Zeta Premier M plus Product guide

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113
Issue: 2.2 Author: NRPJ Date: 24/7/2012
8-24 ZONE CONVENTIONAL FIRE ALARM PANEL
LOG BOOK & CERTIFICATES

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 1
Issue: 2.2 Author: NRPJ Date: 24/7/2012
FIRE ZONE INFORMATION
ZONE NO.
ZONE DESCRIPTION
A brief description of all the rooms and areas contained in
each zone.
QTY
SNDR
QTY
MCP
QTY HEADS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
SOUNDER CIRCUIT INFORMATION
SOUNDER
CIRCUIT
SOUNDER CIRCUIT DESCRIPTION
A brief description of all the rooms and areas contained in each circuit.
QTY SNDR
QTY BELLS
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
ANY OTHER INFORMATION ABOUT THE SOUNDER CIRCUITS

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 2
Issue: 2.2 Author: NRPJ Date: 24/7/2012
OUTPUT ROUTING INFORMATION
TYPE OF OUTPUT
CONNECTED
WHAT HAPPENS WHEN ACTIVATED
FIRE RELAY
YES/NO
FAULT RELAY
YES/NO
F.A.R.E. OUTPUT
YES/NO
ADDITIONAL INFORMATION
THE ABOVE INFORMATION WAS COMPLETED BY:
NAME
COMPANY
POSITION
DATE

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 3
Issue: 2.2 Author: NRPJ Date: 24/7/2012
It is recommended that this LOG BOOK be maintained by the responsible person(s) on site, who
should ensure every event is properly recorded (including fire alarm conditions, failures, tests,
temporary disconnections, disablements, enablements, dates of installing engineers’ visits
together with a note of any outstanding work or panel conditions). This LOG BOOK must be
available for inspection at all times.
You can photocopy this log book now to provide extra pages when this book is full.
Company:_______________________________________________________________________
Site Address:____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
System Designed By: ______________________________________________________________
System Installed By: ______________________________________________________________
System Commissioned By: _________________________________________________________
System Maintained By: ____________________________________________________________
Contract No:_____________________________________________________________________
Contract Valid Until: ______________________________________________________________
For Service (normal hours Mon-Fri) Tel:_______________________________________________
For Service (other times) Tel:_______________________________________________________
Responsible Person(s) on Site: ______________________________________________________
BS5839-1:2002+A2:2008 recommends that fire alarm events should be subdivided & recorded on
separate sheets in the log book. The event categories are:
Maintenance work –to be completed by any engineer undertaking any work on the system.
False Alarms –any alarm on the system not caused by a genuine fire. This includes:
ENVIRONMENTAL
FIRE –LIKE PHENOMENA
INAPROPRIATE ACTION
ACCIDENTAL DAMAGE
MALICIOUS ACTION
GENUINE BELIEF
EQUIPMENT FALSE ALARM
All other events: This would include all genuine alarms, and any faults that occur on the system.

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 4
Issue: 2.2 Author: NRPJ Date: 24/7/2012
MAINTENANCE WORK
DATE
TIME
ZONE/
LOCATION
REASON FOR WORK
WORK CARRIED OUT
ADDITIONAL WORK
REQUIRED
SIGNED

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 5
Issue: 2.2 Author: NRPJ Date: 24/7/2012
DATE
TIME
ZONE/
LOCATION
REASON FOR WORK
WORK CARRIED OUT
ADDITIONAL WORK
REQUIRED
SIGNED

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 6
Issue: 2.2 Author: NRPJ Date: 24/7/2012
FALSE & UNWANTED ALARMS
CATEGORIES OF FALSE ALARMS:
ENVIRONMENTAL - FIRE-LIKE PHENOMENA - INAPROPRIATE ACTION - ACCIDENTAL DAMAGE
MALICIOUS ACTION - GENUINE BELIEF - EQUIPMENT FALSE ALARM
DATE
TIME
ZONE/
LOCATION
CAUSE (IF
KNOWN) OR
ACTIVITIES IN
ALARM AREA
MAINTENANCE
VISIT NEEDED
(YES/NO)
MAINTENANCE
FINDINGS
CATEGORY OF
FALSE ALARM
FURTHER
ACTION
REQUIRED
SIGNED

