8th Edition
This document species the important information to use this product correctly and
safely and the License Agreement of Attached Software for YFGW510 Field Wireless Ac-
cess Point.
Before use the product, be sure to read this document rst.
The conguration of the eld wireless system is described in User’s Manual of the
YFGW410 Field Wireless Management Station (IM 01W02D01-01EN). Read that document
rst.
Contents
Introduction...................................................................................................2
Safety Precautions .......................................................................................4
Explosion Protected Type Specications .............................................. 13
Installation of an Explosion Protected Instrument ......................... 14
FM Approval ......................................................................................... 15
Control Drawing (Doc. No. NFM027-A14) .................................... 17
CSA Certication.................................................................................. 19
ATEX Certication................................................................................ 23
IECEx Certication............................................................................... 30
Ground Cable Connection .................................................................. 37
How to Use Online Manual ....................................................................... 38
Preparation to Use YFGW510 Attached Software ................................. 38
Copyright and Trademark Notices .......................................................... 39
Patent Notice ............................................................................................. 39
Open Source Software ............................................................................. 40
About User’s Manual ................................................................................ 40
Information of User’s Manual Revision .................................................. 41
YFGW510 Software License Agreement................................................. 42

2
<Read Me First>
IM 01W02E01-11EN
Introduction
This manual (IM 01W02E01-11EN) describes the safety precautions, explosion protected
type specications and the license agreement of attached software for the YFGW510.
There are three documents including this one for the YFGW510 listed below. Read them
along with this manual.
Document No. Document name Description
IM 01W02E01-01EN YFGW510
Field Wireless Access Point
This manual is stored in the attached DVD-ROM for
YFGW510. It describes installation, wiring, operation,
maintenance and specication of the YFGW510.
IM 01W02E01-11EN YFGW510
Field Wireless Access Point
Read Me First
This manual. It describes the safety precaution,
explosion protected type specications and the
license agreement of the attached software for the
YFGW510.
GS 01W02E01-01EN YFGW510
Field Wireless Access Point
Product specication including detailed model and
sufx code, optional specications and accessory of
the YFGW510.
n Regarding This User's Manual
l This manual should be provided to the end user. Please recommend end users
to keep this manual at hand and refer to it as needed.
l This manual and the identication tag attached on packing box are essential
parts of the product; keep them in a safe place for future reference.
l Before use, read this manual thoroughly to comprehend its contents.
l The purpose of the User’s Manual is to describe details of functions provided
in this product, not to warrant the product's suitability to the specic purposes
of customers.
l No part of this manual may be reproduced in any form without Yokogawa's
written permission.
l The contents of this manual may be changed without prior notice.
l All reasonable effort has been made to ensure the accuracy of the contents of
this manual. However, if any errors or omissions are found, please inform any
of sales ofces listed on the back cover or your local distributor.
l The specications covered by this manual are limited to those for the standard
type under the specied model number break-down and do not cover custom-
made instruments. When products whose sufx code or optional codes con-
tain code “Z” and an exclusive document is attached, please read it along with
this manual.
l Please note that this User’s Manual may not be revised for any specication
changes, construction changes or operating part changes that are not consid-
ered to affect function or performance.

3
<Read Me First>
IM 01W02E01-11EN
n ATEX Documentation
l This is only applicable to the countries in European Union.
GB
DK
I
E
NL
SF
P
F
D
S
LT
LV
PL
EST
SLO
H
BG
RO
M
CZ
SK
GR
F01.ai

