SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 1
ENGLISH
1.- INTRODUCTION
SNMP06 is a powerful and versatile communication LAN card for XMART online UPS. This card
includes functions as:
- Communication for LAN Ethernet under protocols TCP/IP, UDP, SNMP, SMTP, SNTP, HTTP, HTTPS,
SSL, SSH, IPV4/IPV6, DHCP, etc.
- Connection to external XMART environmental sensor to acquire and send temperature/humidity data
to the network.
- 10M/100M autodetection speed
- Internal data logging up to 200.000 events/alarms
- Interface to monitor and control main parameters of the UPS
2.- DESCRIPTION
A: LAN Ethernet (10/100MB)
B: Sensor T/H
C: Reset Jumper: To reestablish default values
1-2: Normal
2-3: Reset: Revise note 1
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 2
D: LED green = ON: 100MB / OFF: 10MB
E: LED yellow = ON: connection detected / OFF: connection not detected
NOTE 1: RESET: Reset function reinitializes card with factory values. It also eliminates user passwords
To apply a reset follow next procedure:
1) Remove card from UPS and set jumper between pins 2 & 3 (revise previous image)
2) Insert card into the UPS and wait during 5 minutes meanwhile reset is performed.
3) Remove card from UPS again and set jumper between pins 1 & 2.
4) Reinsert card into the UPS and wait during 5 minutes meanwhile card restarts with factory
setting.
Factory setting after reset:
IP: 192.168.102.230 (STATIC IP) ;
Subnet Mask: 255.255.255.0 ; Default gateway: 192.168.102.1
Password: 12345678
3.- INSTALATION
1: Remove cover from intelligent slot in the UPS
2: Check jumper “C” is between pins 1 & 2 in the card
3: Plug RJ45 cable in the Ethernet port of the card and connect other side to the network socket.
Check if yellow LED lights as expected.
If TH sensor is available, connect it to its related RJ11 port in the card according to next figure.
We strongly suggest to check TH sensor manual.
LAN
SENSOR TH
RJ11
RJ45
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 3
4.- COMMUNICATION
There are 2 paths to communicate with SNMP06 cards:
- Using XMART UPS monitoring software (Viewpower Pro)
- Directly by typing IP address of card in an internet navigator (Explorer, Firefox, Chrome, etc)
A) MONITORING SOFTWARE VIEWPOWER PRO
Monitoring software offers all kind of control and monitoring functionality for all UPS in the network.
Software communicates any PC with any of the UPS in the network. It also provides functions to power
off/on UPS in real time. Shutdown Wizard installed in PC allows controlled shutdown of the PC when an
event is detected by the software. Software also provides logging capabilities for data, events and
alarms.
User can install monitoring software from CD included inside the box of SNMP06 card or download it
from www.xmart-ups.com. For more information download and revise user manual for Viewpower PRO
software.
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 4
B) COMMUNICATION FROM INTERNET NAVIGATOR
User can monitor and control any UPS in the network from any PC installed in same network by
contacting SNMP06 card from internet explorer. User only needs to introduce IP address of the
SNMP06 card to open “Web Pro” interface in the navigator.
This LAN card can storage data and events in its internal memory with any external software. SNMP06
card can also send messages and alarms by email if there is a router in the network with open access
to internet.
If network where card is installed is DHCP, card will receive dynamic IP address from the network. If
network use static IP, network administrator must assign IP for the card. We suggest to revise related
section in this manual.
FIG 2: WEB PRO INTERFACE FROM NAVIGATOR
This operator interface is divided in different areas:
1) ADDRESS BAR: Where card IP address must be introduced
2) LOGGIN: To login as administrator introduce password: 12345678
3) FUNCTIONS MENU
1
2
3
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 5
DHCP NETWORKS
To know what IP has been assigned to the card by DHCP network, user can run SNMP Manager
software to perform scan. SNMP manager is available as separate software in the CD or it can be run
from Viewpower Pro software (as indicated in software manual).
Install and execute SNMP MANAGER to open interface window as described in the figure:
We suggest to login as administrator in the System section with password: 12345678
FIG 3: SNMP WEB MANAGER:
Press SCAN to show all cards with dynamic IP available in the network. This process could take some
minutes. Sometimes this SCAN process must be performed several times, until detecting cards.
Take note of the IP for the card and write it in the address bar in the navigator. You can also simply
double click over IP address listed in the SNMP Manager window. System will open navigator will Web
Pro interface.
SCAN
IP address
Introduce password: 12345678
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 6
STATIC IP NETWORKS
If the network where UPS will be connected is static IP network, the network administrator must assign
an IP to the UPS LAN card. This can be done by following procedure:
1.- UPS with SNMP card must be ON
2.- One PC with SNMP MANAGER or Viewpower Pro must be connected to the SNMP card directly
by a RJ45 cable. There are new SNMP cards that can be detected though the network. For those
cards PC can be connected to the network and try to make contact with the SNMP card.
3.- SNMP MANAGER must detect card automatically. If not, a manual SCAN must be done. This
scan process could take about 2 to 5 minutes. Do some scans if necessary.
4.- Select the IP shown in the left area of the SNMP Manager screen.
5.- Open IP SETTINGS tab and select option: “Use a Static Address”.
NOTE: If system does not allow modifications, do SCAN again and repeat previous steps.
6.- Introduce manually static IP address, Subnet mask y Default Gateway.
7.- Select APPLY command key to save modifications.
System could require you a password. In that case introduce password: 12345678.Then do
APPLY again to save modifications. System must show a message:
“OPERATION SUCCESSFULL”
FIG 4: SNMP WEB MANAGER:
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 7
WEB-PRO INTERFACE
INFORMATION:
