Yoto DP-SVA Series User manual

DP-SVA Series Digital Sensor Indicator
FEATURES:
This instrument is widely applied to all kinds of sensors with
linear output and other testing equipments to measure pressure,
weight, temperature, humidity, etc.
With decimal point setting, rate, range and zero point adjustment.
With analogue output 4 - 20mA DC
With auxiliary power supply: 12V or 24V
■
※
※
※
※
1. Ordering Code
2. Technical Specification
Instruction Manual
Thanks a lot for selecting YOTO products!
For your safe, please carefully read this manual and fully understand its contents before operating this instrument. If you have
problems, please contact our sales or distributors whom you buy from. This manual is subject to change without prior notice.
SAFETY CAUTIONS:
Make sure the power is at OFF status before connecting the wires to avoid electric shock and strictly follow the
connection diagram given out by the factory which is stuck on the product.
Make sure the power OFF when cleaning the product.
Working beyond the stated power supply (90 - 260V AC) is prohibited so as to avoid damage to the product
Make sure the output relay is used at the rate load and electrical life, if the contact of the output relay works
against the electrical life, it may melt or burned or even cause fire.
▲
or cause fire. The use life of the output relay is quite different according to its capacity and conditions.
Do not wire when the power is on. Do not connect the unused terminals. Do not disassemble, repair or modify
the instrument. This may cause electrical shock, fire or malfunction.
Power supply: 220V AC
※
Applications
Suitable for all kinds of sensors with linear output and other testing equipment.
This instrument can measure any range of current or voltage signal input.
It can be with 2-wire transmitters, pressure sensors, 4-wire weight sensors and so on.
■
※
※
※
※
※
A: Auxiliary power 12V DC B: Auxiliary power 24V DC
Analogue output 1: No analogue output 2: With 4 ~ 20mA analogue output
DP3-SVA: DP3-SVA Series 3 1/2 digit sensor meter
DP4-SVA: DP4-SVA Series 4 1/2 digit sensor meter
Example: DP3-SVA1B means that it is a DP3-SVA Series, 3 1/2 digit LED display sensor meter,
with no analogue output, auxiliary power 24V DC.
※
DP SVA
P1
Measured function Equipped with all kinds of sensors
Input signal Current: 4 ~ 20mA, 0 ~ 10mA, Voltage: 0 ~ 10V, 0 ~ 5V, 0 ~ 1V, 0 ~ 200mV, 0 ~ 20mV
Accuracy ± 0.5%FS ± 2 digit
A/D converter Dual integral
Sampling rate 2.5 times/second
Full scale DP3: 1999(decimal point can be set freely) DP4: 19999(decimal point can be set freely)
Display mode Red LED display (high: 14.2mm)
Load ≤600Ω
Ambient temperatur
e
0℃~50℃
Power supply AC 110V/ 220V, 50/ 60Hz
Dimension (mm) 48H X 96W X 100L
Weight (appr) 450g
Dielectric strength 1500V AC/ 1min
Insulation resistance 500V DC/ 100MΩ

DP-SVA Series Digital Sensor Indicator
4. Display adjustment
5. Terminal Connection
Current voltage or 12V
24V 4 ~ 20mA
o r 12V
Note: Please subject to the diagram on the product if there is any change.
3. Function setting
2). Decimal point setting (figure 2)
Figure 1 Figure 1
While setting the range and the decimal point, be sure to pull out the internal printed circuit board,
as the follow figure hows:
The pin head of range setting The pin head of decimal point setting
P2
1). Range setting (Figure 1)
While moving the jumper cap on different PIN head, you can get the position of the decimal point that you want.
Note: The original setting range is 0 ~ 10V, display 0 ~ 2000, you can adjust it to what you want.
1. While setting the span and zero, please open the front lid. As the following figure shows.
2. Span adjustment (SPAN)
Input a typical value, the display value can be increased, when forward adjust, the display value can be
decreased while reverse adjust.
3. Zero adjustment (ZERO)
Function forward adjust is forward biased, reverse adjust is reverse biased. After the adjustment of span value
and scale setting, you need to check whether zero need to be reset. Zero adjustment must be in zero input or
input short circuit or an adjustment signal. For example, input 4 ~ 20mA, if you want to display zero, you must
input 4mA in the terminal then adjust to zero. In order to diminish error, please adjust span & zero repeatedly.
The positions of jumper cap 20mA 10V 5V 1V 200mV
Input range 4 ~ 20mA/ 0 ~ 20mA 0 ~ 10V 0 ~ 5V 0 ~ 1V 0 ~ 200mV/ 0 ~ 20mV

+0.5
91
+0.5
45
30
25
112
96
48
6. Dimension
Hole Dimension
8. Cautions:
1). The product should be power on for 15 minutes before operating.
2). The appropriate ambient temperature is 0 ~ 50 ; relative humidity: 85%RH.
3). The product calibration period is 12 months.
4). Avoid shock and impact, prevent operation from heavy dust and poisonous chemicals and gas environment.
5). If the input signals with high frequency interference, the wires must configure a filter.
6). The input wires should not be too long. If the distance between the signal input terminal and the product can
not be shortened, please use shielded cable.
7). For long time storage, the meter should be shield form light with conservation temperature -10 ~ 70 / 60%RH.
9). If stock in long time without operation, power on the instrument one time every 3 month is recommended,
each time should be no less than 4 hours.
9. Others:
1). The complete product contains: product with connection diagram, instruction manual, installing brackets (1 set),
inspection certificate and packing box with product label.
2). Guarantee: any defected products under normal operation within 12 months can be returned and replaced by us;
Damage by user's wrong operation can not be replaced. If request to be returned for repair, buyer should take
chare fo the freight fee, on conditions that large quantities need to be repaired, repair fee should be considered.
8). Please stored in indry and ventilated place. Don't place in an area surrounded by organic solvents or corrosive gases.
7. Installation
1). Please make the holes on the shell according to meter hole dimensions. When there are more than two meters
to be installed, the distance of two holes between left meter and the right meter should be large than 25mm.
and the distance of two holes between the upper meter and the lower meter should be large than 30mm.
2). Insert the meter into the panel.
3). Insert the mounting bracket into mounting slot.
4). Push tight the mounting brackets so that the meter can combine with the shell firmly.
℃
℃
DP-SVA Series Digital Sensor Indicator
P3
V+
V-
Pressure transmitter: output signal in: 4 ~ 20mA, 2-wire
Application example: connect with pressure transmitter
※
Use with 2-wire pressure transmitter/ sensor. The instrument can supply DC 24V auxiliary power,
and the sensor output is 4 ~ 20mA. Software select input signal mA. Please refer to above figure 1.
Figure 1
Table of contents
Popular Controllers manuals by other brands

Full Gauge Controls
Full Gauge Controls TC-900Ri clock user manual

IBC
IBC V-10 operating instructions

Distech Controls
Distech Controls VA-045PNX024P Hardware installation guide

Signature
Signature EZ Indoor 8100 Series Installation & programming guide

A10
A10 Harmony Controller 2000 installation guide

Texmate
Texmate CL-B101D40-RTD manual