................................................................................................................... 9
3.7 Enclosure ........................................................................................................................................................ 9
3.8 Environmental conditions .............................................................................................................................. 9
3.9 Standards........................................................................................................................................................ 9
4INSTALLATION INSTRUCTIONS.........................................................................................................11
4.1 Guidelines for safety and installation........................................................................................................... 11
4.2 Mounting...................................................................................................................................................... 11
4.3 Electrical wiring diagram .............................................................................................................................. 11
4.4 Data connection via RS485........................................................................................................................... 12
4.5 Insert/extract SIM card................................................................................................................................. 12
4.6 LTE Antenna.................................................................................................................................................. 12
4.7 Mains power................................................................................................................................................. 13
5CONFIGURATION .................................................................................................................................14
5.1 Configuration tools....................................................................................................................................... 14
5.2 Gurux GXDLMSDirector - configuration via optical Field Service Interface.................................................. 14
5.3 Gurux GXDLMSDirector - (remote) Configuration via Modem Interface ..................................................... 17
5.4 Basic configuration parameters.................................................................................................................... 18
6OPERATING INSTRUCTIONS..............................................................................................................19
6.1 PWR –POWER Status LED –Red LED ........................................................................................................... 19

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 4 of 20
6.2 WAN –Network Status LED –Green LED ..................................................................................................... 19
6.3 Service button .............................................................................................................................................. 19
7CLEANING.............................................................................................................................................20
8LIFTING AND CARRYING.....................................................................................................................20
9MAINTENANCE AND SERVICE ........................................................................................................... 20

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 5 of 20
1Introduction
1.1 Scope
This manual is applicable to DINgate TM (Transparent Modem), a communication gateway to connect an RS485
device via a wireless communication link.
It describes the specifications, installation and operation of the product. Please read this document carefully before
installation and operating.
1.2 Target group
The installation and the operation of this device and any maintenance must be carried out by a qualified person in
accordance with specific local standards and safety regulations.
1.3 Disclaimer
The information in this document is subject to change without notice and should not be construed as a promise by
Xemex. Xemex assumes no liability for possible errors in this document. In no event shall Xemex be liable for direct,
indirect, special, incidental, or consequential damages of any kind arising out of the use of this document, nor shall
Xemex be liable for incidental or consequential damages arising out of the use of this document, described software
or hardware.
1.4 Applicable product versions
This manual is applicable for following product versions:
Product version
Description
DINgate 1.0 –TM
4G Cat-1 with GPRS fallback communication gateway for ABB B21/B23 E-meters
DINgate 1.1 –TM
4G Cat-M communication gateway for ABB B21/B23 E-meters
1.5 Intended usage
The DINgate TM module is used to access a 2-wire RS485 bus via a remote IP link. Data is forwarded transparently
from the modem to the RS485 interface and vice versa.
1.6 Technical assistance
In case technical assistance is needed, contact Xemex NV:
XEMEX NV
Metropoolstraat 11a
B-2900 Schoten
Belgium
Tel: +32 201 95 95
E-mail: support@xemex.eu
1.7 Used symbols
Following symbols are used in this document and/or are marked on the product:
Alternating current

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 6 of 20
Three-phase alternating current
Equipment protected throughout by DOUBLE INSULATION or REINFORCED
INSULATION
Caution, possibility of electric shock
Caution
1.8 Safety precautions
DANGER —HAZARDOUS VOLTAGES
WARNING - These installation/servicing instructions are for use by qualified personnel only.
To avoid electrical shock, do not perform any servicing other than that contained in the
operating instructions unless you are qualified to do so.
WARNING –Mains protection
WARNING - The DINgate module must always be protected by fuses on the incoming side. To
enable maintenance DINgate module, it is recommended to install a short circuit protection.
Do not operate the equipment other than indicated by the technical data.
Always adhere to the following checklist:
1. Only qualified personnel or licensed electricians should install the Xemex DINgate TM. The mains voltages of
230 Vac can be lethal!
2. Follow all applicable local and national electrical and safety codes.
3. Install the device in an electrical enclosure (panel or junction box) or in a limited access electrical room.
4. Verify that circuit voltages and currents are within the proper range for the DINgate module.
5. Ensure that the DINgate is placed behind fuses or circuit breakers.
6. Equipment must be disconnected from the HAZARDOUS LIVE voltages before access.
7. Before applying power, check that all the wires are securely installed by tugging on each wire.
8. Do not install the DINgate module where it may be exposed to temperatures below –20°C or above 70°C,
excessive moisture, dust, salt spray, or other contamination. The device requires an environment no worse
than pollution degree 2 (normally only non-conductive pollution; occasionally, a temporary conductivity
caused by condensation must be expected).
9. Do not drill mounting holes in the device. Click the module on a DIN Rail instead.
10. If the DINgate device is installed incorrectly, the safety protections may be impaired.