4
<Read Me First>
IM 01W02E01-11EN
Safety Precautions
n Safety, Protection, and Modication of the Product
l In order to protect the operator, product, and system controlled by the prod-
uct, observe the safety precautions described in this User’s Manual. If users
handle contrary to these instructions, we can not guarantee the safety.
l If this instrument is used in a manner not specied in this User’s Manual, the
protection provided by this instrument may be impaired.
l Modication of the product is strictly prohibited.
l If customers attempt to repair or modify explosion protected type products
and fail to return them to their original state, the explosion protected structure
of this product will be lost, resulting in a hazardous state. All repairs and modi-
cations of the product must be consulted with Yokogawa.
l If any protection or safety circuit is required for the system controlled by the
product or for the product itself, prepares it separately.
l Be sure to use the spare parts approved by Yokogawa Electric Corporation
(hereafter simply referred to as Yokogawa) when replacing parts or consuma-
bles.
l The following symbols are used in the product and User’s Manual to indicate
that there are precautions for safety:
CAUTION
Indicates that caution is required for operation. This symbol is placed on the parts necessary to
refer to the User’s Manual for protecting the operator and equipment. In the User’s Manual you
will nd precautions to avoid physical injury or death of the operator, including electrical shocks,
injuries of human body, and so on.
WARNING
Indicates instructions that must be observed in order to prevent the software or hardware from
being damaged or the system from becoming faulty.
IMPORTANT
Indicates important information required to understand operations or functions.

5
<Read Me First>
IM 01W02E01-11EN
NOTE
Draws attention to information essential for understanding the operation and features.
TIP Indicates additional information.
SEE
ALSO
Indicates a source to refer to
Indicates a protective grounding terminal. Before using the product, ground the terminal.
Indicates a functional grounding terminal. Before using the product, ground the terminal.
Indicates a DC supply
n Safe Use of This Product
This product is designed to be used by a person with specialized knowledge. For the safety of
the operator and to protect the instrument and the system, please be sure to follow this manual’s
safety instructions when handling this instrument. If these instructions are not heeded, the protec-
tion provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that
the instrument can be safely operated. Please pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowl-
edge of this device. Operators are not allowed to carry out installation unless they meet this
condition.
• All installation shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge
of this instrument. Operators are not permitted to carry out wiring unless they meet this condi-
tion.
(c) Operation
• Wait 1 min. after the power is turned off, before opening the covers.
(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require
further assistance, please contact the nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust or other materials on the display glass
and the name plate. To clean these surfaces, use a soft, dry cloth.
(e) Explosion Protected Type Instrument
• Users of explosion protected instruments should refer rst to “Explosion Protected Type
Specications” section of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the
device.

6
<Read Me First>
IM 01W02E01-11EN
• Take care not to create sparks when accessing the instrument or peripheral devices in a
hazardous location.
• Repair or modication to this instrument by customer will cause malfunction of explosion
protect function and hazardous situation. If you need to repair or modication, please contact
the nearest Yokogawa ofce.
(f) Modication
• Yokogawa will not be liable for malfunctions or damage resulting from any modicationmade
to this instrument by the customer.
(g) Product Disposal
• The instrument should be disposed of in accordance with local and national legislation/regu-
lations.
n Warranty
l The warranty terms of this instrument are described in the quotation. We will
make any repairs that may become necessary during the guaranteed term free
of charge.
l Please contact our sales ofce or your local distributor if this instrument re-
quires repair.
l If the instrument is faulty, contact us with complete details about the prob-
lem and the length of time it has been faulty, and state the model and serial
number. We would appreciate the inclusion of drawings or additional informa-
tion.
l The results of our examination will determine whether the product will be re-
paired free of charge or on an at-cost basis.
n The guarantee will not apply in the following cases:
l Damage due to negligence or insufcient maintenance on the part of the cus-
tomer.
l Problems or damage resulting from handling, operation or storage that vio-
lates the intended use and specications.
l Problems that result from using or performing maintenance on the instrument
in a location that does not comply with the installation location specied by
Yokogawa.
l Problems or damage resulting from repairs or modications not performed by
Yokogawa or someone authorized by Yokogawa.
l Problems or damage resulting from inappropriate installation after delivery.