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 7
Issue: 2.2 Author: NRPJ Date: 24/7/2012
CATEGORIES OF FALSE ALARMS:
ENVIRONMENTAL - FIRE-LIKE PHENOMENA - INAPROPRIATE ACTION - ACCIDENTAL DAMAGE
MALICIOUS ACTION - GENUINE BELIEF - EQUIPMENT FALSE ALARM
DATE
TIME
ZONE/
LOCATION
CAUSE (IF
KNOWN) OR
ACTIVITIES IN
ALARM AREA
MAINTENANCE
VISIT NEEDED
(YES/NO)
MAINTENANCE
FINDINGS
CATEGORY OF
FALSE ALARM
FURTHER
ACTION
REQUIRED
SIGNED

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 8
Issue: 2.2 Author: NRPJ Date: 24/7/2012
GENUINE ALARMS AND ALARM SYSTEM FAULTS
ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS
DATE
TIME
ZONE/
LOCATION
DETAILS OF EVENT (INCLUDING
CAUSE IF KNOWN)
ACTION REQUIRED
DATE
COMPLETED
INITIALS

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 9
Issue: 2.2 Author: NRPJ Date: 24/7/2012
ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS
DATE
TIME
ZONE/
LOCATION
DETAILS OF EVENT (INCLUDING
CAUSE IF KNOWN)
ACTION REQUIRED
DATE
COMPLETED
INITIALS

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 10
Issue: 2.2 Author: NRPJ Date: 24/7/2012
COMMISSIONING THE SYSTEM, INCLUDING P.S.E.
The commissioning of this fire alarm system should be performed by a qualified
commissioning engineer, who has an understanding of sections 2,3,& 4 of BS5839-
1:2002+A2:2008 (i.e. Design considerations, Limitations of false alarms, Installation
recommendations)
The system layout drawing should be checked for accuracy & stored in a safe place,
accessible to any fire officer.
The Fire Alarm System Summary (Page 2) should be checked for accuracy.
The fire alarm log book contact details should be checked for completeness.
The insulation of cables should be checked in accordance with BS5839-1:2002+A2:2008
clause 38.2 for compliance.
The Earthing should be checked in accordance with BS5839-1:2002+A2:2008 clause 38.2 for
compliance.
The PSE mains feed from a 3A spur should be checked. It should be protected by an over
current device (MCB) NOT an earth leakage device (RCD).
The PSE Charger voltage should be checked & adjusted if necessary (27.6 with batteries
disconnected).
The battery voltage should be checked (should be between 24 & 27V)
All call points & detectors can signal an alarm condition and indicate the correct zone (and
text message) on the fire alarm panel.
The Sound pressure level throughout the building should be checked for compliance with
the recommendations of BS5839-1:2002+A2:2008 clause 16.2
Any deviations from BS5839-1:2002+A2:2008 clause 7.2 should be listed in the Certificate
of Installation & Commissioning.
The Certificate of Installation & Commissioning should be completed, and the whole user
manual passed to the relevant person on site. (They should be given a brief training on the
basic operation of the FACP)
DESIGN, INSTALLATION & COMMISSIONING CERTIFICATES
The guidelines in BS5839-1:2002+A2:2008 say that each stage of the system design and installation
should have a separate certificate. Before this User Manual is handed over to the relevant
person(s) on site, the following certificates (or the relevant company’s equivalent) should be
completed by the system designer, the installation engineer and the commissioning engineer. The
System Description sheet should also be completed on Page 2 as should the relevant parts of the
Log Book section on Page 3.
The user, or responsible person should then complete the acceptance certificate to acknowledge
that they have been instructed in the use of the fire alarm, have witnessed that it is operational,
and have been given all the relevant paperwork (drawings, log book, user manual, etc.)