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 7 of 20
2Technical description
The Xemex DINgate TM device is a communication gateway with a 2-wire RS485 interface. An optical interface can
be used for configuration purposes.
It has following interfaces:
•Main power connection 230V
•2-wire RS485 Communication Interface
•Optical Interface (IR)
•User Interface - LEDs
•SIM card slot (for 2FF SIMs)
•LTE antenna connection (SMA)
The DINgate TM gateway module is able to setup a transparent IP link between a server application and an RS485
device connected to the gateway. Data send over LTE is forwarded transparently to the RS485 interface and vice
versa.
The IDNgate TM also incorporates a management application interface that can be accessed locally via the IR port, or
remotely via GSM communication. It can be used to manage settings and perform firmware updates.
LTE antenna connection
RS485 Interface
Mains power
connection 230V
User Interface - LEDs
SIM card slot
Optical Interface

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 8 of 20
3Technical specifications
3.1 Mains power connection
DANGER
Working with high voltages is a potential danger to life. Persons exposed to high voltages can
suffer cardiac arrest, burns or other serious injuries. To avoid such accidents, make sure to
disconnect the power supply before starting the installation.
Nominal Voltage: 230 Vac
Voltage range: 220-240 Vac +/-10%
Frequency: 50 or 60 Hz
I nom: 10 mA
Connector: 2-pole screw terminal connector
Terminal wire: Solid wire / 0.2 –6 mm2
Stranded wire / 0.2 –4 mm2
Max torque: 0.6 Nm
Wire stripping: 7 mm
3.2 RS485 Interface
3.2.1 Physical Interface
Connector: Screw terminal connector for A, B and Shield
Terminal wire: 0.2 -1.5 mm2
Wire stripping length: 5 –6 mm
Max torque: 0.2 Nm
Max cable length: 30 meter
Cable location: indoor
3.2.2 Protocol Description
Protocol: Transparent link –binary data can be forwarded
Baud rate: 115200, 57600, 38400, 19200 ,9600, 4800, 2400, 1200, 300
default value = 9600 baud
Line setting: 8N1, 8E1, 7E1
default value = 8E1
3.3 IR Interface
Optical interface to configure the settings or update the FW of the DINgate TM device via DLMS protocol.
Protocol: DLMS
Baud rate: 9600 baud
Line setting 8E1