- STATUS:
This section offers information about the UPS like:
- Operation mode and main parameters
- Input values: Voltage and Frequency
- Output values: Voltage, Frequency, Current, Load connected to UPS, etc.
- Battery information
- Temperature and Humidity (only if external TH sensor is connected to the SNMP card)
- BASIC INFORMATION: It provides information about UPS technology, rated voltage, quantity of
batteries and the kind of SNMP card connected to UPS.
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 8
UPS SETTING: Parameters Settings: In this section main UPS parameters can be revised and
modified: Alarm Beep, Operation modes, etc.
CONTROL: Real Time Control: Allows real time control: UPS can be turned-off and turned-on, alarm
mute, battery tests, etc.
SYSTEM CONFIGURATION: In this area important functions can be configured. For example:
- User name and password
- Emails sending
- SMS sending (it requires external GSM connected to port B of the card) (Check figure below).
- Wake on LAN: PC prepared with this function can be waked from UPS.
- Shutdown: SNMP card, based on some events, can send commands to shutdown PC in the network.
PC to be shutdown require to have Shutdown Wizard software installed. Revise Viewpower Pro manual.
- Event Action: When AC failure is detected, SNMP card can send shutdown command to PC on the
network. Main parameters can be configured in this section.
- Scheduled: Some actions can be configured to be performed at scheduled date and time.
- System Time: To configure date and time.
- SNMP Configuration: To configure LAN parameters for the SNMP card.
LOG: Event and data logs can be revised in this section
HELP: Serial Port Debugging: Only for service purposes. Allows to check communication between card
and external device.
GSM PIN-OUT
* Cable not included. (PIN 2 to 4 / PIN 3 to 3 / PIN 5 to 1)
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 9
5- EMAILS CONFIGURATION
This card can send emails using accounts based on SNMP, SSL or TTL servers. Check SYSTEM
CONFIGURATION / E-mail to check parameters to be configured like: email server name, email account
name & password, receivers, etc.
EMAIL SENDER:
SMTP server: Describes email server to be used to send emails. For example:
“smtp.xxxxxxxxxxx.com”.
Security Type: We must select kind of email server to be used:
NONE: Usually for web-domain email servers.
SSL: For servers with security SSL like Gmail, Yahoo, etc
TLS: Para servidores de emails con seguridad TLS like Hotmail.
Port: Usually 25 (for SMTP servers)
Usually 465 (for servers SSL)
Usually 587 (for servers TLS)
Check with your email provider
Send from: Configure name of the email account to be used to send emails. For
example: [email protected]
User name: Configure user name of the email account to be used to send emails.
Usually same tan email account name.
Need Authorization: Check this option for accounts that require Authorization (“Need Auth”)
Password: Email account password.
APPLY It is necessary to select APPLY to save modifications.
EMAIL RECEIVERS:
In these fields you can configure up to 8 receivers. Do APPLY for each receiver added.
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 10
Once email section has been configured we suggest to do a TEST by selection TEST button.
System will response with a message: “TEST SUCCESSFULL” when email has been sent without
errors. In case email cannot be sent because an error in any of the configured above fields, system will
show a failure message.
IMPORTANT: If card informs problems to send emails it can be caused by 2 reasons:
1.- A mistake in any of the data fields
2.- DNS has not been saved automatically in the card.
ACTIONS:
a) Check SYSTEM CONFIGURATION / SNMP Configuration / network settings
b) Revise if DNS fields shows appropriate DNS. If it shows 0.0.0.0, user must introduce
manually DNS of the network and do APPLY.
Test Successfull
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 11
To know DNS of your network, you can run from system command line of your PC, the command:
ipconfig -all
Your operating system will list several parameters related. Look for the line dedicated to DNS server. In
the below example the value is: 192.168.1.1 (FIG. 5)
c) Go back to “WEB PRO” card interface to mark option: “Use a static IP address”. Introduce
DNS value and APPLY. Wait for some seconds
d) Mark again option: “Automatically obtain IP address” (for DHCP networks) and APPLY. Wait
some seconds during card restarts to recover communication.
Go back to E-mail section and do test again,
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 12
FIG 5: IPCONFIG -ALL
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 13
6- HTTPS SECURE COMMUNICATION & HTTP PORT (80)
This card allows both http and https communication protocol.
Factory set is http. To operate only under https protocol, user requires to disable http port 80. If not
card will be able to communicate under any of these 2 protocols.
To disable port 80 go to menu SYSTEM CONFIGURATION / WEB
Make sure you have already logged in as administrator by introducing password: “12345678”
FIG 6
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 14
HTTP PORT (80)
1- Select System Configuration / Web menu, FIG 7.
2- Select option LOGIN and password: 12345678. If you do not enter as administrator, modifications
will be NOT saved.
3- Uncheck option Http Port and APPLY to disable port 80. Only if port 80 is disable, card will be
forced to communicate under HTTPS protocol.
NOTE: If APPLY is not selected, changes will not be saved. A message OPERATION SUCCESSFUL must
be shown. Select Accept button.
FIG 7
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 15
4- Wait about 30s to save changes and try to update navigator with F5 key (in Windows). Navigator
must response with a message indicating communication is lost. This is caused by port 80 is disable
and HTTP communication is prohibited.
5- At this moment you can check if HTTPS protocol is active by introducing in the navigator bar
address, the IP of the card preceded by https://
For example: https://192.168.1.18
6- Navigator will open WEB PRO interface under HTTPS according to figure 8
FIG 8

