A&D AD-8923-CC User manual

AD-8923-CC
Remote Controller
(CC-Link)
INSTRUCTION MANUAL
1WMPD4002124C

© 2010 A&D Company, Limited. All rights reserved.
No part of this publication may be reproduced, transmitted, transcribed, or translated
into any language in any form by any means without the written permission of A&D
Company, Limited.
The contents of this manual and the specifications of the instrument covered by this
manual are subject to change for improvement without notice.
.

3
CONTENTS
1. INTRODUCTION ...................................................................................... 4
1.1. Features .............................................................................................. 4
1.2. Applicable Instruments ........................................................................ 5
2. DESCRIPTION OF EACH PART.............................................................. 6
2.1. Display ................................................................................................ 7
2.2. Keys .................................................................................................... 7
2.3. Connectors.......................................................................................... 7
3. CONNECTION ......................................................................................... 8
3.1. Setting the weighing instrument and the AD-8923-CC ........................ 8
3.2. Connecting the cables ......................................................................... 8
3.3. Turning the power on ......................................................................... 11
3.4. Operation .......................................................................................... 13
3.5. Calibrating the AD-4212C.................................................................. 14
4. FUNCTION SETTING ............................................................................ 16
4.1. Display and keys ............................................................................... 17
4.2. Function table ................................................................................... 17
4.3. Initializing the AD-8923-CC ............................................................... 18
5. RS-232C CONNECTOR ......................................................................... 19
5.1. RS-232C serial interface specifications ............................................. 19
6. CC-Link CONNECTOR .......................................................................... 20
6.1. CC-Link interface specifications ........................................................ 20
6.2. Timing chart ...................................................................................... 25
6.3. Fixing the decimal point position ....................................................... 27
6.4. Calibration with the AD-4212C using the register of the CC-Link ............. 28
7. TROUBLESHOOTING ........................................................................... 29
8. SPECIFICATIONS.................................................................................. 30
9. EXTERNAL DIMENSIONS ..................................................................... 31

4
1. INTRODUCTION
This manual describes how the AD-8923-CC remote controller works and how
to get the most out of it in terms of performance.
Read this manual thoroughly before using the AD-8923-CC and keep it at
hand for future reference.
1.1. Features
Connecting the AD-8923-CC remote controller to a weighing instrument will
enable transmission of RS-232C weighing data from the weighing instrument
to a PLC using CC-Link(⋆1).
Displays the weighing data transmitted from the weighing instrument.
Key operations remotely control the weighing instrument (⋆2)
Using the CC-Link interface, the AD-8923-CC can receive the weighing data
or perform re-zeroing of the weighing instrument.
Note
⋆1 The AD-8923-CC CC-Link is a remote device station of CC-Link
ver.1.10.
⋆2 Entering the function setting mode of the weighing instrument is not
available. Available operations depend on the weighing instrument
used. See Table 2 in “1-2 Applicable Instruments”.
⋆3 CC-Link is a high-speed field network able to simutaneouslly handle
both control and information data. With a high communication speed
of 10 Mbps, CC-Link can achieve a maximum transmission distance of
100 meters and connect to 64 stations.
When a CC-Link network is configured using the AD-8923-CC, the
maximum number of stations (or units) will be 42.

