User’s
Manual
Model UPM100, UPM101
Universal Power Monitor
< Measured Value Display Operations >
This manual describes the measured value display procedures and measuring ranges
for the UPM100 and UPM101 which have display function.
1. Action Flow on Measured Value Display ------------- P. 1
2. Measured Value Display ----------------------------- P.1-P.2
3. Measured Value Resetting Procedures --------------- P.2
4. Troubleshooting --------------------------------------------- P.2
1. Action Flow on Measured Value Display
Display Key Operation Description
Display after Power-on
Active Energy
LAG Reactive Energy
LEAD Reactive Energy
Apparent Energy
Optional Electric Energy
Instantaneous Active Power
Instantaneous Reactive Power
Instantaneous Apparent Power
Instantaneous Voltage
Instantaneous Current
Instantaneous Power Factor
Frequency
LEAD
display
Minimum value
Maximum value
Maximum value
LAG
display
Without power factor option
Return to
beginning
After the UPM100 is turned on, the address
(station number) (initial setting:01) is
displayed for about 5 seconds and then the
measured value display is displayed.
This symbol means the optional measuring function. The parameter with this
symbol indicated will not be measured and displayed for the UPM100 without the
optional measuring function.
Option
Without reactive power option
Without reactive power option
To go to the parameter setting display, hold the <SET/ENT> key down for about 3 seconds.
Regenerative Energy
The active energy is displayed.
For details, see “2. Measured Value Display.”
The regenerative energy is displayed.
For details, see “2. Measured Value Display.”
The LAG reactive energy is displayed.
For details, see “2. Measured Value Display.”
The LEAD reactive energy is displayed.
For details, see “2. Measured Value Display.”
The apparent energy is displayed.
For details, see “2. Measured Value Display.”
The active energy during any given time
period is displayed.
For details, see “2. Measured Value Display.”
The instantaneous active power or
instantaneous regenerative power is displayed.
For details, see “2. Measured Value Display.”
A minus sign (-) is always displayed for
regenerative power measurement.
The instantaneous reactive power is
displayed.
For details, see “2. Measured Value Display.”
The instantaneous apparent power is
displayed.
For details, see “2. Measured Value Display.”
The instantaneous voltage is displayed.
For details, see “2. Measured Value Display.”
The instantaneous current is displayed.
For details, see “2. Measured Value Display.”
The instantaneous power factor is displayed.
LEAD is displayed as the numerical value
after “d”, and LAG is displayed after “G”.
For details, see “2. Measured Value Display.”
The frequency is displayed.
For details, see “2. Measured Value Display.”
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The next measured
value is displayed.
Press
once.
The active energy is
dispayed.
Press
2. Measured Value Display
This chapter describes display procedures, display ranges and other information for UPM100
with display function. For UPM100 without display function, see the communication function
User's Manual (IM 77C01H01-10E).
2.1 Active Energy, Apparent Energy and Regenerative Energy
The active energy and regenerative energy up to the present moment is indicated in “kWh” or
“MWh” unit (it is output in kWh unit during communication). The apparent energy is indicated
in “kVAh” or “MVAh” unit (it is output in “kVAh” unit during communication). However, if the
instantaneous active power or instantaneous apparent power is less than the previously
determined “integral low-cut power,” then it is not integrated. Active energy, apparent energy
and regenerative energy is recorded even during a power interruption.
Individual electric energy is displayed as shown in the table below, in accordance with the
measurement conditions.
For apparent energy, the unit is “VA” instead of “W.” For regenerative energy, a minus sign (-)
is always displayed. When “Integral resolution Wh” is specied at ordering, Type (3) in the table
is applied without the condition of “Secondary-side rated power x VT ratio x CT ratio” and the
display unit is “kWh” or “kVAh” only.
For Types (2) and (3), you can press the <Down> key to display as many as three digits
following the decimal point. (See the example display operations.)
Type
Secondary-side Rated Power x VT ratio x CT ratio
Integral Display Range Remarks
(1) Less than 1 MW 0 to 999999 kWh *1 Six digits, without decimal point
(2) 1 MW or greater, but less than 10 MW 0.00 to 9999.99 MWh *1 Six digits, with decimal point
(3) 10 MW or greater 0.0 to 99999.9 MWh *1*2 Six digits, with decimal point
*1: The unit is “kVAh” or “MVAh” for apparent energy. A minus sign (-) is displayed for regenerative energy.
*2: The unit is “kWh” or “kVAh” for “Integral resolution Wh,” and “MWh” or “MVAh” for ”Integral resolution kWh.”
<Down> key<Move> key
<Up> key<SET/ENT> key
Measured value display
Communication light
Power light
COS Ø light
RST light Integrated pulse light
Unit light
IMPORTANT
Pressing this switch resets all
measured values other than
active energy, apparent
energy, regenerative energy
and reactive energy.