7
<Read Me First>
IM 01W02E01-11EN
l Problems or damage resulting from disasters such as res, earthquakes,
storms, oods, or lightning strikes and external causes.
n Warranty and Disclaimer
l Yokogawa assumes no responsibilities for this product except as stated in the
warranty.
l Yokogawa shall have neither liability nor responsibility to any person or entity
with respect to any direct or indirect loss or damage arising from using the
product or any defect of the product that Yokogawa can not predict in ad-
vance.
n Authorized Representative in the EEA
The Authorized Representative for this product in the EEA is: Yokogawa Europe B.V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS.
n Notes on Hardware
lAppearance and Accessories
Check the following when you receive the product:
• Appearance
• Standard accessories
Contact our sales representative or your local distributor if the product’s coating has come off or
any accessories are missing.
l Model and Sufx Codes
The name plate on the product contains the model and sufx codes. Verify that the specication
indicated in the “MODEL AND SUFFIX CODES” and “OPTIONAL SPECIFICATIONS” in General
Specications “GS 01W02E01-01EN” is in compliance with the specications written on the order
sheet. If you have any questions, contact our sales ofce or your local distributor.
n Notes on Attached Software
l Before opening the media package, read YFGW510 Software License Agree-
ment. Once the package is opened, it is thought that the contract is agreed.
l Yokogawa assumes no responsibilities for this software except as stated in
the warranty.
l This software is used with this product exclusively. This can be installed in the
computer which connects with this product.

8
<Read Me First>
IM 01W02E01-11EN
n Regulatory Compliance for Radio and Telecommunication
Please conrm that an installation region fullls a standards, require additional regulatory infor-
mation and approvals, contact to Yokogawa Electric Corporation.
l Radio Equipment Directive
Hereby, Yokogawa Electric Corporation declares that the radio equipment type YFGW510 is in
compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is avail-
able at the following internet address:
http://www.yokogawa.com/d/
l EMC Conformity Standards
EN 301 489-1, EN 301 489-17, EN 61326-1 Class A, Table 2 (For use in industrial locations),
EN55011 Class A, Group 1, EN61000-6-2
This instrument is a Class A product, and it is designed for use in the industrial environment.
Please use this instrument in the industrial environment only.
l Safety Conformity Standards
Applicable standard: EN61010-1, EN 62311
(1) Pollution Degree 2
“Pollution degree” describes the degree to which a solid, liquid, or gas which deteriorates dielec-
tric strength or surface resistivity is adhering. “2” applies to normal indoor atmosphere. Normally,
only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by
condensation must be expected.
(2) Installation Category I
“Overvoltage category (Installation category)” describes a number which denes a transient
overvoltage condition. It implies the regulation for impulse withstand voltage. “I” applies to electri-
cal equipment which is supplied from the circuit when appropriate transient overvoltage control
means (interface) are provided.
l Spectrum Conformity Standard
EN 300 328

9
<Read Me First>
IM 01W02E01-11EN
lFCC compliance
YFGW510 contains transmitter module
• FCC ID: SGJ-WFC006 (All Model)
• FCC ID: SGJ-WFC008 (Wireless LAN Single Model)
• FCC ID: SGJ-WFC009 (Wireless LAN Redundant Model)
Co-located:
This transmitter must not be co-located or operated in conjunction with any other antenna or
transmitter.
FCC CAUTION
Changes or modications not expressly approved by the party responsible for compliance could
void the user’s authority to operate the equipment.
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful interference to radio communica-
tions. Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
RF Exposure Compliance:
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environ-
ment and meets the FCC radio frequency (RF) Exposure Guidelines in Supplement C to OET65.
This equipment has very low levels of RF energy that it deemed to comply without maximum
permissive exposure evaluation (MPE). But it is desirable that it should be installed and oper-
ated keeping the radiator at least 20cm or more away from person’s body (excluding extremities:
hands, wrists, feet and ankles).
Wireless LAN Model Only:
Compliance with FCC requirement 15.407(c)
Data transmission is always initiated by software, which is the passed down through the MAC,
through the digital and analog baseband, and nally to the RF chip. Several special packets are
initiated by the MAC. These are the only ways the digital baseband portion will turn on the RF
transmitter, which it then turns off at the end of the packet. Therefore, the transmitter will be on
only while one of the aforementioned packets is being transmitted. In other words, this device
automatically discontinue transmission in case of either absence of information to transmit or
operational failure.
5.15-5.25GHz band:
5.15-5.25GHz band is restricted to indoor operations only.
Frequency Tolerance:
±20 ppm