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 11
Issue: 2.2 Author: NRPJ Date: 24/7/2012
Design Certificate (Page 1 of 2)
Certificate of DESIGN for the Infinity 8 Fire Alarm System installed at:
ADDRESS:
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the design of
the fire alarm system, particulars of which are set out below, CERTIFY that the said design for which I/we
have been responsible complies to the best of my/our knowledge and belief with the recommendations of
section 2 of BS 5839-1:2002 for the system category described below, except for the variations, if any,
stated in this certificate
Name (Block Letters):
Position:
Signature:
Date:
For & on behalf of:
Address
The extent of liability of the signatory is limited to the system described below.
System Category (see BS 5839-1:2002, Clause 5):
Variations from the recommendations of section 2 of BS 5839-1:2002 (see Clause 7):)
Extent of system covered by this certificate:
Brief description of areas protected (not applicable for Category M, L1 or P1 systems):

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 12
Issue: 2.2 Author: NRPJ Date: 24/7/2012
Design Certificate (Page 2 of 2)
Measures incorporated to limit false alarms. Account has to be taken of the guidance contained in section 3
of BS 5839-1: 2002 and, more specifically (tick as appropriate):
The System is manual. Type & siting of manual call points takes account of the guidelines contained in
section 3 of BS 5839-1
The system incorporates automatic fire detectors, and account has been taken of reasonably foreseeable
causes of unwanted alarms, particularly in the selection and siting of detectors
An appropriate analogue system has been specified
An appropriate multi-sensor system has been specified
A time-related system has been specified. Details:
Fire signals from automatic fire detectors result initially in a staff alarm, which delays a general alarm /
transmission of signals to an alarm receiving centre (delete as applicable) for min.
Appropriate guidance has been provided to the user to enable limitation of false alarms.
Other measures as follows:
INSTALLATION & COMMISSIONING RECOMMENDATIONS
It is strongly recommended that installation and commissioning be undertaken in accordance with the
recommendations of section 4 and section 5 of BS 5839-1: 2002 respectively.
SOAK TEST
In accordance with the recommendations of clause 35.2.6 of BS 5839-1:2002, it is recommended that
following commissioning a soak period of should follow.
(enter a period of at least 1 week)
As the system incorporates no more than 50 automatic fire detectors, no soak test is necessary to satisfy
the recommendations of BS 5839-1:2002
VERIFICATION
Verification that the system complies with BS 5839-1:2002 should be carried out, on completion, in
accordance with BS 5839-1:2002 Clause 43
Yes No To be decided by the purchaser or user
MAINTENANCE
It is strongly recommended that, after completion, the system is maintained in accordance with section 6 of
BS 5839-1:2002
USER RESPONSIBILITIES
The user should appoint a responsible person to supervise all matters pertaining to the fire alarm system in
accordance with the recommendations of section 7 of BS 5839-1:2002

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 13
Issue: 2.2 Author: NRPJ Date: 24/7/2012
Installation Certificate
Certificate of INSTALLATION for the Infinity 8 Fire Alarm System installed at:
ADDRESS:
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the
installation of the fire alarm system, particulars of which are set out below, CERTIFY that the said
installation for which I/we have been responsible complies to the best of my/our knowledge and belief
with the specifications described below, and with the recommendations of BS5839-1:2002, except for the
variations, if any, stated in this certificate
Name (Block Letters):
Position:
Signature:
Date:
For & on behalf of:
Address
The extent of liability of the signatory is limited to the system described below.
Extent of the installation work covered by this certificate.
Specification against which the system was installed:
Variations from the specification and/or section 4 of BS 5839-1:2002 (see clause 7)
The wiring has been tested in accordance with the recommendations of clause 38 of BS 5839-
1:2002. The test results have been recorded and provided to:
Unless supplied by others, the “as fitted” drawings have been supplied to the person responsible for
commissioning the system (see BS 5839-1:2002 clause 36.2m)