5
1.2. Applicable Instruments
The AD-8923-CC functions in two ways as follows, depending on the weighing instrument used:
● A remote controller that displays the weighing data and remotely controls the weighing
instrument.
● A remote display that displays the weighing data.
Available key operations depends on the weighing instrument used. (Refer to “Table 2”)
For weighing instruments not listed in this table, please refer to the A&D website.
Table 1 Applicable weighing instruments and what is required
Weighing instrument What is required to connect to weighing instrument
Option for the instrument Communication cable
(
Length 2m
)
AD-4212C,AD-4212D None (D-sub 9 pin)
None
(Use the cable provided for AD-4212C/D)
⋆1
AD-4212A/B,GX,GF,GX-K,GF-K,MC,GP,GR,HR
None (D-sub 25 pin) AX-KO1710-200
GX-A,GF-A, GX-M,GF-M,FZ-i,FX-i,EK-i,EW-i,
EK-L,BM,GH,HR-i,HR-AZ,HR-A, None (D-sub 9 pin) AX- KO2466-200
EJ,HV-C,HV-CP,HW-C,HW-CP OP-03 (D-sub 9 pin) AX- KO2466-200
HV-G,HW-G,HW-WP None (Din 8 pin) AX-KO1786-200
FG-L,FG-M OP-23 (Din 8 pin) AX-KO1786-200
FS-i,SC,SE,SW OP-03 (Wire) AX-KO3285-320
⋆1 When connecting to the AD-4212C/D, use the cable provided as a standard accessory for the
AD-4212C/D.
The part number for standard accessory cable for the AD-4212C is AX-KO3590-1000 (10m).
The part number for standard accessory cable for the AD-4212D is AX-KO3590-200 (2m).
Table 2 Applicable weighing instruments and key operations
Weighing instrument
AD-8923-CC keys
ON:OFF
CAL SAMPLE PRINT MODE RE-ZERO
AD-4212C
Turns the
weighing
instrument
display on or
off.
(Note 1)
Calibrates
using the
external
weight
(Note 4)
Switches the
readability
(Note 2)
Determines
operation
during various
settings
Switches the
response
chracteristic
Sets the display
to zero
AD-4212D
Calibrates
using the
internal
weight
GX, GX
-
A,
GX-M,GX-K,GP,GH,
FZ-i,MC,BM,HR-AZ
Switches the
unit displayed
(Note 3)
GR
GF, GF-A, GF-M,GF-K,
AD-4212A/B,HR-i,
FX-i, HR-A
-
EJ,EK-i,EW-i,EK-L,
FG-L,FG-M,FS-i,SW,
HV-G,HW-G,HW-WP,HV-
C,HV-CP,HW-C,HW-CP
(Note 5)
⋆ "ー" in the table indicates that the key operation is not available.
Note 1)Switching the standby or weighing mode is available for the AD-4212C/D.
2)Not available for the counting mode or percent mode.
3)Not available for the AD-4212A/B.
4)For weighing instruments other than AD-4212C/D, the AD-8923-CC displays "------".
Use the display on the balance.
5)Do not operate by using the key on the AD-8923-CC.

6
Accessories
2. DESCRIPTION OF EACH PART
See the note
below.
Note
When the AD-8923-CC is to be
built into a weighing system, be
sure to ground the FG terminal.
Please confirm that the AC
adapter type is correct for your
local voltage and receptacle type.
Display
AC adapter
input jack
Rear View
Keys
DC input terminal
CC
-
Link connector
RS
-
232C connector
(D-Sub 9-pin)
FG terminal
AD adapter
ID label
CC
-
Link plug 1 pc
.
Connector operation lever 1 pc.
AC adapter 1 pc.
Attach the identification
sticker for your model to
the AC adapter as shown.

7
2.1. Display
Displays the weighing data received. When the unit is “g” (gram), the unit
indicator turns on. If the balance outputs RS-232C weighing data that
exceeds six digits, the AD-8923-CC does not display the high-end digits. (2
highest digits for an 8 digit display)
Weight value of the CC-link is output even if it exceeds six digits.
When the weight value is stable (the header of the weighing data received is
“ST”), the STABLE indicator turns on.
If the AD-8923-CC does not receive the weighing data for two seconds or
more, - - - - - is displayed (Bar display).
When AD-4212C/D is connected, displays the AD-4212C/D weighing speed
that is currently set, by turning on the weighing speed indicator. When
connected to other instruments, the AD-8923-CC weighing speed indicators
have no function.
2.2. Keys
Used to operate the weighing instruments. For details, refer to “3.4. Operation”.
To enter the function setting of the AD-8923-CC, press the CAL key while
holding down the ON:OFF key.
For details, refer to “4. FUNCTION SETTING”.
2.3. Connectors
RS-232C connector .......... D-Sub 9-pin (male)
Used for connection to the weighing unit. For the proper cable, refer to the
instruction manual for the weighing instrument used.
CC-Link connector ........... 5-pin (male)
Used to connect to other AD-8923-CCs, PLCs or other CC-Link devices. For
details, refer to “6. CC-Link CONNECTOR”.
DC input terminal (24 DCV) / AC adapter input jack
Either power supply can be used. For details, refer to “3.3. Turing the power on”.
Weighing
speed
indicators
Turns on while the weighing
instrument is in the standby
mode.
STABLE indicator
Unit indicator
AD-8923
REMOTE CONTROLLER
ON:OFF
CAL
SAMPLE PRINT
MODE
RE-ZERO
STABLE FAST MID.
RESPONSE
SLOW