10
<Read Me First>
IM 01W02E01-11EN
l Industry Canada (IC) compliance
YFGW510 contains transmitter module
• IC: 8999A-WIC003 (All Model)
• IC: 8999A-WIC007 (Wireless LAN Single Model)
• IC: 8999A-WIC008 (Wireless LAN Redundant Model)
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is sub-
ject to the following two conditions: (1) this device may not cause interference, and (2) this device
must accept any interference, including interference that may cause undesired operation of the
device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio
exempts de licence.L’exploitation est autorisée aux deux conditions suivantes : (1) l’appareil ne
doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioé-
lectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of
a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce
potential radio interference to other users, the antenna type and its gain should be so chosen that
the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful
communication.
This radio transmitter IC Number 8999A-WIC003, 8999A-WIC007 and 8999A-WIC008 has been
approved by Industry Canada to operate with the antenna types listed below with the maximum
permissible gain and required antenna impedance for each antenna type indicated. Antenna
types not included in this list, having a gain greater than the maximum gain indicated for that
type, are strictly prohibited for use with this device.
Antenna type Frequency Band Gain, Impedance Description
Sleeve 2.4GHz 2.14dBi, 50Ω
Sleeve 2.4GHz/5GHz 2.14dBi, 50Ω 8999A-WIC007/008 Only
Collinear 2.4GHz 9dBi, 50Ω
Conformément à la réglementation d’Industrie Canada, le présent émetteur radio peut fonction-
ner avec une antenne d’un type et d’un gain maximal (ou inférieur) approuvé pour l’émetteur par
Industrie Canada. Dans le but de réduire les risques de brouillage radioélectrique à l’intention
des autres utilisateurs, il faut choisir le type d’antenne et son gain de sorte que la puissance
isotrope rayonnée équivalente (p.i.r.e.) ne dépasse pas l’intensité nécessaire à l’établissement
d’une communication satisfaisante.
Le présent émetteur radio IC Number 8999A-WIC003, 8999A-WIC007 and 8999A-WIC008 a été
approuvé par Industrie Canada pour fonctionner avec les types d’antenne énumérés ci-dessous
et ayant un gain admissible maximal et l’impédance requise pour chaque type d’antenne. Les
types d’antenne non inclus dans cette liste, ou dont le gain est supérieur au gain maximal in-
diqué, sont strictement interdits pour l’exploitation de l’émetteur.
Antenna type Frequency Band Gain, Impedance Description
Sleeve 2.4GHz 2.14dBi, 50Ω
Sleeve 2.4GHz/5GHz 2.14dBi, 50Ω 8999A-WIC007/008 Only
Collinear 2.4GHz 9dBi, 50Ω

11
<Read Me First>
IM 01W02E01-11EN
RF Exposure Compliance:
This equipment complies with IC radiation exposure limits set forth for an uncontrolled environ-
ment and meets RSS-102 of the IC radio frequency (RF) Exposure rules. This equipment has
very low levels of RF energy that it deemed to comply without maximum permissive exposure
evaluation (MPE). But it is desirable that it should be installed and operated keeping the radiator
at least 20cm or more away from person’s body (excluding extremities: hands, wrists, feet and
ankles).
Cet équipement est conforme aux limites d’exposition aux rayonnements énoncées pour un envi-
ronnement non contrôlé et respecte les règles d’exposition aux fréquences radioélectriques (RF)
CNR-102 de l’IC. Cet équipement émet une énergie RF très faible qui est considérée conforme
sans évaluation de l’exposition maximale autorisée. Cependant, cet équipement doit être installé
et utilisé en gardant une distance de 20 cm ou plus entre le dispositive rayonnant et le corps (à
l’exception des extrémités : mains, poignets, pieds et chevilles).
Wireless LAN Model Only:
5.15-5.25GHz band:
5.15-5.25GHz band is restricted to indoor operations only.
La bande 5150-5250 MHz est restreints à une utilisation à l’intérieur.