<Example of Display Operation>
• Decimal point cannot be moved through
key operations
• Display unit: kWh or kVAh
The numbers in the rectangular box left
are the measured value to be displayed.
Press the <Down> key once to display
three digits after the decimal point.
Press the <Down> key once again to
return to the initial measured value
display.
• Display unit: MWh or MVAh
The numbers in the rectangular box left
are the measured value to be displayed.
Press the <Down> key once to display
two digits after the decimal point.
Press it again to display three digits after
the decimal point.
With three digits after the decimal point
displayed, press the <Down> key to
return to the initial measured value
display.
• Display unit: MWh (kWh or kVAh when
“Integral resolution Wh” is specified.
Type Measured Value Display Key Operation Description
(1)
(2)
(3)
once.
Press
Press
Press
Press
Press
once.
once.
once.
once.
• Electric energy (active power, regenerative power, reactive power and apparent power) are set to “0” as
shown below if they exceed the maximum integral value.
Maximum
integrated value
Electric
energy
Time
0
(Active power)0
Electric
energy
(Regenerative power) Time
Maximum
2.2 Reactive Energy (Optional Measuring Function)
The reactive energy up to the present moment is indicated in “kvarh” or “Mvarh” unit (it is output
in “kvarh” unit during communication). LAG (+) and LEAD (–) are separately integrated and
displayed. (A plus sign (+) is not displayed for LAG (+).) However, if the instantaneous reactive
power is less than the previously determined “integral low-cut power,” then it is not integrated.
Reactive energy is recorded even during a power interruption.
Reactive energy is displayed as shown in the table below, in accordance with the measurement conditions.
When “Integral resolution Wh” is specied at ordering, Type (3) in the table is applied without
the condition of “Secondary-side rated power x VT ratio x CT ratio.”
For Types (2) and (3), you can press the <Down> key to display as many as three digits
following the decimal point. (Display operations can be performed in the same manner as in the
example display operations in “2.1 Active Energy, Apparent Energy and Regenerative Energy.”
Type
Secondary-side Rated Power x VT ratio x CT ratio
Integral Display Range Remarks
(1) Less than ±1 Mvar ±0 to ±99999 kvarh Five digits, without decimal point
(2) ±1 Mvar or greater, but less than ±10 Mvar ±0.00 to ±999.99 Mvarh Five digits, with decimal point
(3) ±10 Mvar or greater ±0.0 to ±9999.9 Mvarh Five digits, with decimal point
2.3 Optional Electric Energy
While optional integration is running, the active energy is displayed (and output through
communication) in “Wh” unit. However, if the instantaneous active power is less than the
previously determined “integral low-cut power,” then it is not integrated.
Optional integration is started/stopped through RS-485 communication. (Optional integration
start [D0062]/optional integration stop [D0063]) Please see the communication user's manual
(IM 77C01H01-10E).
- Integration is not performed while optional integration is stopped. Instead, the immediately
preceding optional electric energy is displayed.
-
When optional integration is reactivated, the optional electric energy is reset and integration starts.
• Maximum integration display: 999999 Wh
2. Instantaneous Active/Regenerative Power, Instantaneous Apparent
Power and Instantaneous Reactive Power
• Instantaneous active/regenerative power is an active/regenerative power at a given point
of time displayed in “W”, “kW”, or “MW” unit, with a minus sign (-) if it is a negative value.
(It is output in “W” unit during communication.) (A minus sign (-) is always displayed for
regenerative power measurement.)
• Instantaneous apparent power is an apparent power at a given point of time displayed in
“VA”, “kVA”, or “MVA” unit, with a minus sign (-) if it is a negative value. (It is output in “VA”
unit during communication.)
• Instantaneous reactive power is a reactive power at a given point of time displayed in “var”,
“kvar”, or “Mvar” unit, with a minus sign (-) if it is a negative value. (It is output in “var” unit
during communication.)
The table below shows the measured value display ranges for instantaneous active power.
The same ranges apply for instantaneous apparent power and instantaneous reactive power,
except the unit is “VA” instead of “W” for instantaneous apparent power, and “var” instead of
“W” for instantaneous reactive power.
Secondary-side Rated Power × 1.2 × VT Ratio × CT Ratio
Measuring Range Remarks
6 W or greater, but less than 100 W 0.00 to 99.99 W
100 W or greater, but less than 1 kW 0.0 to 999.9 W
1 kW or greater, but less than 10 kW 0 to 9999 W
10 kW or greater, but less than 100 kW 0.00 to 99.99 kW
100 kW or greater, but less than 1 MW 0.0 to 999.9 kW
1 MW or greater, but less than 10 MW 0 to 9999 kW
10 MW or greater, but less than 100 MW 0.00 to 99.99 MW
100 MW or greater, but less than 1 GW 0.0 to 999.9 MW
1 GW or greater 0 to 9999 MW
In this manual, the “UPM100” means the “UPM100” or “UPM101,”
and the illustrations show the “UPM100 with display function.”