- 5 -
OPERATION MANUAL
Preparation
1) Make sure that all the gas cocks are closed.
2) Use air, nitrogen or other appropriate gas to check the leak inside the gas piping
3) Check if all the equipment for air and gas lines work properly..
4) Make sure that the gas is supplied as per specified pressure and that the gas inside the piping
has been replaced.
5) Start the blower and check if the outlet pressure is per specifications.
6) Use the control damper to set the maximum combustion (6kPa) and the minimum
combustion (0.1 ~0.5kPa).
7) Fully open the control damper and purge inside the furnace with air (You need to purge area
that is approximately 3 times larger than the furnace capacity).
8) Set the control damper to the minimum combustion.
Ignition
1) Make sure that the cock before the burner, solenoid valve and limiting valve are fully closed.
2) Ignite the pilot burner by pressing the ignition button. (Always use the pilot burner. Use of
torch or igniter rod is dangerous. Also, check if the ignition was made securely.)
3) Fully open the cock before the burner and the solenoid valve. Slowly open the limiting valve
and check if the main burner was ignited securely.
Adjustment
1) Measure the pressure difference of air orifice and acquire the air capacity from the table.
2) Calculate the required gas capacity and acquire the pressure difference of orifice that suits the
flow. Use the limiting valve to set the pressure difference. At this time, make sure to
convert the specific gravity of the atmosphere.
3) When using the equalizing valve control, slowly open the control damper to the maximum
combustion as you check the combustion status. Check the flow rates.
4) Use the flame detector to check the current value.
5) When the air ratio setting is completed, set the control damper to the minimum combustion
again. Joint the control motor and the control damper so that the necessary turndown will be
obtained.
Notes
1) The pressure inside the burner tile becomes high during the combustion, and removing the
sight hole may expose you to the flame. Pay special attention to the looseness of the sight
hole or glass daniage.
2) There are 3 types of orifices available depending on the type of gas. A plate that indicates
the orifice size is attached to the flange bolt where the gas orifice is fitted. Use the following
table to confirni the orifice size.
3) An orifice built in to the burner is intended to serve as adjustment guide. If you need more
accurate value, we recommend to install MO type metering orifice at some midpoint in the piping.
Extinction
Fully close the cock before the burner and the solenoid valve, and check if the flame has been
extinguished.
To protect the nozzle, wait until the furnace temperature falls down below 500 ℃
before stopping the combustion blower.