12
<Read Me First>
IM 01W02E01-11EN
n Control of Pollution Caused by the Product
l China RoHS
This is an explanation for the product based on “Control of Pollution caused by Electronic Infor-
mation Products” in the People’s Republic of China.
電子情報製品汚染制御管理弁法(中国版 RoHS)
产品中有害物质或元素的名称及含量
型号 部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴二
苯醚
(PBDE)
YFGW510
现场无线接入点
壳体×○○○○○
基板组件 × ○ ○ ○ ○ ○
电缆×○○○○○
天线组件 × ○ ○ ○ ○ ○
○:表示该部件的所有均质材料中的有害物质的含量均在GB/T26572 标准中所规定的限量以下。
×:表示至少该部件的某些均质材料中的有害物质的含量均在GB/T26572 标准中所规定的限量以上。
环保使用期限:
该标识适用于SJ /T11364 中所述,在中华人民共和国销售的电子电气产品的环保使用期限。
注)该年数为“环保使用期限”,并非产品的质量保证期。
l EU RoHS
This product is in conformity with the following standard:
EN 50581:2012 (Technical documentation for the assessment of electrical and electronic prod-
ucts with respect to the restriction of hazardous substances)

13
<Read Me First>
IM 01W02E01-11EN
Explosion Protected Type Specications
n Optional Specications (For Explosion Protected Type)
Item Description Code
Factory
Mutual
(FM)
FM Nonincendive Approval
Applicable standards: Class 3600:2011, Class 3611:2004,
Class 3810:2005, NEMA 250:2003
Nonincendive for Class I, Division 2, Groups A, B, C and D; alternatively
for Class I, Zone 2, Groups IIC. Suitable for Class II, Division 2, Groups F
and G; Suitable for Class III, Division 1
Indoor/outdoor Type 4X in hazardous (classied) locations.
Temperature Class T4 at Ta = –40 to 65°C (–40 to 149°F)
Cable parameters for antenna connection:
Ccable: ≤ 4 nF, Lcable: ≤ 20 μH
FN17
Explosionproof Approval -
Canadian
Standards
Association
(CSA)
CSA Non-Incendive Approval
Certicate: 2655412
Applicable standards: C22.2 No.0-10, CAN/CSA-C22.2 No. 0.4-04,
CAN/CSA-C22.2 No. 94-M91, C22.2 No. 213-M1987,
CAN/CSA-C22.2 No. 60079-0:11,
CAN/CSA-C22.2 No. 60079-15:12,
CAN/CSA-C22.2 No. 61010-1-04, IEC 60529 :2001
Non-Incendive for Class I, Division 2, Groups A, B, C and D;
Class II , Division 2, Groups F and G; Class III, Division I
Non-Incendive Field Wiring Connections for Class I , Division 2,
Groups A, B, C, D;
Ex nA [nL] IIC T4.
Ambient Temperature: –30 to 65 °C (–22 to 149°F), Altitude: ≤ 3000m
Enclosure: Type 4X, IP66
Cable parameters for antenna connection:
Ccable: ≤ 4 nF, Lcable: ≤ 20 μH
CN17
Flameproof Approval -
ATEX Type n Declaration
Applicable standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012,
EN 60079-15:2010
II 3 G Ex nA [ic] IIC T4 Gc
Enclosure: IP66
Amb. Temp. (Tamb): –30 to 65°C (–22 to 149°F)
KN27
ATEX Flameproof Approval
Certicate: DEKRA 15ATEX0042 X
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-11:2012
II 2 G Ex d [ib] IIC T4 Gb
Um: 250 V
Amb. Temp.(Tamb): -40 to 65°C (-40 to 149°F)
KF27
IECEx IECEx Type n Approval
Certicate: IECEx DEK 14.0028
Applicable standard: IEC60079-0:2011, IEC60079-11:2011,
IEC60079-15:2010
Ex nA [ic] IIC T4 Gc
Enclosure: IP66
Amb. Temp(Tamb): -30 to 65°C (-22 to 149°F)
SN27
IECEx Flameproof Approval
Certicate: IECEx DEK 15.0021X
Applicable Standard: IEC 60079-0:2011, IEC 60079-1:2007,
IEC 60079-11:2011
Ex d [ib] IIC T4 Gb
Um: 250 V
Amb. Temp.(Tamb): -40 to 65°C (-40 to 149°F)
SF27