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 14
Issue: 2.2 Author: NRPJ Date: 24/7/2012
Commissioning Certificate
Certificate of COMMISSIONING for the Infinity 8 Fire Alarm System installed at:
ADDRESS:
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the
commissioning of the fire alarm system, particulars of which are set out below, CERTIFY that the said work
for which I/we have been responsible complies to the best of my/our knowledge and belief with the
recommendations of Clause 39 of BS5839-1:2002, except for the variations, if any, stated in this certificate
Name (Block Letters):
Position:
Signature:
Date:
For & on behalf of:
Address
The extent of liability of the signatory is limited to the system described below.
Extent of the installation work covered by this certificate.
Variations from the recommendations of clause 39 of BS 5839-1:2002 (see clause 7)
All equipment operates correctly
Installation work is, as far as can be reasonably ascertained, of an acceptable standard
The entire system has been inspected and tested in accordance with the recommendations of 39.2.c of
BS 5839-1: 2002.
The system performs as required by the specifications prepared by:
Taking into account the guidance contained in section 3 of BS 5839-1: 2002, I/we have not identified
any obvious potential for an unacceptable rate of false alarms.
The documentation described in Clause 40 of BS 5839-1:2002 has been provided to the user
The following work should be completed before/after (delete as applicable) the system becomes
operational
The following potential causes of false alarms should be considered at the time of the next service visit:
Before the system becomes operational, it should be soak tested in accordance with the recommendations
of Clause 35.2.6 of BS 5839-1:2002 for a period of: (enter a period of 1 week, the period
required by the design specification, or the period recommended by the signatory to this certificate,
whichever period is the greatest, or delete if not applicable)

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-113 PAGE 15
Issue: 2.2 Author: NRPJ Date: 24/7/2012
Acceptance Certificate
Certificate of ACCEPTANCE for the Infinity 8 Fire Alarm System installed at:
ADDRESS:
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the
acceptance of the fire alarm system, particulars of which are set out below, ACCEPT the system on behalf
of:
Name (Block Letters):
Position:
Signature:
Date:
For & on behalf of:
Address
The extent of liability of the signatory is limited to the system described below.
Extent of the system covered by this certificate.
All installation work appears to be satisfactory.
The system is capable of giving a fire alarm signal
The facility for remote transmission of alarms to an alarm receiving centre operates correctly.
(Delete if not applicable)
The following documents have been provided to the purchaser or user:
“As fitted” drawings.
Operating and maintenance instructions
Certificates of Design, Installation and Commissioning.
A log book.
Sufficient representatives of the user have been properly instructed in the use of the system, including,
at least, all means of triggering fire signals, silencing and resetting the system, and avoidance of false
alarms.
All relevant tests, defined in the purchasing specification, have been witnessed.
(Delete if not applicable.)
The following work is required before the system can be accepted:
Other manuals for Premier M plus
2
This manual suits for next models
1
Table of contents
Other Zeta Fire Alarm manuals
Popular Fire Alarm manuals by other brands

DSC
DSC WS4916 Series Installation and operation instruction manual

Gamewell
Gamewell Smart Start IDENTIFLEX 630 Installation & operation manual

Etherma
Etherma eNEXHO-IC Assembly and operating instructions

System Sensor
System Sensor SS24ADAS Series quick start guide

Tyco
Tyco MZX125 user manual

Dellcos
Dellcos FM-CO user manual

Teknim
Teknim TFS-1183R installation manual

Simplex
Simplex IDNet 4099-9801C installation instructions

Simplex
Simplex Saturn 2500 operating instructions

Comelit
Comelit 48CME100 Technical manual

Polon-Alfa
Polon-Alfa POLON 4000 Series Installation and maintenance manual

bolid
bolid S2000-IP-03 instruction manual