Popular Computer Hardware manuals by other brands

DAQ system PCIe-FRM16 user manual

DAQ system

DAQ system PCIe-FRM16 user manual

Digitus DS-33172 manual

Digitus

Digitus DS-33172 manual

DeLOCK 90300 user manual

DeLOCK

DeLOCK 90300 user manual

Infinion TLD5098EP user manual

Infinion

Infinion TLD5098EP user manual

Ikegami IK-8046 Installation & operating manual

Ikegami

Ikegami IK-8046 Installation & operating manual

National Semiconductor LM4681 user guide

National Semiconductor

National Semiconductor LM4681 user guide

Avnet Zynq-7000 AP SoC Getting started guide

Avnet

Avnet Zynq-7000 AP SoC Getting started guide

YASKAWA VS-616 Series Option instruction manual

YASKAWA

YASKAWA VS-616 Series Option instruction manual

Azoteq IQS7211AEV02A user guide

Azoteq

Azoteq IQS7211AEV02A user guide

Sharp AN-WC11B Operation manual

Sharp

Sharp AN-WC11B Operation manual

Yamaha DMP9-16 owner's manual

Yamaha

Yamaha DMP9-16 owner's manual

Kontron AM4024 user guide

Kontron

Kontron AM4024 user guide

National Instruments AT-GPIB/TNT Getting started

National Instruments

National Instruments AT-GPIB/TNT Getting started

ekwb EK-UNI RAD INSTALLATION AND MOUNTING MANUAL

ekwb

ekwb EK-UNI RAD INSTALLATION AND MOUNTING MANUAL

SIIG CyberParallel Dual Quick installation guide

SIIG

SIIG CyberParallel Dual Quick installation guide

ST FP-ATR-BLE1 quick start guide

ST

ST FP-ATR-BLE1 quick start guide

Sony MVS-8000A-C installation manual

Sony

Sony MVS-8000A-C installation manual

US Robotics MAXg user guide

US Robotics

US Robotics MAXg user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.