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 9 of 20
3.4 User Interface - LEDs
Power / RS485 indicator: Red LED
WAN indicator: Green LED
(See operating instruction 6.1 and 6.2 for functional explanation of the LEDs.)
3.5 SIM card slot
SIM card type: mini SIM (2FF) 25 x 15 mm
SIM Insert / extract: push / push
3.6 LTE antenna connection
The DINgate TM is equipped with an LTE Cat-1 modem with GPRS fallback (DINgate TM 1.0) or an LTE Cat-M modem
(DINgate TM 1.1) functionality.
The supported frequency bands are:
3.6.1 DINgate TM 1.0
-LTE Cat-1: B1, B3, B7, B8, B20
-GPRS: 900/1800 MHz
-Connector type on DINgate: SMA Female
3.6.2 DINgate TM 1.1
-LTE-M: B3 (1800MHz) / B8 (900MHz) / B20 (800MHz)
-Connector type on DINgate: SMA Female
3.7 Enclosure
DIN rail mount: DIN 43880 / 2 units
Dimensions: 90 x 36 x 65 mm
Weight: 106 gr
Material: PA66-FR
3.8 Environmental conditions
Protection class II
Operating temperature -20 °C - +70 °C
Storage temperature -40 °C - +70 °C
Relative humidity < 75 % year’s average at 21 °C
< 95 % less than 30 days/year, at 25 °C
Pollution Degree 2
Altitude < 2000m
Application area Residential, Indoors in suitable meter cabinet
3.9 Standards
Safety: IEC 60950-1
Radiated emission: EN 55016-3-2
Conducted emission: EN 55016-2-1
Harmonic current emission: EN 61000-3-2
Voltage changes, fluctuations & flicker: EN 61000-3-3
Electrostatic discharge: EN 61000-4-2
RF immunity: EN 61000-4-3
Electrical fast transient: EN 61000-4-4

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 10 of 20
Surges: EN 61000-4-5
RF common mode: EN 61000-4-6
Voltage dips: EN 61000-4-11

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 11 of 20
4Installation instructions
4.1 Guidelines for safety and installation
This installation guide must be consulted in all cases when manipulating parts which are marked
with the Caution symbol.
The installation and the operation of this device and any maintenance must be carried out by a
qualified person in accordance with specific local standards and safety regulations.
Caution: never open the secondary circuit of a Current Transformer while current is flowing
through the primary circuit!
If the secondary circuit is opened when primary current is flowing, then the voltage will go to a very
high value, possibly causing electrical arcing and/or electrical shock to service personnel. Therefore
CT’s with internal TVS must be used.
Failing to obey the ”Guidelines for safety and installation”, the guarantee no longer applies.
4.2 Mounting
Mount the device in a DIN rail cabinet.
4.3 Electrical wiring diagram
WARNING
The DINgate TM module power connection always needs to be protected with a circuit
breaker.

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 12 of 20
4.4 Data connection via RS485
4.5 Insert/extract SIM card
The DINgate TM has as slot on the front to insert a SIM card:
-Formfactor: mini SIM or 2FF
-To insert: push the SIM, with the contact area on the right side, in the slot until it clicks.
-To extract: push the SIM a bit further in the housing until it clicks and then release it to let it spring back.
4.6 LTE Antenna
The antenna used to connect to the DINgate TM needs to have an SMA male connector.
The supported bands need to correspond with the bands provided by the SIM operator within the available LTE and
GPRS bands. (see 3.6)
B (-)
A (+)
Shield

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 13 of 20
4.7 Mains power
DANGER
Working with high voltages is a potential danger to life. Persons exposed to high voltages can suffer
cardiac arrest, burns or other serious injuries. To avoid such accidents, make sure to disconnect the
power supply before starting the installation.
WARNING
The DINgate TM module power connection always needs to be protected with a circuit breaker.
N
L

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 14 of 20
5Configuration
By default the DINgate TM modules are preconfigured in production.
Some configuration settings can be changed via the DLMS protocol using specific tooling (remote or local via optical
interface). The configuration is described in document “Xemex product configuration via Gurux.docx” and out of
scope for this document.
5.1 Configuration tools
•HW –Optical Reader (IEC1107) 1U DIN rail module
•Config via optical interface
•For Initial or field service config
•SW –DLMS Client Application
•Communication channels
•IEC/HDLC/Serial (for config via optical channel)
•DLMS Wrapper/TCP/IP (for config via the modem channel)
•E.g. GXDLMSDirector
http://www.gurux.fi/Download
5.2 Gurux GXDLMSDirector - configuration via optical Field Service Interface
Step 1: Add DINgate device
•Open GXDLMSDirector
•Right click “Devices”
•Select “Add Device” from the popup menu
•Fill out the Device Properties for the DINgate connection via Optical Interface and click ”OK”.
Module dependent settings:
•Fill in the correct LLS password
•Select the Serial Port to which your Optical Reader is connected
•Select the COM-port of the optical reader