8
3. CONNECTION
3.1. Setting the weighing instrument and the AD-8923-CC
Set the following items so that the weighing instrument and the AD-8923-CC
have the same value for each item.
Item Weighing instrument AD-8923-CC
Baud rate 600, 1200, 2400*, 4800, 9600, 19200 bps
Data bits, parity 7 bits EVEN*
Stop bits 1 bit*
Terminator <CR><LF>*
Data format A&D standard format
Communication control No RTS/CTS control
Data output mode Stream mode
* Factory setting for the AD-8923-CC. The factory setting for the AD-4212C
is the same unless otherwise specified.
3.2. Connecting the cables
Connect the cables using the connectors located on the rear of the
AD-8923-CC.
Connection example to the AD-4212C and a PLC
Note
Be sure to ground the AD-4212C and the AD-8923-CC.
PLC
(CC-Link master station)
AD
-
8923
-
CC
RS
-
232C connector (D
-
Sub 9
-
pin)
Connect to the power supply
Refer to “3.3. Turning the power on”.
RS-232C cable
provided with the AD-4212C
CC
-
Link connector (5
-
pin)
Ground
CC
-
Link network
CC-Link network
To other remote stations
such as the AD-8923-CC.
AD
-
4212C
Ground

9
Connection example for the CC-Link network (weighing
instruments No.1 through No.4)
No.1 No.2 No.3 No.4
The value of the terminating resistor varies depending on the CC-Link cable
used.
Use the same resistance value at each end of the network.
Cable FANC-110SBH
Terminating resistor 110 1/2 W
Terminating resistors are not provided.
Connect a terminating resistor
only to the stations at each end
of the network.
AD-8923-CC
AD-4212C
AD-8923-CC
AD-4212C
AD-8923-CC
AD-4212C
CC-Link
master station
AD-8923-CC
AD-4212C
(Ground)
Weighing
instrument

10
When connecting the AD-8923-CC to the CC-Link network using the
connector provided (721-105 / 037-000 equivalent), use the ferrule listed
below (sold separately).
(Example: when using the FANC-110SBH cable)
Insert the cable into the ferrule and crimp it using the Variocrimp4 206-204
crimping jig, and insert it into the connector.
A dual cable connection is also available (not provided).
(Example: when using the FANC-110SBH cable)
Insert the cable into the ferrule and crimp it using the Variocrimp4 206-204
crimping jig, and insert it into the connector.
Connector (provided)
Made by WAGO Corporation
721-105 / 037-000 equivalent
FANC
-
110SBH
Ferrule
Made by WAGO Corporation
216-202W equivalent or
216-202W-L equivalent
D
ual cable
connection connector
Made by WAGO Corporation
721-2105 / 037-000 equivalent
FANC
-
110SBH
Ferrule
Made by WAGO Corporation
216-242 equivalent

11
3.3. Turning the power on
As a power supply, an external 24-VDC power supply (24 VDC±10% / 700mA)
or a 12-VDC AC adapter can be used.
When connected to the following instruments, power can be supplied to both
instruments by plugging the AC adapter into either the weighing instrument or
the AD-8923-CC.
(Both instruments can have their AC adapter connected at the same time.)
Compatible models : AD-4212C / D
When the external 24-VDC power supply is used
Connect an external 24-VDC power supply to the DC input terminal located on
the rear of the AD-8923-CC.
Precautions on using the external power supply
CAUTION
Use a power supply within the rated voltage range (24 VDC±10%).
Never use a power supply with a voltage exceeding the rated range.
It may cause damage or heat buildup.
The AD-8923-CC may not function properly.
Ground the FG terminal of the switching power supply used.
To avoid electrical shock and increase the system safety.
To increase the resistance against noises.
Do not share the power line with other devices.
Strong noises introduced from other devices may cause damage to the
AD-8923-CC.
Inrush current from other devices may cause the AD-8923-CC not to start up
properly.
Circuit configuration of the AD-8923-CC may affect other devices to
prevent them from functioning properly.
Select a switching power supply with a capacity of approximately 700mA for
each AD-8923-CC. Note that the AD-8923-CC may not start up with a
capacity less than 700mA.
If the power supply capacity is not sufficient, the AD-8923-CC may not function
properly.

