ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60
Air Handler Models Heater
Models1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity MOP.3Min Wire Size (AWG)4
208V 230V 208V 230V 208V 230V
AHR18B
6HK(0,1)6500206 10.0 12.6 14.3 15 15 12 12
6HK(0,1)6500506 20.0 23.4 26.8 25 30 10 10
6HK(0,1)6500806 32.0 36.4 41.8 40 45 8 8
6HK(0,1)6501006 40.0 45.1 51.8 50 60 8 6
AHR22B
6HK(0,1)6500206 10 13.5 15.3 15 20 12 12
6HK(0,1)6500506 20 24.3 27.8 25 30 10 10
6HK(0,1)6500806 32 37.3 42.8 40 45 8 8
6HK(0,1)6501006 40 46.0 52.8 50 60 6 6
6HK(1,2)6501306 52 59.0 67.8 60 70 6 4
6HK(1,2)6501506 60 67.7 77.8 70 80 4 4
AHR24B
6HK(0,1)6500206 10.0 12.6 14.3 15 15 12 12
6HK(0,1)6500506 20.0 23.4 26.8 25 30 10 10
6HK(0,1)6500806 32.0 36.4 41.8 40 45 8 8
6HK(0,1)6501006 40.0 45.1 51.8 50 60 8 6
6HK(1,2)6501306 52.0 58.1 66.8 60 70 6 4
6HK(1,2)6501506 60.0 66.8 76.8 70 80 4 4
AHR29C
AHR34C
6HK(0,1)6500206 10.0 13.8 15.4 15 20 12 12
6HK(0,1)6500506 20.0 24.6 27.9 25 30 10 10
6HK(0,1)6500806 32.0 37.6 42.9 40 45 8 8
6HK(0,1)6501006 40.0 46.3 52.9 50 60 6 6
6HK(1,2)6501306 52.0 59.3 67.9 60 70 6 4
6HK(1,2)6501506 60.0 68.0 77.9 70 80 4 4
AHR30B
AHR42C
6HK(0,1)6500206 10.0 14.6 16.3 15 20 12 12
6HK(0,1)6500506 20.0 25.4 28.8 30 30 10 10
6HK(0,1)6500806 32.0 38.4 43.8 40 45 8 8
6HK(0,1)6501006 40.0 47.1 53.8 50 60 6 6
6HK(1,2)6501306 52.0 60.1 68.8 70 70 6 4
6HK(1,2)6501506 60.0 68.8 78.8 70 80 4 4
AHR36B
AHR48D
6HK(0,1)6500206 10.0 14.6 16.3 15 20 12 12
6HK(0,1)6500506 20.0 25.4 28.8 30 30 10 10
6HK(0,1)6500806 32.0 38.4 43.8 40 45 8 8
6HK(0,1)6501006 40.0 47.1 53.8 50 60 8 6
6HK(1,2)6501306 52.0 60.1 68.8 70 70 6 4
6HK(1,2)6501506 60.0 68.8 78.8 70 80 4 4
6HK(1,2)6501806 72.0 81.8 93.8 90 100 4 3
6HK(1,2)6502006 80.0 90.4 103.8 100 110 3 2
AHR60D
6HK(0,1)6500206 10.0 14.6 16.3 15 20 12 12
6HK(0,1)6500506 20.0 25.4 28.8 30 30 10 10
6HK(0,1)6500806 32.0 38.4 43.8 40 45 8 8
6HK(0,1)6501006 40.0 47.1 53.8 50 60 8 6
6HK(1,2)6501306 52.0 60.1 68.8 70 70 6 4
6HK(1,2)6501506 60.0 68.8 78.8 70 80 4 4
6HK(1,2)6501806 72.0 81.8 93.8 90 100 4 3
6HK(1,2)6502006 80.0 90.4 103.8 100 110 3 2
6HK(1,2)6502506 100.0 112.1 128.8 125 150 2 1
1. (0,1) - maybe 0 (no circuit breaker) or 1 (with circuit breaker).
2. (1,2) maybe 1 (with circuit breaker, no breaker jumper bar) or 2 (with circuit breaker & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
4. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.