14
<Read Me First>
IM 01W02E01-11EN
n Installation of an Explosion Protected Instrument
If a customer makes a repair or modication to an explosion protected instrument and the instru-
ment is not restored to its original condition, its explosion protected construction may be com-
promised and the instrument may be hazardous to operate. Please contact Yokogawa before
making any repair or modication to an instrument.
CAUTION
This instrument has been tested and certied as being explosion protected. Please note that se-
vere restrictions apply to this instrument’s construction, installation, external wiring, maintenance
and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
CAUTION
To preserve the safety of Flameproof equipment requires great care during mounting, wiring, and
piping. Safety requirements also place restrictions on maintenance and repair activities. Please
read the following sections very carefully.
CAUTION
• The front and rear cover are locked by an Allen head bolt (a shrouding bolt) on Flameproof
type instruments. When the shrouding bolt is driven clockwise by an Allen wrench, it is going
in and cover lock is released, and then cover can be opened by hand.
• When a cover is closed, it is the must turn the shrouding bolt counterclockwise and lock the
cover. Tighten the shrouding bolt to a torque of 0.7 N·m.
Shrouding bolt
F02.ai

15
<Read Me First>
IM 01W02E01-11EN
nFM Approval
Caution for FM Nonincendive Approval
(1) Technical Data
Note 1. Model YFGW510 Field Wireless Access Point with optional code FN17 is applica-
ble for use in hazardous (classied) locations.
• Applicable standards: Class 3600:2011, Class 3611:2004, Class 3810:2005,
NEMA 250:2003
• Nonincendive for Class I, Division 2, Groups A, B, C and D;
Alternatively for Class I, Zone 2, Group IIC
Suitable for Class II, Division 2, Groups F and G;
Suitable for Class III, Division 1
• Locations: Indoor/outdoor in hazardous (classied) locations
• Enclosure: Type 4X
• Temperature Class: T4
• Ambient Temperature: -40 to 65ºC
• Altitude: Up to 3000m
• Power supply: 10.0 V DC to 26.4 V DC (Rated voltage: 24.0 V DC)
• Power dissipation: 3.5 W max
• RF power: 60 mW max (ISA100.11a; IEEE802.15.4),
64 mW max (Wireless LAN: IEEE802.15.11a/b/g)
• Cable parameters for antenna connection: Ccable: 4 nF, Lcable: 20 μH
(2) Maintenance and Repair
WARNING
The instrument modication or parts replacement by other than authorized Representative of
Yokogawa Electric Corporation is prohibited and will void the FM Approvals approval.
(3) Installation
WARNING
• The installation of the devices should be carried out by the engineers or other professional
personnel of the related expertise. The installation should not be carried out by operators or
other unprofessional personnel.
• The equipment shall be installed in accordance with the user’s manual and following Control
drawing pages. (Doc. No. NFM027-A14)
• Screws of power supply terminals shall be tightened with specied torque values: 1.2 Nm to
1.4 Nm.

