Device Recovery Objects (Send 0 and 1) [disabled/enabled]: this parameter
lets the integrator activate two new communication objects (“[Heartbeat]
Device Recovery”), which will be sent to the KNX bus with values “0” and “1”
whenever the device begins operation (for example, after a bus power failure).
It is possible to parameterise a certain delay [0…255][s] to this sending.
Figure 5. Device Recovery Objects.
Note: After download or bus failure, the sending takes place with a delay of up
to 6,35 seconds plus the parameterised delay, to prevent bus overload.
Internal Temperature Sensor [disabled/enabled]: enables or disables the
“Temperature Sensor” tab in the tree on the left. See section 2.1.2 for details.
Sounds [Default / Custom]: sets whether the sound functions (button beeps,
alarm and doorbell) should work according to the pre-defined configuration or
to a user-defined configuration. See section 2.1.4 for details.
Ambient luminosity sensor [disabled/enabled]: enables setting the ambient
luminosity sensor. When the sensor is enabled, a new tab for its configuration
is shown. See section 2.1.5 for details.
Proximity Sensor [disabled/enabled]: enables the proximity sensor. This
functionality permits “waking up” the device when detecting presence, see
section 2.1.6.
Time to Consider Inactivity [1…30…255][s/min/h]: allows setting a time after
which, if no pulsation or proximity detection has occurred, the LEDs turn off (or
acquire the brightness level configured, see section 2.1.3).
Advanced Configuration [disabled/enabled]: enables or disables the
“Advanced” tab in the tree on the left. See section 2.1.7 for details.