Xtralis VPS-215-E Installation and operation manual

Xtralis Power Supplies VPS-215-E & VPS-220-E Installation and Commissioning Instructions
www.xtralis.com Approved Document No. DFU0002150 Rev 3 www.xtralis.com Page 1 of 2
VPS-215-E & VPS-220-E are power supply units (PSU) for Xtralis Aspirating Smoke Detectors (ASD).
They are compliant with EN54-4:1997+A1:2002+A2:2006.
Xtralis VPS-215-E
(0.5A load, 7Ah max)
and
Xtralis VPS-220-E
(0.5A load, 14Ah max)
1
Location: Site the PSU indoors on a dry, flat surface in an area that is well ventilated. Where possible the panel’s indicators (internal and
external) should be at eye level and the unit should be installed in the same location as the ASD it powers.
2
Knockouts: Before mounting, remove selected knockouts with a sharp light tap, using a flat broadsided screwdriver (shown right). Fill knockout
holes with good quality cable glands.
3
Mounting: Mount the metal base securely onto a wall using the four mounting holes provided. Assess the condition and construction of the wall
and use No.8-10, or 4-5mm screws. Use the fixing hole template overleaf as a guide.
4
Wiring: Connect all AC cables BEFORE applying power. Maintain segregation between AC and DC cabling. All wiring should be installed in
accordance with relevant national standards, e.g. IEE Wiring Regulations BS7671 in the UK. Connect the incoming AC to CONN1 (②shown
overleaf)and ensure that earth straps are connected to the earth tag (shown right).
5
Connect DC: Connect the DC output to the Xtralis detector. Examples for the VESDA VLC, VLP and VLF are shown below which may use the General Purpose Input (GPI) to transmit the PSU
fault signal. The VESDA detector must be configured to interpret the GPI input as a ‘Mains OK’ if this feature is used.
6
Connect Batteries: Secure the batteries using battery straps and connect as shown. With charged batteries the DC output ⑧will turn on, the OK LED will illuminate and the Fault LED will also
illuminate (as there is no AC input).
CAUTION: Only use good quality sealed Valve Regulated Lead Acid (VRLA) batteries. There is a risk of explosion if the batteries are replaced by incorrect types.
7
Commissioning: Switch on the AC supply to the PSU. The OK LED should stay lit and the Fault LED should turn off.
Check the fault relay is energized (short circuit between C and NO terminals ⑪). Switch off the AC supply and confirm correct
operation of LEDs and relay –see table right. Restore the AC supply. Disconnect the batteries and confirm correct operation of
LEDs and relay –see table right.
8
Normal Operation/Fault Finding: The table in Step 7 provides a summary of the normal operation of the PSU when the battery and/or AC supply fails. When the AC supply fails, the DC output
is maintained for at least 24 hours as long as the batteries are in good condition. Damage to the batteries as a result of deep discharge is prevented by turning the DC output off (load shed mode)
when the battery voltage falls below approximately 21V. Should this happen the DC output will not be restored until the AC supply is re-established OR fully charged batteries have been installed.
However, the terminal voltage of the discharged batteries measured after the PSU has entered load shed mode may be greater than 21V because the voltage can recover when the battery is not
under load. Never leave the batteries connected for prolonged periods without an AC supply connected because, during load shed mode, there is a monitoring current Imin (<12mA) which, over
several days, will drain the batteries to the point they are damaged.
AC
Batteries
OK
LED
Fault
LED
Fault
relay
Fault terminals
ON
OK (Healthy)
ON
OFF
ON
NO-C=short
OFF
ON
ON
OFF
NC-C=short
ON
Not OK
(Discharged or
Disconnected
or Faulty)
ON
ON
OFF
NC-C=short
OFF
OFF
OFF
OFF
NC-C=short

Xtralis Power Supplies VPS-215-E & VPS-220-E Installation and Commissioning Instructions
www.xtralis.com Approved Document No. DFU0002150 Rev 3 www.xtralis.com Page 2 of 2
Legend
Description (UK)
Description (FR)
Beschreibung (DE)
Descriptiόn (ES)
Descrizione (IT)
Value
①
AC supply
230Vac, 50/60Hz (tested +10% / -15%)
②
AC supply input terminals
L=LIVE, N=Neutral, =Earth
③
PSU earth strap: connect to enclosure
earth tag
PSU is CLASS 1 AND MUST BE EARTHED
④
AC supply fuse (F1): high rupturing
capacity, ceramic
1A HRC, 20mm
⑤
Red LED: Hazardous voltages in PCB
hashed area
Hazardous voltages =
⑥
PLK1 Charge current link. Remove if
using batteries <7Ah (Minimum 2Ah)
PLK2 Battery monitoring link. Fit if
batteries NOT used
⑦
Power output (maximum and battery cut
off voltage)
24Vdc (V max = 30V, V min = 19.5V)
I max a & I max b with PLK1 fitted
0.5A
I max a & I max b with PLK1 NOT fitted
1A (non EN54-4 certified)
Output ripple voltage (peak-to-peak)
1.2V@30MHz bandwidth, 600mV 100nF loading
⑧
Battery connection to VRLA batteries
Maximum internal battery resistance
Ri max = 1500mΩ
I min: Monitoring current in load shed
<12mA
AC supply/battery charger monitored
Batteries monitored
Charging is temperature compensated
VPS-215-E battery size (Yuasa NP type
or equivalent)
2 x 12V, 7Ah (NP7-12)
VPS-220-E battery size (Yuasa NP type
or equivalent)
2 x 12V, 7Ah (NP7-12) or
2 x 12V, 12Ah (NP12-12) or
4 x 12V, 7Ah (NP7-12)
⑨
VPS-215-E indications: Internal only.
Output OK (Green LED), Fault(Yellow LED)
Output OK = Fault =
VPS-220-E indications: External only.
Output OK (Green LED), Fault(Yellow LED)
Output OK = Fault =
⑩
PL1: 4-way display connector
⑪
Fault relay: isolated relay output
Change-over NO-COM-NC 1A@50V
⑫
PL2: high temperature output (unused)
Operates at approx 55oC internal box temp, 30V
200mA max current sink.
⑬
Battery fuse (F2): fast, glass
3.15A F, 20mm
⑭
Charge Off Input: Disablement of battery
charger when closed (unused)
⑮
Wiring loom to Display PCB (VPS-220-E
only)
VPS-215-E dimensions (H x W x D)
VPS-215-E weight (without batteries)
286 x 226 x 113mm
2.5kg
VPS-220-E dimensions (H x W x D)
VPS-220-E weight (without batteries)
351 x 255 x 110mm
3kg
VPS-215-E mounting
4 x Ø5mm holes on 220 x 180mm centres
VPS-220-E mounting
4 x Ø5mm holes on 270 x 180mm centres
Temperature range
Maximum relative humidity (RH)
Ingress protection (IP) Rating
-5oC to +40oC ambient
95% RH
IP30
This manual suits for next models
1
Other Xtralis Power Supply manuals
Popular Power Supply manuals by other brands

Integrated Power Designs
Integrated Power Designs REL-185 Series operating instructions

Wheelock
Wheelock POWERPATH series PS-12-24-8CP installation instructions

Horizont Agrar
Horizont Agrar farmer A1000 solar Operating instruction

Joy-it
Joy-it DPS5015 manual

Bticino
Bticino 346050 quick start guide

Siemens
Siemens SITOP 6EP1336-3BA00 manual