16
<Read Me First>
IM 01W02E01-11EN
(4) Electrical Connection
• The type of electrical connection depends on the marking below on YFGW510.
Marking The type of electrical connection Note
MM20 (ISO) M20 X 1.5
N1/2 NPT 1/2-14
• This marking is incused at the back side of the electrical connection block.
Marking
F03.ai

17
<Read Me First>
IM 01W02E01-11EN
(5) Control Drawing
F04.ai

18
<Read Me First>
IM 01W02E01-11EN
F05.ai

19
<Read Me First>
IM 01W02E01-11EN
n CSA Certication
Caution for CSA Non-incendive Certication
(1) Technical Data
Note 1. Model YFGW510 Field Wireless Access Point with optional code CN17 is applica-
ble for use in hazardous area.
• Certicate: 2655412
• Applicable standards:
C22.2 No.0-10, CAN/CSA-C22.2 No. 0.4-04,
CAN/CSA-C22.2 No. 94-M91, C22.2 No. 213-M1987
CAN/CSA-C22.2 No. 60079-0:11
CAN/CSA-C22.2 No. 60079-15:12
CAN/CSA-C22.2 No. 61010-1-04
IEC 60529:2001
• Hazardous Location Ratings: Non-Incendive for
Class I, Division 2, Groups A, B, C and D;
Class II , Division 2, Groups F and G;
Class III, Division I
Non-Incendive Field Wiring Connections for Class I , Division 2, Groups A, B, C, D;
Ex nA [nL] IIC T4
• Ambient Temperature: –30 to 65 °C
• Altitude: ≤ 3000m
• Enclosure: Type 4X, IP66
• Power Supply: 10.0 V d.c. to 26.4 V d.c. (Rated voltage: 24.0 V d.c.)
• Power dissipation: ≤ 3.5 W
• RF power: ≤ 60 mW (ISA100.11a; IEEE802.15.4)
≤ 64 mW (Wireless LAN: IEEE802.15.11a/b/g)
• Cable parameters for antenna connection: Ccable: ≤ 4 nF, Lcable: ≤ 20 μH
• Routine Test: The RF power is checked by routine tests.
(2) Specic condition of use
Precautions shall be taken to minimize the risk from electrostatic discharge of painted parts.
(3) Electrical Connection
• The type of electrical connection depends on the marking below on YFGW510.
Marking The type of electrical connection Note
MM20 (ISO) M20 X 1.5
AANSI 1/2 NPT 1/2-14 NPT

20
<Read Me First>
IM 01W02E01-11EN
• This marking is incused at the back side of the electrical connection block.
Marking
F06.ai
(4) Installation
Hazardous Location
*1: These apparatus are simple apparatus.
*2: Surge Arrester may not be installed.
Electrical Equipment
(e.g.) “d”, “i”, “Type n” equipment
Antenna
(*1)
Surge
Arrester
(*1, *2)
Antenna
(*1)
Surge
Arrester
(*1, *2)
Antenna
(*1)
Surge
Arrester
(*1, *2)
Hazardous Location
Zone 2 / Division 2
YFGW510
Field Wireless Access Point
Nonhazardous Location
Radio wave
(IEEE802.15.4)
wiring
Control
Equipment 1
Power Supply
Control
Equipment 2
Radio Wave
(IEEE802.11a/b/g)
or
metal wiring
or
optical fiber
ISA WLAN2
WLAN1
F07.ai
Table of contents
Other YOKOGAWA Wireless Access Point manuals
Popular Wireless Access Point manuals by other brands

WYLMAN
WYLMAN PEGASUS quick start guide

D-Link
D-Link NUCLIAS CONNECT DAP-2680 Quick installation guide

Ubiquiti
Ubiquiti Uni-fi AP quick start guide

ADTRAN
ADTRAN Bluesocket 2020 Series quick start

LevelOne
LevelOne WAB-6120 Quick installation guide

Planet Networking & Communication
Planet Networking & Communication WDAP-C7200E user manual