
035-13329-001-B-0504
16 Unitary Products Group
TWO-STAGE HEATING:
a. If the fan switch is in the “ON” position, the evapora-
tor blower motor relay (BR) will be energized
through terminal G to provide continuous blower
operation. If the fan switch is in the “AUTO” position,
the blower will operate only when there is a call for
heating by the thermostat.
b. Upon a call for first-stage heat by the thermostat, the
first stage of heat will be energized.
c. The thermostat will cycle the electric heat to satisfy
the heating requirements of the conditioned space.
CONTINUOUS BLOWER - Continuous blower operation is
possible by closing the R to G circuit on the thermostat.
HEAT ANTICIPATOR SETPOINTS
It is important that the anticipator setpoint be correct. Too
high of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON” cycles
and may result in the lowering of the temperature within the
conditioned space. Refer to Table 8 for the required heat
anticipator setting.
CHECKING SUPPLY AIR CFM
The speed of the supply air blower will depend on the
required CFM, the unit accessories and the static resistances
of both the supply and the return air duct systems. With this
information, the speed for the supply air blower can be deter-
mined from the static resistance and blower performance
data on Tables 3 thru 5.
Knowing the required blower RPM and the blower motor HP,
the speed setting for the direct-drive supply air motor can be
determined.
The setting (turns open) for the belt-drive supply air motor
pulley can be determined from Table 9.
BELT-DRIVE BLOWER
All units with belt-drive blowers have single-speed motors.
The variable pitch pulley on the blower motor can be adjusted
to obtain the desired supply air CFM.
Refer to Table 6 for blower motor and drive data. The tension
on the belts should be adjusted as shown in Figure 7.
Start the supply air blower motor. Adjust the resistances in
both the supply and the return air duct systems to balance
the air distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.
To check the supply air CFM after the initial balancing has
been completed:
TABLE 8: HEAT ANTICIPATOR SETTING
NOMINAL
HEATER
SIZE KW VOLTAGE SETTING, AMPS
TH1 TH2
5
7
10
15
20
30
240-3-60
0.35
0.35
0.35
0.35
0.35
0.35
-
-
-
0.19
0.38
0.38
7
10
15
20
30
480-3-60
0.35
0.35
0.35
0.37
0.37
-
-
-
0.29
0.29
TABLE 9: BELT DRIVE SUPPLY AIR ADJUSTMENT
MOTOR PULLEY ADJUSTMENT
TURNS
OPEN*
*.Pulley can be adjusted in half-turn increments.
BLOWER DRIVE RANGE (RPM)
3 TONS 4 TON 5 TON
5780 790 850
4842 856 924
3904 922 998
2966 988 1072
11028 1054 1246
01090 1120 1220
FIGURE 7 - BELT ADJUSTMENT
SPANLENGTH
DEFLFORCE
*NEVERLOOSEN
(A) (C)*
(D)
CAUTION
Procedureforadjustingbelt tension:
1.Loosennut(D)fromthemotormount.
2.Neverloosennuts(C)fromeachotherwhilelooseningnut(
D).
3.Adjust thetensionbyturningbolt(B).
4.Donotloosenthefournuts(topandbottom)(A);unlessadditionaltensioning
distanceisreq
uired;immediatelyre-tightentheseboltsifloosened.
5.Useabelt tensioncheckertoapplyaperpendicularforcetoonebeltat the
midpo
intof thespanasshown.Thedeflectionforceshouldbeapplied
untilaspecificdeflectiondistanceof4mm(5/32")isobtained.Todetermin
e
thedeflectiondistancefromnormalposition,useastraightedgefrom
sheavetosheaveasareferenceline.Therecommendeddeflection
force
isasfollows:
Tensionnewbeltsat themax.deflectionforcerecommendedforthebelt
section.Checkthebelt tensionatleast twotimesdu
ringthefirst24hoursof
operation.Anyre-tensioningshouldfallbetweenthemin.andmax.
deflectionforcevalues.
6.Afteradjusting,re
-tightennut(D)against themotormount takingcarenot
toloosennuts(C).
(B)