12
Be sure to add a noise filter on the front end of the switching power supply
and ground the FG terminal.
This will increase the resistance against noises.
Be sure to ground the FG terminal of the AD-8923-CC and weighing
instruments.
This will increase the resistance against noises.
Cable connection
CAUTION
Before inserting the power line, make sure that the power to the
AD-8923-CC is turned off.
(1) Inserting the power line
Press down the release button on
the DC input terminal using a
screwdriver and insert the power
line.
The recommended stripping
length for the power line is 10 mm.
Applicable wire range
Single wire: 1.0 mm (AWG 26) to 1.2 mm (AWG 16)
Twisted wire: 0.3 mm2 (AWG 22) to 0.75 mm2 (AWG 20)
Individual wire diameter 0.18 mm or greater
(2) Securing or removing the power line
To secure the power line, return the release button to the initial position
using the screwdriver. The power line will be locked.
To remove the power line, press the release button again using the
screwdriver, unlocking the power line.
When the AC adapter is used
Insert the AC adapter plug into the
AC adapter input jack located on the
rear of the AD-8923-CC and insert
the AC adapter into an electrical
outlet.
DC input
terminal
AD-8923-CC rear
Release button
Screwdriver
Power line
AC adapter input jack
DC input terminal
AC adapter plug
AD-8923-CC rear

13
3.4. Operation
Displays the data transmitted by the weighing instrument connected.
The keys on the AD-8923-CC can control the weighing instrument. The key
operation depends on the weighing instrument connected. For details, refer
to “Table 2” of “1-2 Applicable Instruments”.

14
3.5. Calibrating the AD-4212C
The following is the calibration procedure when the AD-4212C is connected.
(A calibration weight is used.)
Caution
Do not allow vibration, drafts or temperature change to affect the AD-4212C
during calibration.
Caution on using an external calibration weight
The accuracy of the weight can influence the accuracy of weighing.
Select an appropriate weight as listed below.
A calibration weight of 200 g is provided with the AD-4212C as a standard
accessory.
Weighing instrument Usable calibration weight
AD-4212C-300 50g, 100g,
200 g
,
300g
AD-4212C-600 50g, 100g,
200 g
,
300g, 400 g, 500 g, 600 g
AD-4212C-3000 50g, 100g,
200 g
, 300g, 400 g, 500 g, 1000 g, 2000g, 3000g
AD-4212C-6000
200 g
, 500 g, 1000 g, 2000g, 3000g, 4000 g, 5000 g, 6000 g
The calibration weight in bold type: factory setting
Display
This indicator means “the AD-4212C is measuring
calibration data”. Do not allow vibration, drafts or other
external disturbances to affect AD-4212C while this
indicator is displayed.

15
Calibration procedure
Calibrates the AD-4212C using the calibration weight.
Operation
1. Warm up the AD-4212C for 30 minutes or more with
nothing on the pan.
2. Press the CAL key. Cal 0 is displayed.
If you want to cancel calibration, press the CAL key.
The display will return to the weighing mode.
If you want to change the calibration weight value,
press the SAMPLE key.
Press the RE-ZERO key to select the weight value,
and press the PRINT key to store it. Cal 0 is
displayed.
3. Confirm that there is nothing on the pan and press the
PRINT key. The AD-4212C measures the zero point.
Do not allow vibration or drafts to affect the
AD-4212C.
The calibration weight value is displayed.
4. Place a calibration weight, of the weight value
displayed, on the pan and press the PRINT key.
The AD-4212C measures the calibration weight.
Do not allow vibration or drafts to affect the
AD-4212C.
5. end is displayed. Remove the weight from the pan.
6. The display will automatically return to the weighing
mode.
7. Place the calibration weight on the pan and confirm
that calibration was performed correctly. If not, check
the ambient conditions such as drafts or vibration,
and repeat steps 2 through 7.
* It is also possible to carry out a calibration described
above using the register of the CC-Link.
For details, refer to “6.4. Calibration with the AD-4212C using the register of the
CC-Link”.
Press
C
alibration
weight
Press
Press
STABLE FAST MID.
RESPONSE
SLOW
CAL
STABLE FAST MID.
RESPONSE
SLOW
PRINT
STABLE FAST MID.
RESPONSE
SLOW
STABLE FAST MID.
RESPONSE
SLOW
PRINT
STABLE FAST MID.
RESPONSE
SLOW
STABLE FAST MID.
RESPONSE
SLOW
STABLE FAST MID.
RESPONSE
SLOW

16
4. FUNCTION SETTING
Function setting specifies the AD-8923-CC performance. The parameters are
stored in non-volatile memory, and are maintained even if the power line or AC
adapter is removed.
The function setting menu consists of two layers. The first layer is the “Class”
and the second layer is the “Item”. Each item stores a parameter.
Press the SAMPLE key to select an item and press the RE-ZERO key to
change the parameter. Then, press the PRINT key to store the new
parameter.
Example
This example sets “Baud rate” to “9600 bps”.
Note
The AD-8923-CC may not function properly, depending on the settings
and operating environment. Check the settings and change them as
necessary.