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 15 of 20
Configure serial port
•Press Advanced button
•Fill in settings below
oBaudrate 9600
o8 Data bits, no parity & 1 Stop bit
•Click “OK”

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 16 of 20
Step 2: Read out settings
•Expand the “Devices” list (click on + in front of “Devices”)
•First, right click “Transparent Modem via Optical Interface” in the Devices list and select “Connect”
•Next, right click “Transparent Modem via Optical Interface” in the Devices list and select “Read”
•Next, expand the “Transparent Modem via Optical Interface” device to show its DLMS objects:
Step 3: Adjust settings
•Select the object to configure
•First, click on “+” in front of the object Class (e.g. Data) to show all objects of this Class.
•Next, click on the object (e.g. 0.0.129.0.0.255 Manufacturer specific).
•In the right pane, edit the object attributes values accordingly your settings.
•Click on the right arrow in the toolbar to send the updated attribute values to the Transparent Modem.

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 17 of 20
5.3 Gurux GXDLMSDirector - (remote) Configuration via Modem Interface
Step 1: Add Transparent Modem device
•Open GXDLMSDirector
•Right click “Devices”
•Select “Add Device” from the popup menu
•Fill out the Device Properties for the Transparent Modem Optical Interface and
click ”OK”. Select the IP address of your Transparent Modem Module:
Module dependent settings:
•Fill in the correct LLS password
•Select the IP address of the DINgate module to connect
Step 2: See 5.2 Step 2
Step 3: See 5.2 Step 3

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 18 of 20
5.4 Basic configuration parameters

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 19 of 20
6Operating instructions
The DINgate TM module can setup a remote IP link to a connected RS485 device.
The IR supports the industry-standard protocol DLMS-COSEM for configuration purposes. This protocol implements
the SMR5 application layer.
The DINgate module gives visual feedback on its working state by its 2 Status LED Indicators:
6.1 PWR –POWER Status LED –Red LED
•Not lit: DINgate module is not powered
•Blinking: DINgate module is powered, but not (yet) able to readout the connected RS485 device
•Lit: DINgate module is powered, and has readout the connected RS485 device
6.2 WAN –Network Status LED –Green LED
•Not lit: The DINgate module is not connected to a radio network.
This may have one of the following causes
-No or wrong SIM card (disabled)
-No network coverage
-Modem is defect
•Blinking: The DINgate module is registered to the radio network
No end to end data session with the head-end system can be established.
•Lit: The DINgate module is registered to the radio network and a PDP context was established.
This means the module got an IP address from the network and the head-end system is
able to establish a data connection with the module.
The nominal state of the network status LED is ‘LED Lit’
This means the module can always be reached on its IP address by the head-end system.
6.3 Service button
For future use.

User Manual - DINgate TM
26 October 2021 XEMEX Confidential Page 20 of 20
7Cleaning
Clean the unit with a slightly damp cloth and mild detergent.
8Lifting and carrying
Use care when lifting and carrying the product.
9Maintenance and Service
There are no serviceable parts inside.
End Of Document.
Table of contents
Popular Modem manuals by other brands

Patton electronics
Patton electronics 2192 user manual

Funk-Electronic Piciorgros
Funk-Electronic Piciorgros TMO-100 Setup and configuration guide

chinavasion
chinavasion CVSB-028 user manual

Efficient Networks
Efficient Networks SpeedStream 5260 quick start guide

ALZA
ALZA Cudy WU1300S user manual

Aduance
Aduance i-tec user guide

i-mate
i-mate JASJAR Guidelines for use

ZyXEL Communications
ZyXEL Communications P-2612HW-F1 - user guide

Novatel
Novatel Merlin for GPRS G201 user manual

Vega
Vega VEGACOM 557 operating instructions

Allied Data Technologies
Allied Data Technologies Tornado FMV 56.0 Quick installation guide

APLIC
APLIC 304747 user manual