17
4.1. Display and keys
The STABLE indicator turns on to indicate that the parameter displayed is in effect.
Selects a class or item.
Changes the parameter.
When a class is displayed, moves to an item in the class.
When an item is displayed, stores the new parameter and displays the
next class.
When an item is displayed, cancels the new parameter and displays the
next class.
When a class is displayed, exits the function setting mode and returns to
the weighing mode.
4.2. Function table
Class Item and Parameter Description
fnc
Environment
Display
dpp
Decimal point
position
- Not fixed
Displays the decimal point position of the
weighing data received.
0
Fixed
Fixes the decimal point at the set digit.
Even if the minimum display is switched
using the SAMPLE key, the decimal point
position does not change. For details,
refer to “6.3. Fixed decimal point position.”
5
5apl
Sample key
function
0 Disabled
Disables the SAMPLE key function.
1 Enabled
Enables the SAMPLE key function.
5if
Serial
interface
bp5
Baud rate
0 600 bps
Set the same value as that of the
weighing instrument to be connected.
1 1200 bps
2 2400 bps
3 4800 bps
4 9600 bps
5 19200 bps
CCl
CC-Link
interface
n5t
Number of
station
1
64
Number of
station
C-bp
CC-Link
baud rate
0 156 Kbps
Set the same value as that of the
CC-Link master station to be
connected
1
625 Kbps
2 2.5 Mbps
3 5 Mbps
4 10 Mbps
Factory setting

18
4.3. Initializing the AD-8923-CC
Initialization restores the function settings of the AD-8923-CC to factory
settings.
Operation
1 Turn the power on. - - - - - or weighing
mode display appears.
2 While holding down the ON:OFF key, press
the PRINT key. Clr is displayed.
3 Press the PRINT key.
To cancel this operation, press the CAL key
4 Press the RE-ZERO key to select “go”.
5 Press the PRINT key to perform initialization.
After initialization, - - - - - or weighing
mode display appears.
.
ON:OFF
PRINT
PRINT
RE-ZERO
PRINT
Press
While holding
down
Press
Press
Press

19
9876
(Va)
(Vs)
SG
TXD
RXD
(CTS)
(RTS)
(DSR)
5 4 3 2 1
AD-8923-CC
interior
Inch screw
(#4-40UNC)
To the weighing instrument
5. RS-232C CONNECTOR
5.1. RS-232C serial interface specifications
RS-232C
Transmission system
: EIA RS-232C
Transmission form : Asynchronous, bi-directional, half duplex
Data format : Baud rate : 600, 1200, 2400, 4800, 9600, 19200 bps
Data bits : 7 or 8 bits
Parity : EVEN, ODD (Data bits 7 bits)
NONE (Data bits 8 bits)
Stop bits : 1 bit or 2 bits
Code : ASCII
Terminator: <CR> or <CR><LF>
Circuit
Connection to the weighing instrument
D-Sub 9-pin male
Pin
No.
Signal
name
Direction
Description
1 (Vs) Used internally
2 RXD Input Receive data
3 TXD Output
Transmit data
4 N.C.
5 SG Signal ground
6 (DSR)
Used internally
7 (RTS)
Used internally
8 (CTS)
Used internally
9 (Va) Used internally
Note
When the user prepares a cable, do not connect to the pins that are
used internally.
(The AD-8923-CC is a DTE device.
Connect to a DCE device such as the
weighing instruments using a straight
through cable.)

20
6. CC-Link CONNECTOR
The AD-8923-CC CC-Link is a remote device station of CC-Link ver.1.10.
When a CC-Link is used, the AD-8923-CC can be controlled by the PLC
remote I/O or remote registers. So, the program can be simple. And
connection to a PLC is simple, thus, a weighing system can be built easily.
The setting values of CC-Link are changed in the function setting CCl.
6.1. CC-Link interface specifications
Number of station 1 to 64
Baud rate 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps
Communications connector
The connector used can be attached or removed while the power is ON.
The function of each signal line is as follows.
DA Signal DA
DB Signal DB
DG Signal ground
SLD Shield
FG Frame ground
Status LEDs
LED ON OFF Blinking
RUN Normal Resetting
No signal
SD Transmitting
RD Receiving
ERR
Setting error
CRC error
Station trouble
Normal When the setting
values are changed
CC-Link connector and LEDs